Outdoor three-phase air switches<br />
NPS modular <strong>outdoor</strong> switch disconnectors<br />
−−Modular and flexible design adapts to various pole types for<br />
mounting<br />
−−Robust, light weight makes installation easier and safer<br />
−−Wide range of accessories for various applications<br />
−−Easy to upgrade from manual switch to remote controlled/<br />
automated switch<br />
−−Simple design provides reliable operation<br />
Technical data<br />
Rated maximum voltage kV 24 24 24 36 36<br />
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60<br />
Rated continuous current A 630 630 630 630 630<br />
Rated short time withstand current (1 sec) kA 16 16 20 21 21<br />
Rated short time withstand current (3 sec) kA 10 10 16 16 16<br />
Rated peak withstand current kA 40 40 50 52 52<br />
Rated short circuit making current kA 5 5 5 7.5 7.5<br />
with standard whip (at 12/24/36kV) A 25 1 25 1 25 1 16 16<br />
Mainly active load<br />
breaking current<br />
with chamber K4 fitted (at 24kV) A 250 – – – –<br />
with chamber K5 fitted (at 24 kv) A 630 630 630 – –<br />
Rated lightning impulse withstand (BIL) kV 125 125 125 200 200<br />
Rated power frequency across the isolating distance kV 75 75 75 88 88<br />
withstand voltage, wet to earth and between phases kV 55 55 55 80 80<br />
Insulators Epoxy Silicon Silicon Silicon Silicon<br />
Creepage distance to earth mm (inch) 740 (29.10) 2 715 (28.15) 3 760 (29.90) 3 1205 (47.41) 3 1365 (53.70) 3<br />
Arcing distance mm (inch) 200 (7.90) 255 (10.00) 260 (10.20) 380 (14.95) 385 (15.15)<br />
Ambient temperature limits C -50…+40 -40…+40 -40…+40 -40…+40 -40…+40<br />
Control voltage for motor drive (if fitted) V 24, 48, <strong>11</strong>0, 220 VDC <strong>11</strong>0, 230 VAC<br />
Standard type of control unit used in motor drives REC523 or REC5<strong>01</strong> 4<br />
Standard tested to: IEC 60694 , 6<strong>01</strong>29, 60265-1.<br />
1)<br />
40 A for 12 kV.<br />
2)<br />
Epoxy insulators version.<br />
3)<br />
Silicon insulators version.<br />
4)<br />
For the details about REC523 control unit used in motor drives see page 17.<br />
1 NPS cabinet | 2 GridGuard TM cabinet (page 15)<br />
1 2<br />
14 Outdoor three-phase air switches | ABB Medium Voltage Products