General product <strong>cataloge</strong><br />
ABB Medium Voltage Products<br />
Outdoor <strong>apparatus</strong>
Contents<br />
Introduction<br />
04 This is ABB<br />
05 The one-shop service for all your medium voltage needs<br />
Outdoor dead tank circuit breakers<br />
06 R-MAG magnetically actuated <strong>outdoor</strong> vacuum circuit breaker<br />
Outdoor live tank circuit breakers<br />
07 OVB-SDB <strong>outdoor</strong> vacuum circuit breaker<br />
08 OVB-VBF <strong>outdoor</strong> vacuum circuit breaker<br />
Reclosers<br />
09 OVR-1 single-phase solid dielectric recloser<br />
10 OVR-3 three-phase solid dielectric recloser<br />
<strong>11</strong> OVR-3SP three-phase solid dielectric recloser<br />
12 PCD control for OVR-3 and OVR-3SP three-phase solid dielectric recloser<br />
Pole mounted circuit breaker<br />
13 PVB pole mounted vacuum circuit breaker<br />
Outdoor three-phase air switches<br />
14 NPS modular <strong>outdoor</strong> switch disconnectors<br />
15 GridGuard three-phase <strong>outdoor</strong> air switch<br />
2 Contents | ABB Medium Voltage Products
Outdoor three-phase load break switches<br />
16 SECTOS 24kV NXB and NXBD SF6 load break switch<br />
<strong>18</strong> SECTOS 36kV NXA SF6 load break switch<br />
Electronic sectionalizers<br />
20 AutoLink single-phase electronic sectionalizer<br />
21 AutoLink three-phase electronic sectionalizer<br />
22 AutoLink loadbreak electronic sectionalizer<br />
Single-phase switches<br />
23 DCD single-phase disconnect switch<br />
24 SID single-phase disconnect switch<br />
25 LSID single-phase load break disconnect switch<br />
26 RBD single-phase bypass disconnect switch<br />
27 ITD inline tension disconnect switch<br />
Fuse cutouts<br />
28 ICX interchangeable fuse cutout<br />
29 NCX fuse cutout<br />
30 LBU-II loadbreak fuse cutout<br />
Instrument transformers<br />
31 Outdoor ANSI medium voltage instrument transformers<br />
32 Outdoor IEC medium voltage instrument transformers<br />
Service<br />
33 Reliable, trouble-free and efficient operation<br />
ABB Medium Voltage Products | Contents 3
Introduction<br />
This is ABB<br />
ABB is a global leader in power and<br />
automation technologies that enable<br />
utility and industry customers to improve<br />
their performance while <strong>low</strong>ering<br />
environmental impact.<br />
Our group comprises five main divisions:<br />
−−Power Products<br />
−−Power Systems<br />
−−Discrete Automation and Motion<br />
−−Low Voltage Products<br />
−−Process Automation<br />
Sustainability<br />
Sustainability is integral to all aspects of ABB’s business<br />
so we aim to balance economic success, environmental<br />
stewardship and social prog<strong>res</strong>s to benefit all our<br />
stakeholders.<br />
Sustainability considerations cover how we design and<br />
manufacture products, what we offer customers, how we<br />
engage suppliers, how we assess risks and opportunities, and<br />
how we behave in the communities where we operate and<br />
towards one another. We also strive for excellence in health<br />
and safety performance.<br />
Technology<br />
Technology plays a key role for ABB. We have nine <strong>res</strong>earch<br />
centers, 6,000 scientists and 70 university collaborations<br />
across the world – all working to develop unique technologies<br />
that make our customers more competitive and efficient while<br />
minimizing impact on the environment.<br />
Where to find us<br />
ABB operates in more than 100 countries and we have offices<br />
in 87 of those countries to provide the support our global and<br />
local customers need to develop and conduct their business<br />
successfully.<br />
4 Introduction | ABB Medium Voltage Products
Introduction<br />
The one-shop service for all your medium voltage needs<br />
With ABB, you can meet all your requirements for medium<br />
voltage products and systems from a single supplier.<br />
We have over 100 years of experience in the design,<br />
development, manufacturing and through-life service<br />
support of medium voltage switchgear, and the largest<br />
installed base of any manufacturer worldwide.<br />
Whatever your application – utility, industrial, transportation or<br />
commercial – we can provide the perfect, coordinated solution<br />
that delivers maximum efficiency, reliability and safety. Our<br />
comprehensive medium voltage portfolio covers switchgear,<br />
<strong>apparatus</strong>, modular packages and distribution automation.<br />
Thanks to ABB’s global service network, we support our<br />
products and systems through a comprehensive range<br />
of services that ensure optimum performance throughout<br />
their life – from installation and commissioning through<br />
routine maintenance, retrofit and upgrades to eventual<br />
decommissioning.<br />
Quality systems<br />
ABB operates the very highest global, national and<br />
industry-specific quality standards including ISO 90<strong>01</strong>. Our<br />
environmental management systems conform to ISO 140<strong>01</strong><br />
and our health and safety management system conforms to<br />
OHSAS <strong>18</strong>0<strong>01</strong>.<br />
A wide range of applications<br />
ABB’s medium voltage equipment serves a wide variety of<br />
applications throughout the world including:<br />
−−Utility generation<br />
−−Utility transmission<br />
−−Utility distribution<br />
−−Transportation<br />
−−Heavy industrial process plant<br />
−−Mining and mineral processing<br />
−−Light industrial parks<br />
−−Hospitals<br />
Product portfolio<br />
ABB offers a wide range of medium voltage products for<br />
primary and secondary distribution applications, conforming<br />
to IEC standards as well as those of the major industrialized<br />
countries, including:<br />
−−Circuit breakers<br />
−−Switch disconnectors<br />
−−Contactors<br />
−−Fixed parts and enclosu<strong>res</strong><br />
−−Distribution switchgear<br />
−−Protection relays and control systems<br />
−−Substation automation<br />
−−Electrical distribution substations<br />
−−A comprehensive range of accessories<br />
ABB Medium Voltage Products | Introduction 5
Outdoor dead tank circuit breakers<br />
R-MAG magnetically actuated<br />
<strong>outdoor</strong> vacuum circuit breaker<br />
−−Reduced maintenance costs<br />
– 10,000 mechanical operations (five times ANSI<br />
requirements)<br />
– Maintenance free magnetic actuator<br />
– Eliminates need to replace motors, trip and close coils<br />
– Vacuum interruption<br />
−−Definite purpose capacitor switching in accordance with ANSI<br />
C37.06<br />
−−15.5 – 27 kV, up to 3700 A, 25 kA<br />
−−38 kV, up to 2000 A, 31.5 kA<br />
Technical data<br />
R-MAG<br />
Rated maximum voltage kV 15.5 15.5 15.5 27 27 27 38<br />
Continuous current A<br />
800/1250 800/1250/<br />
2000<br />
800/1250/2000/ 1250 1250/2000 1250/2000 1250/2000<br />
3000 1 /3700 2<br />
Operating temperature -50 °C and 70 °C per IEC 62271-100 3<br />
Voltage range factor K 1 1 1 1 1 1 1<br />
Short circuit interrupting current<br />
(at contact part) kA, RMS, Sym<br />
kA 12.5 20 25 12.5 20 25 31.5<br />
Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60<br />
Power frequency withstand dry 60 Hz for 1 min kV 50 50 50 60 60 60 80<br />
Power frequency withstand wet 60 Hz for 10 sec kV 45 45 45 50 50 50 75<br />
Lightning impulse withstand (BIL) kV <strong>11</strong>0 <strong>11</strong>0 <strong>11</strong>0 125/150 125/150 125/150 200<br />
Chopped wave withstand (kV peak) kV 142 142 142 194 ∆ 194 ∆ 194 ∆ 258<br />
Operating duty (standard duty cycle) cycles Exceeds ANSI standard O-0.3 sec-CO-3 min-CO<br />
Maximum interrupting time cycles 3 3 3 3 3 3 3<br />
Permissible tripping delay Y sec 2 2 2 2 2 2 2<br />
Closing time cycles 6 6 6 6 6 6 6<br />
Reclosing time sec 0.3 0.3 0.3 0.3 0.3 0.3 0.3<br />
Short circuit interrupting current (at contact part) kA,<br />
RMS, Sym<br />
kA 12.5 20 25 12.5 20 25 31.5<br />
Close and latch (initial current loop) kA, RMS, Asym kA 20 32 40 20 32 40 50.4<br />
Close and latch (kA peak) kA 32.5 52 65 32.5 52 65 81.9<br />
Short time current (3 sec) kA, RMS, Sym kA 12.5 20 25 12.5 20 25 31.5<br />
Rated duration of short-circuit @ short-time current sec 3 3 3 3 3 3 2<br />
Transient recovery voltage (kV Peak) kV 29 29 29 51 51 51 71.7<br />
Load current switching capability A 600/800/<br />
1250<br />
600/800/<br />
1250/2000<br />
600/800/1250/<br />
2000/3000<br />
1250 1250/2000 1250/2000 1250/2000<br />
Wire line charging current A 100 100 100 100 100 100 100<br />
Isolated cable charging current A 600 600 600 400 400 400 600<br />
Isolated capacitor bank switching current (A RMS) A 600 600 600 600 600 600 600<br />
Back-to-back shunt capacitor bank switching<br />
current (A RMS)<br />
A 600 600 600 600 600 600 600<br />
Transient overvoltage factor C1* C1* C1* C1*<br />
Transient inrush current (kA peak) back-to-back A 20 20 20 20 20 20 20<br />
Transient inrush frequency (Hz) back-to-back Hz 4240 4240 4240 4240 4240 4240 4240<br />
Grounding of system and capacitor bank system<br />
Grounded or ungrounded<br />
Capacitor bank<br />
Grounded or ungrounded<br />
Mechanical life (no load operations) 10000 10000 10000 10000 10000 10000 10000<br />
1<br />
Up to 3000 A standard breaker. 2 3700 A forced air cooled breaker. 3 Above 40°C breaker derated per ANSI C37.<strong>01</strong>0. * Per C37.09a <strong>res</strong>trike category. ∆ For 150 kV BIL full-wave rating only.<br />
<br />
Interrupter life rated for 30,000 operations when interrupting loads are less than 1 kA.<br />
6 Outdoor dead tank circuit breakers | ABB Medium Voltage Products
Outdoor live tank circuit breakers<br />
OVB-SDB <strong>outdoor</strong> vacuum circuit breaker<br />
Long life and less maintenance<br />
Available with simple spring mechanism or magnetic actuator:<br />
−−Spring mechanism certified for 10,000 mechanical<br />
operations<br />
−−Magnetic actuator rated for 10,000 mechanical operation:<br />
eliminates need to replace motors, trip and close coils<br />
Reliability and safe operation<br />
−−Long electrical life with proven ABB vacuum interrupters<br />
that utilize excellent arc quenching properties<br />
−−Simple and reliable spring mechanism ensu<strong>res</strong> longer life;<br />
tested for 10,000 mechanical operations<br />
−−Optional magnetic actuator eliminates maintenance on<br />
operating mechanism<br />
Availability and certifications<br />
−−Suitable for auto reclosing duty cycle and capacitor<br />
switching duty: type tested as per latest IEC 62271-100,<br />
M2 and C2 Class<br />
−−Ease of installation and commissioning with telescopic<br />
mounting structure<br />
−−Various accessories available to meet most applications<br />
Technical data OVB-SDB 12.08.13 OVB-SDB 12.12.20 OVB-SDB 12.20.25<br />
Rated voltage kV 12 12 15<br />
Power frequency withstand voltage kV rms 28 28 35<br />
Impulse withstand voltage kV (peak) 75* 75* 95<br />
Rated frequency Hz 50 50 50<br />
Creepage distance to earth mm 450** 450** 450**<br />
Rated normal current A 800 1250 2000<br />
Rated breaking current kA 13.1 20 26.3<br />
Rated short time withstand current kA for 3 sec 13.1 20 26.3<br />
Rated making current kA peak 33 50 65.75<br />
First pole to clear factor 1.5 1.5 1.5<br />
Duty cycle<br />
Standard tested to: IEC 62271-100.<br />
* 95 kV (peak) available on request.<br />
** Higher creepage distance available on request.<br />
O-0.3 sec – CO – 3 min – CO/<br />
CO – 15 sec – CO<br />
O-0.3 sec – CO – 3 min – CO/<br />
CO – 15 sec – CO<br />
O-0.3 sec – CO – 3 min – CO/<br />
CO – 15 sec – CO<br />
No. of breaks per pole 1 1 1<br />
Weight (approx.) kg 500 500 500<br />
ABB Medium Voltage Products | Outdoor live tank circuit breakers 7
Outdoor live tank circuit breakers<br />
OVB-VBF <strong>outdoor</strong> vacuum circuit breaker<br />
Long life and less maintenance<br />
−−Vacuum switching for higher short circuit operations<br />
−−Simple spring mechanism certified for 10,000 mechanical<br />
operations<br />
Reliability and safe operation<br />
−−Long electrical life with proven ABB vacuum interrupters<br />
that utilize excellent arc quenching properties<br />
−−Simple and reliable spring mechanism ensu<strong>res</strong> longer life:<br />
tested for 10,000 mechanical operations<br />
Availability and certifications<br />
−−Suitable for auto reclosing duty cycle and capacitor<br />
switching duty; type tested as per latest IEC 62271-100,<br />
M2 and C2 Class<br />
−−Ease of installation and commissioning with telescopic<br />
mounting structure<br />
−−Various accessories available to meet most applications<br />
Technical data OVB-VBF 36.20.25 OVB-VBF 40.25.32<br />
Rated voltage kV 36 40.5<br />
Power frequency withstand voltage kV rms 70 95<br />
Impulse withstand voltage kV (peak) 170* 195*<br />
Rated frequency Hz 50 50/60<br />
Creepage distance to earth mm 900** <strong>11</strong>16<br />
Rated normal current A 2000 2500<br />
Rated breaking current kA 26.3 31.5<br />
Rated short time withstand current kA for 3 sec 26.3 31.5<br />
Rated making current kA peak 65.75 82<br />
First pole to clear factor 1.5 1.5<br />
Duty cycle<br />
O-0.3 sec – CO – 3 min – CO/<br />
CO – 15 sec – CO<br />
O-0.3 sec – CO – 3 min – CO/<br />
CO – 15 sec – CO<br />
No. of breaks per pole 1 1<br />
Weight (approx.) kg 850 900<br />
Standard tested to IEC 62271-100.<br />
* 200 kV (peak) available on request.<br />
** Higher creepage distance available on request.<br />
8 Outdoor live tank circuit breakers | ABB Medium Voltage Products
Reclosers<br />
OVR-1 single-phase solid dielectric recloser<br />
−−Solid dielectric recloser utilizing ABB vacuum interrupters<br />
−−Long life and <strong>low</strong> maintenance with 10,000 operations<br />
−−No electronics in pole assembly provides increased<br />
reliability and less maintenance<br />
−−Solid dielectric insulation with HCEP for enhanced reliability<br />
and increased life expectancy<br />
−−Electromechanical counter is standard<br />
ICD single phase recloser control<br />
−−AC powered electronic control eliminates battery<br />
maintenance<br />
−−Optional battery backup available<br />
−−Available under voltage trip/<strong>res</strong>tore function – reduces the<br />
effects of cold load pick-ups<br />
−−Zone sequence coordination<br />
−−Al<strong>low</strong>s for seamless communication integration with<br />
SCADA, modem and radio systems<br />
Technical data<br />
OVR-1<br />
Nominal operating voltage kV 2.4 – 14.4 24.9<br />
Rated maximum voltage kV 15.5 27<br />
Rated power frequency 50/60 50/60 50/60 Hz Hz 50/60 50/60<br />
Rated continuous current A 630/800 630/800<br />
Rated symmetrical interrupting current 10 12<br />
Rated lightning impulse withstand (BIL) kV <strong>11</strong>0/125 125<br />
Dry withstand 60 Hz 1 min. kV 50 60<br />
Wet withstand 60 Hz 10 sec. kV 45 50<br />
Phase spacing mm (inch) 394 (15.5) 394 (15.5)<br />
External creep distance, H2-ground mm (inch) 960 (38.00) 960 (38.00)<br />
Minimum external strike distance mm (inch) 240 (9.50) 240 (9.50)<br />
Maximum interrupting time sec 0.04 0.03<br />
Maximum closing time sec 0.06 0.055<br />
Operating temperature C -40 + 70 (-40 ºF to + 158 ºF)<br />
Control voltage V 120/240 VAC<br />
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-<strong>11</strong>1.<br />
ABB Medium Voltage Products | Reclosers 9
Reclosers<br />
OVR-3 three-phase solid dielectric recloser<br />
Advanced technology<br />
−−Solid dielectric recloser – ABB vacuum interrupters and<br />
sensors embedded in each recloser pole<br />
−−HCEP insulation material ensu<strong>res</strong> improved reliability and<br />
life expectancy<br />
−−Modular pole and actuator assembly – al<strong>low</strong>s easy removal<br />
in the field<br />
−−Magnetic actuator per phase – al<strong>low</strong>s for single phase<br />
tripping capability<br />
Reduced maintenance costs<br />
−−No electronics in high voltage recloser cabinet – reduced<br />
maintenance costs<br />
−−Modular PCD control – ability to replace and upgrade<br />
individual control cards without removing the relay<br />
Reliability and increased life<br />
−−Superior life – rated for 10,000 operations<br />
−−Grade 304 stainless steel cabinet<br />
−−3 year warranty<br />
Technical data<br />
OVR-3<br />
Nominal operating voltage kV 2.4-14.4 24.9 34.5<br />
Rated maximum voltage kV 15.5 27 38<br />
Rated power frequency 50/60 50/60 50/60 Hz Hz 50/60 50/60 50/60<br />
Rated continuous current A 630/800/1200 630/800/1200 630/800/1200<br />
Rated symmetrical interrupting current kA 12.5 12.5 16<br />
Rated lightning impulse withstand (BIL) kV <strong>11</strong>0/125 125 150/170<br />
Dry withstand 60 Hz 1 min. kV 50 60 70<br />
Wet withstand 60 Hz 10 sec. kV 45 50 60<br />
Phase spacing mm (inch) 394 (15.5) 394 (15.5) 394 (15.5)<br />
External creep distance, H2-ground mm (inch) 960 (38) 960 (38) 1288 (50.70)<br />
External creep distance, H1-H2 mm (inch) <strong>11</strong>60 (45) <strong>11</strong>60 (45) 1260 (49.80)<br />
Minimum external strike distance mm (inch) 240 (9.5) 240 (9.5) 367 (14.4)<br />
Maximum interrupting time sec 0.03 0.03 0.03<br />
Maximum closing time sec 0.055 0.055 0.044<br />
Operating temperature C -40 – 70 (-40 ºF to 158 ºF)<br />
Control voltage V 90 – 265 VAC / 125 DC<br />
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-<strong>11</strong>1.<br />
10 Reclosers | ABB Medium Voltage Products
Reclosers<br />
OVR-3SP three-phase solid dielectric recloser<br />
Advanced technology<br />
−−Individual pole design al<strong>low</strong>s flexible mounting<br />
arrangements<br />
– Phase-over-phase/Wrap-around/Cross arm<br />
– Substation replacement of small profile devices<br />
– Seamless transition for replacement of three hydraulic<br />
units<br />
−−One PCD control operates all three recloser poles<br />
– Available in rack mount design for substation mounting<br />
or in standard cabinet<br />
−−Solid dielectric recloser – ABB vacuum interrupters and<br />
sensors embedded in each recloser pole<br />
−−HCEP insulation material ensu<strong>res</strong> improved reliability and<br />
life expectancy<br />
−−Modular pole and actuator assembly – al<strong>low</strong>s easy removal<br />
in the field<br />
−−Magnetic actuator per phase – al<strong>low</strong>s for single phase<br />
tripping capability<br />
Reduced maintenance costs<br />
−−No electronics in high voltage recloser – reduced<br />
maintenance costs<br />
−−Modular PCD control – ability to replace and upgrade<br />
individual control cards without removing the relay<br />
Reliability and increased life<br />
−−Superior life – rated for 10,000 operations<br />
−−Grade 304 stainless steel control cabinet<br />
−−3 year warranty<br />
Technical data<br />
OVR-3<br />
Nominal operating voltage kV 2.4 – 14.4 24.9 34.5<br />
Rated maximum voltage kV 15.5 27 38<br />
Rated power frequency 50/60 50/60 50/60 Hz Hz 50/60 50/60 50/60<br />
Rated continuous current A 630/800/1200 630/800/1200 630/800/1200<br />
Rated symmetrical interrupting current kA 12.5 12.5 16<br />
Rated lightning impulse withstand (BIL) kV <strong>11</strong>0/125 125 150/170<br />
Dry withstand 60 Hz 1 min. kV 50 60 70<br />
Wet withstand 60 Hz 10 sec. kV 45 50 60<br />
Phase spacing mm (inch) 394 (15.5) 394 (15.5) 394 (15.5)<br />
External creep distance, H2-ground mm (inch) 960 (38.00) 960 (38.00) 1288 (50.70)<br />
External creep distance, H1-H2 mm (inch) <strong>11</strong>60 (45.00) <strong>11</strong>60 (45.00) 1260 (49.80)<br />
Minimum external strike distance mm (inch) 240 (9.50) 240 (9.50) 367 (14.4)<br />
Maximum interrupting time sec 0.03 0.03 0.03<br />
Maximum closing time sec 0.055 0.055 0.044<br />
Operating temperature C -40 – 70 (-40 ºF to 158 ºF)<br />
Control voltage V 90 – 265 VAC / 125 DC<br />
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-<strong>11</strong>1.<br />
ABB Medium Voltage Products | Reclosers <strong>11</strong>
Reclosers<br />
PCD control for OVR-3 and OVR-3SP three-phase solid<br />
dielectric recloser<br />
Protection<br />
Phase and ground overcurrent protection, sensitive earth fault<br />
(SEF), directional phase and ground current protection, under<br />
– overvoltage protection, frequency protection, breaker failure<br />
protection, cold load supervision.<br />
Control featu<strong>res</strong><br />
−−Local programming from HMI; Remote control from SCADA<br />
using Modbus ASCII and RTU, DNP 3.0, IEC 60870-1<strong>01</strong><br />
protocols<br />
−−Modular PCD control design al<strong>low</strong>s for easy upgrades and<br />
simple, fast troubleshooting by replacing any of the six<br />
backwards compatible cards – no need to replace entire<br />
control<br />
−−Up to 48-hour backup power during loss of source<br />
power with ability to operate on AC only – without battery<br />
assistance<br />
−−Recloser up to 4 automatic shots<br />
Condition monitoring<br />
−−Monitors individual pole operations and battery condition<br />
−−Recloser counters for each reclose shot<br />
−−KSI sum for each phase: counters based on how much fault<br />
is interrupted for each recloser trip<br />
Metering<br />
−−Measu<strong>res</strong> kW and kVARh, power factor, demand Watts and<br />
VARs, and frequency to ±2% accuracy<br />
−−Power quality such as sag, swell<br />
Data capture<br />
−−Fault summary and operations record: PCD provides a<br />
summary for the last 128 faults including tripping element,<br />
date and time, phase and neutral currents, active setting<br />
group when fault occurred and captu<strong>res</strong> the last 1024<br />
operations<br />
Load profile records: PCD has a load profile that sto<strong>res</strong><br />
historical load data such as kW on each phase, kVAR on each<br />
phase, voltages and currents on each phase, power factor<br />
Reliability improvements<br />
−−Single phase tripping reduces unnecessary three-phase<br />
interruptions and outages due to single-phase faults<br />
−−Voltage based loop control schemes to coordinate multiple<br />
reclosers to sectionalize or remove faulted sections from a<br />
distribution system<br />
−−Al<strong>low</strong>s an OVR recloser to act as a sectionalizer, midpoint,<br />
or tie without physical connections to other reclosers<br />
−−Remote communication capability – licensed and unlicensed<br />
radios, Web IP radios, GSM/Cellular and digital packet data<br />
12 Reclosers | ABB Medium Voltage Products
Pole mounted circuit breaker<br />
PVB pole mounted vacuum circuit breaker<br />
−−Solid dielectric breaker – ABB vacuum interrupters<br />
embedded in each pole<br />
−−HCEP insulation material ensu<strong>res</strong> improved reliability and<br />
life expectancy<br />
−−Long creepage distance (392 mm) – suitable for highly<br />
polluted environments<br />
−−Spring operating mechanism with anti-pumping function –<br />
modular design and maintenance free<br />
−−Reflective position and charge indicators are easily visible<br />
from ground, even at night<br />
−−Easily upgraded from manual operated to motor operated<br />
and remote control<br />
−−Mounting flexibility – various mounting brackets are<br />
available for customer application requirements<br />
−−Superior life – rated for 10,000 operations<br />
−−Three options of protection and control unit<br />
– MFC: Provides overcurrent protection, no extra power<br />
required<br />
– REF615: Provides overcurrent protection and earth fault<br />
protection, with optional recloser function<br />
– PCD: Provides full protection for current and voltage<br />
faults, with advanced measurement, recloser and<br />
communication<br />
Technical data<br />
PVB<br />
Nominal operating voltage kV 10<br />
Rated maximum voltage kV 12<br />
Rated power frequency Hz 50/60<br />
Rated continuous current A 630<br />
Rated symmetrical interrupting current kA 20<br />
Rated lightning impulse withstand (BIL) kV 75<br />
Dry withstand 50/60 Hz 1 min. kV 42<br />
Wet withstand 50/60 Hz 10 sec. kV 34<br />
Phase spacing mm (inch) 280 (<strong>11</strong>.02)<br />
External creep distance, H2-ground mm (inch) 392 (15.43)<br />
External creep distance, H1-H2 mm (inch) 392 (15.43)<br />
Minimum external strike distance mm (inch) 230 (9.05)<br />
Rated standard operating duty O – 0.3s – C O – 15s – C O*<br />
Maximum interrupting time sec 0.08<br />
Maximum closing time sec 0.08<br />
Operating temperature C -40 (-25 if motor operated) to +40<br />
Control voltage V <strong>11</strong>0 – 220 VAC / 24 – 220 VDC<br />
Standard tested to: GB 1984-2003 and IEC 62271-100.<br />
* For motor operation.<br />
ABB Medium Voltage Products | Pole mounted circuit breaker 13
Outdoor three-phase air switches<br />
NPS modular <strong>outdoor</strong> switch disconnectors<br />
−−Modular and flexible design adapts to various pole types for<br />
mounting<br />
−−Robust, light weight makes installation easier and safer<br />
−−Wide range of accessories for various applications<br />
−−Easy to upgrade from manual switch to remote controlled/<br />
automated switch<br />
−−Simple design provides reliable operation<br />
Technical data<br />
Rated maximum voltage kV 24 24 24 36 36<br />
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60<br />
Rated continuous current A 630 630 630 630 630<br />
Rated short time withstand current (1 sec) kA 16 16 20 21 21<br />
Rated short time withstand current (3 sec) kA 10 10 16 16 16<br />
Rated peak withstand current kA 40 40 50 52 52<br />
Rated short circuit making current kA 5 5 5 7.5 7.5<br />
with standard whip (at 12/24/36kV) A 25 1 25 1 25 1 16 16<br />
Mainly active load<br />
breaking current<br />
with chamber K4 fitted (at 24kV) A 250 – – – –<br />
with chamber K5 fitted (at 24 kv) A 630 630 630 – –<br />
Rated lightning impulse withstand (BIL) kV 125 125 125 200 200<br />
Rated power frequency across the isolating distance kV 75 75 75 88 88<br />
withstand voltage, wet to earth and between phases kV 55 55 55 80 80<br />
Insulators Epoxy Silicon Silicon Silicon Silicon<br />
Creepage distance to earth mm (inch) 740 (29.10) 2 715 (28.15) 3 760 (29.90) 3 1205 (47.41) 3 1365 (53.70) 3<br />
Arcing distance mm (inch) 200 (7.90) 255 (10.00) 260 (10.20) 380 (14.95) 385 (15.15)<br />
Ambient temperature limits C -50…+40 -40…+40 -40…+40 -40…+40 -40…+40<br />
Control voltage for motor drive (if fitted) V 24, 48, <strong>11</strong>0, 220 VDC <strong>11</strong>0, 230 VAC<br />
Standard type of control unit used in motor drives REC523 or REC5<strong>01</strong> 4<br />
Standard tested to: IEC 60694 , 6<strong>01</strong>29, 60265-1.<br />
1)<br />
40 A for 12 kV.<br />
2)<br />
Epoxy insulators version.<br />
3)<br />
Silicon insulators version.<br />
4)<br />
For the details about REC523 control unit used in motor drives see page 17.<br />
1 NPS cabinet | 2 GridGuard TM cabinet (page 15)<br />
1 2<br />
14 Outdoor three-phase air switches | ABB Medium Voltage Products
Outdoor three-phase air switches<br />
GridGuard three-phase <strong>outdoor</strong> air switch<br />
Robust construction<br />
−−Resilient, higher BIL silicone rubber insulators<br />
(porcelain available)<br />
−−Steel phase base construction (¼") meets<br />
Federal Specification BR-C-271<br />
−−Reverse loop silver plated copper j<strong>aw</strong> contacts<br />
−−All ferrous components are hot dip galvanized<br />
−−Tinned copper terminal pads<br />
−−Standard quality featu<strong>res</strong> include ¼" phase base<br />
boxframe construction, 3 /8" dead-end connectors,<br />
stainless steel brass bearing rotating shafts,<br />
silver-plated copper reverse loop contacts and<br />
busbar grade copper blades that contribute to<br />
an extended life, even in harsh environments<br />
Reliable design<br />
−−Looped contact design improves contact<br />
integrity<br />
−−Interrupter contact operating speed is<br />
independent of switch operating speed, ensuring<br />
full loadbreak capability<br />
−−All copper construction is grade C<strong>11</strong>0, providing<br />
high conductivity and strength<br />
−−Self-<strong>res</strong>etting interrupter<br />
−−Advanced shunt design eliminates contact pitting<br />
−−Unitized construction: aluminium, steel, or fibre<br />
glass<br />
−−Visible break al<strong>low</strong>s for safe operation and<br />
maintenance<br />
−−Maintenance-free stainless steel and brass<br />
bearing mechanism<br />
−−RUS approved<br />
Application<br />
−−Line switching: load splitting (parallel or loop<br />
switching), load dropping, and associated<br />
charging currents<br />
−−Transformer switching: load dropping, including<br />
associated magnetizing currents<br />
−−Cable switching: load switching (parallel or<br />
loop switching), load dropping, and associated<br />
charging currents<br />
Technical data 15 kV 27 kV 38 kV<br />
Nominal voltage 14.4 21 34.5 kV 14.4 21 34.5<br />
Maximum voltage 17 29 38 kV 17 29 38<br />
BIL <strong>11</strong>0 150 200 kV <strong>11</strong>0 150 200<br />
Continuous current<br />
Fault close<br />
Momentary current<br />
Insulator type<br />
Interrupter type<br />
Crossarm type<br />
Mounting configurations<br />
Control mechanism<br />
*Ice breaking ¾" (manual operation).<br />
**Mechanical Tested up to 5,000 cycles (open/close).<br />
600 A (ANSI), 900 A (IEEE)*<br />
900 A (ANSI)<br />
1200 A (ANSI)**<br />
15 kA rms-asym: 5 x manual operation<br />
20 kA rms-asym: 3 x manual operation<br />
30 kA rms-asym: 2 x manual operation<br />
600 A: 40,000 A-rms 10 cycles/25,000 A-rms 3 sec<br />
900 A: 51,000 A-rms 10 cycles/32,000 A-rms 3 sec<br />
1200 A: 70,000 A-rms 10 cycles/44,000 A-rms 3 sec<br />
Silicone<br />
Porcelain<br />
Expulsion tube: 2,500 open and close operations<br />
Vacuum bottle: 5,000 open and close operations<br />
Galvanized steel: 2,000 lbs/phase<br />
Fibreglass: 1,000 lbs/phase<br />
Horizontal (upright, extra clearance, or underarm)<br />
Vertical (phase over phase)<br />
Riser (vertical)<br />
Delta (pole top)<br />
Hookstick<br />
Reciprocating control rod<br />
Torsional control rod<br />
Motor operator<br />
ABB Medium Voltage Products | Outdoor three-phase air switches 15
Outdoor three-phase load break switches<br />
SECTOS 24kV NXB and NXBD SF6 load break switch<br />
−−Full options for sectionalizer: current and voltage based<br />
logic<br />
−−ABB patent spiral spring operation mechanism with clear<br />
indication<br />
−−Reliable, stable gas density switch and gauge with<br />
temperature compensation<br />
−−Gas-<strong>low</strong> locking device/manual locking device as options<br />
−−Completely sealed stainless steel tank<br />
−−Easily upgraded from manual operated to motor operated<br />
and remote control<br />
−−Safe, compact design<br />
−−Sensor solution with wide dynamic range<br />
−−Integrated earthing switch for increased safety during<br />
maintenance<br />
−−NXBD is a 3-way switch with 1 input + 2 outputs or 2 inputs<br />
+ 1 output: useful for the loop power supply<br />
Technical data<br />
SECTOS NXB and NXBD<br />
Nominal operating voltage kV 12 24<br />
Power frequency<br />
to earth and between phases kV 28 65<br />
withstand voltage, 50 Hz<br />
across the isolating distance kV 32 79<br />
Lightning impulse<br />
to earth and between phases kV 75 125<br />
withstand voltage<br />
across the isolating distance kV 85 145<br />
Rated power frequency Hz 50/60<br />
Rated normal current A 630<br />
Mainly active load breaking current A 630<br />
Number of breaking operations CO n 100<br />
Line-charging breaking current A 50<br />
Cable-charging breaking current A 50<br />
Earth fault breaking current A 50<br />
Cable-charging breaking current under earth fault conditions A 28<br />
No-load transformer breaking current A 6.3<br />
Short-time withstand current (4 sec) kA 20<br />
Peak withstand current kA 50<br />
Short-circuit making current kA 50<br />
main switch 50 kA (CL E2) n 5<br />
Number of making<br />
main switch 31.5 kA (CL E3) n 10<br />
operations CO<br />
earthing switch 50 kA (CL E2) n 3<br />
earthing switch 31.5 kA (CL E3) n 5<br />
Creepage distance mm 620<br />
Operating temperature C -40 … +60<br />
Mechanical endurance<br />
main switch n 5000<br />
(no. of close-open operation) earthing switch n 2000<br />
Filling p<strong>res</strong>sure (+20 Celsius) bar (abs) 1.5<br />
density switch bar (abs) 1.2<br />
Alarm p<strong>res</strong>sure<br />
(+20 Celsius)<br />
density gauge bar (abs) 1.2<br />
<strong>low</strong> gas lock-out mechanism bar (abs) 1.1<br />
Weight kg 82 141<br />
Standard tested to: ANSI C37.63 and 37.71 and IEC 6<strong>01</strong>29, IEC 60265-1 and IEC 60694.<br />
16 Outdoor three-phase load break switches | ABB Medium Voltage Products
Outdoor three-phase load break switches<br />
SECTOS 24kV NXB and NXBD SF6 load break switch<br />
REC 523 control featu<strong>res</strong><br />
−−Remote monitoring and control from SCADA using SPA,<br />
LON, IEC870-1<strong>01</strong>, Modbus and DNP 3.0 protocols with one<br />
RS-485, two RS-232 serial and fibre optic communication<br />
ports<br />
−−Provides 15 digital inputs and 9 digital outputs including<br />
two power outputs<br />
−−9 analog inputs – 9 sensors CTs and VTs<br />
−−12V DC for powering communication devices<br />
−−21 freely configurable LED’s<br />
−−Reclosing functionality<br />
Metering<br />
−−Phase currents and phase to phase voltages<br />
−−Residual current and voltage<br />
−−Active and reactive power<br />
−−Active and reactive energy<br />
−−Demand values of current and power<br />
−−Frequency<br />
−−Power factor<br />
−−Harmonics<br />
−−Disturbance and event recording<br />
Condition monitoring<br />
−−Control circuit supervision<br />
−−Circuit breaker/disconnector<br />
condition monitoring<br />
−−SF6 p<strong>res</strong>sure of primary equipment<br />
−−Battery condition monitoring<br />
−−Battery deep discharge protection<br />
−−Operations counter for primary equipment<br />
−−Internal self-supervision of the unit<br />
Protection and fault indication capabilities<br />
−−Directional earth-fault protection; two stages (<strong>low</strong>-set and<br />
high-set)<br />
−−Three-phase directional overcurrent protection, two stages<br />
(<strong>low</strong>-set and high-set)<br />
−−Three-phase transformer inrush and motor startup current<br />
detector<br />
−−Non-directional earth-fault protection; two stages (<strong>low</strong>-set<br />
and high-set)<br />
−−Three-phase non-directional overcurrent protection, two<br />
stages (<strong>low</strong>-set and high-set)<br />
−−Three-phase under voltage protection; two stages (<strong>low</strong>-set<br />
and high-set)<br />
−−Circuit breaker failure protection<br />
ABB Medium Voltage Products | Outdoor three-phase load break switches 17
Outdoor three-phase load break switches<br />
SECTOS 36kV NXA SF6 load break switch<br />
−−Full options for sectionalizer: current and voltage based<br />
logic<br />
−−ABB patent spiral spring operation mechanism with clear<br />
indication<br />
−−Reliable, stable gas density switch and gauge with<br />
temperature compensation<br />
−−Gas-<strong>low</strong> locking device/manual locking device as options<br />
−−Completely sealed stainless steel tank<br />
−−Easily upgraded from manual operated to motor operated<br />
and remote control<br />
Technical data<br />
NXA<br />
Nominal operating voltage kV 36<br />
Power frequency withstand voltage, 50 Hz to earth and between phases kV 70<br />
Power frequency withstand voltage, 50 Hz across the isolating distance kV 80<br />
Lightning impulse withstand voltage to earth and between phases kV 170<br />
Lightning impulse withstand voltage across the isolating distance kV 195<br />
Rated power frequency Hz 50/60<br />
Rated normal current A 630<br />
Mainly active load breaking current A 630/400<br />
Number of breaking operations CO n 50/400<br />
Line-charging breaking current A 40<br />
Cable-charging breaking current A 40<br />
Earth fault breaking current A 175<br />
Cable-charging breaking current under earth fault conditions A 80<br />
No-load transformer breaking current A 20<br />
Short-time withstand current (3 sec) kA 12.5<br />
Peak withstand current kA 31.5<br />
Short-circuit making current kA 31.5<br />
Number of making operations CO main switch 31,5 kA (CL E3) n 5<br />
Creepage distance mm 960/1440<br />
Operating temperature celsius -40 … +60<br />
Mechanical endurance (number of close-open operation) main switch n 5000<br />
Filling p<strong>res</strong>sure (+20 Celsius) bar (abs) 1.5<br />
Alarm p<strong>res</strong>sure (+20 Celsius) density switch bar (abs) 1.2<br />
Alarm p<strong>res</strong>sure (+20 Celsius) density gauge bar (abs) 1.2<br />
Alarm p<strong>res</strong>sure (+20 Celsius) <strong>low</strong> gas lock-out mechanism bar (abs) 1.1<br />
Weight kg <strong>11</strong>7<br />
Standard tested to: ANSI C37.63 and 37.71 and IEC 6<strong>01</strong>29, IEC 60265-1 and IEC 60694.<br />
<strong>18</strong> Outdoor three-phase load break switches | ABB Medium Voltage Products
Outdoor three-phase load break switches<br />
SECTOS 36kV NXA SF6 load break switch<br />
REC 523 control featu<strong>res</strong>:<br />
−−Remote monitoring and control from SCADA using SPA,<br />
LON, IEC870-1<strong>01</strong>, Modbus and DNP 3.0 protocols with one<br />
RS-485 and two RS-232 serial communication ports<br />
−−Provides 15 digital inputs and 9 digital outputs including<br />
two power outputs<br />
−−12V DC for powering communication devices<br />
−−21 freely configurable LEDs<br />
−−Reclosing functionality<br />
Metering<br />
−−Phase currents and phase to phase voltages<br />
−−Residual current and voltage<br />
−−Active and reactive power<br />
−−Active and reactive energy<br />
−−Demand values of current and power<br />
−−Frequency<br />
−−Power factor<br />
−−Harmonics<br />
−−Disturbance and event recording<br />
Condition monitoring<br />
−−Control circuit supervision<br />
−−Circuit breaker/disconnector condition monitoring<br />
−−SF6 p<strong>res</strong>sure of primary equipment<br />
−−Battery condition monitoring<br />
−−Battery deep discharge protection<br />
−−Operations counter for primary equipment<br />
−−Internal self-supervision of the unit<br />
Protection and fault indication capabilities<br />
−−Directional earth-fault protection; two stages (<strong>low</strong>-set and<br />
high-set)<br />
−−Three-phase directional overcurrent protection, two stages<br />
(<strong>low</strong>-set and high-set)<br />
−−Three-phase transformer inrush and motor startup current<br />
detector<br />
−−Non-directional earth-fault protection; two stages (<strong>low</strong>-set<br />
and high-set)<br />
−−Three-phase non-directional overcurrent protection, two<br />
stages (<strong>low</strong>-set and high-set)<br />
−−Three-phase under voltage protection; two stages (<strong>low</strong>-set<br />
and high-set)<br />
−−Circuit breaker failure protection<br />
ABB Medium Voltage Products | Outdoor three-phase load break switches 19
Electronic sectionalizers<br />
AutoLink single-phase electronic sectionalizer<br />
−−Prevents temporary faults from causing outages<br />
−−Reduces replacement of fuses<br />
−−Coordinates perfectly with reclosers, reducing operating<br />
costs and improving system reliability<br />
−−Minimizes inventory as only one model is needed per<br />
voltage rating<br />
−−Fits on an interchangeable type cutout body<br />
−−Field <strong>res</strong>ettable as many times as needed between 6 and<br />
215 A, and from 1 to 4 counts<br />
−−Detects and discriminates inrush current<br />
−−Trip arm is <strong>res</strong>et with no tools required<br />
−−Does not require any power sources<br />
Technical data<br />
Single-phase AutoLink<br />
Model AL<strong>11</strong> AL12 AL14/15 AL17<br />
Rated voltage kV 15 27 27/33 38<br />
Insulation level (BIL) kV <strong>11</strong>0 125 150 170<br />
Insulator material Silicone/porcelain Silicone/porcelain Silicone/porcelain Porcelain<br />
Rated frequency Hz 50/60 50/60 50/60 50/60<br />
Nominal current A 200 200 200 200<br />
Actuating current A 6 – 215 6 – 215 6 – 215 6 – 215<br />
Number of counts before operation 1 – 4 1 – 4 1 – 4 1 – 4<br />
Short time current, 1 sec (effective) kA 4 4 4 4<br />
Asymmetrical initial (peak) kA 10 10 10 10<br />
Dead line detection mA < 200 < 200 < 200 < 200<br />
Maximum memory time with dead line min 3.5 3.5 3.5 3.5<br />
Memory <strong>res</strong>et sec 30 30 30 30<br />
Standard tested to: ANSI (IEEE) C37.63.<br />
20 Electronic sectionalizers | ABB Medium Voltage Products
Electronic sectionalizers<br />
AutoLink three-phase electronic sectionalizer<br />
−−Prevents temporary faults from causing outages<br />
−−Automatic three-phase opening for overhead line isolation<br />
and protection<br />
−−One simple pole mounting arrangement<br />
−−Field <strong>res</strong>ettable as many times as needed between 6 and<br />
215 A, and from 1 to 4 counts<br />
−−Visible isolation on the lines<br />
−−High level of operating safety<br />
−−Maintenance-free<br />
−−Does not require any power sources<br />
Technical data<br />
Three-phase AutoLink<br />
Model AL32 AL34<br />
Rated voltage kV 27 27<br />
Insulation level (BIL) kV 125 150<br />
Insulator material Porcelain Porcelain<br />
Rated frequency Hz 50/60 50/60<br />
Nominal current A 200 200<br />
Actuating current A 6 – 215 6 – 215<br />
Number of counts before operation 1 – 4 1 – 4<br />
Short time current, 1 sec (effective) kA 4 4<br />
Asymmetrical initial (peak) kA 10 10<br />
Dead line detection mA < 200 < 200<br />
Maximum memory time with dead line min 3.5 3.5<br />
Memory <strong>res</strong>et sec 30 30<br />
Standard tested to: ANSI (IEEE) C37.63.<br />
ABB Medium Voltage Products | Electronic sectionalizers 21
Electronic sectionalizers<br />
AutoLink loadbreak electronic sectionalizer<br />
−−Improves network reliability<br />
−−Isolates temporary faults preventing extended outages<br />
−−Reduces replacement of fuses<br />
−−Reduces operating costs<br />
−−Field configurable as many times as needed between 6 and<br />
215 A, and from 1 to 4 counts<br />
−−Detects inrush current<br />
−−Does not require hookstick with loadbreak accessory<br />
−−Does not require an auxiliary power source<br />
Technical data<br />
Loadbreak AutoLink<br />
Model AL41 AL42 AL44<br />
Rated voltage kV 15 15/27 15/27<br />
Insulation level (BIL) kV <strong>11</strong>0 125 150<br />
Insulator material Porcelain/silicone Silicone Porcelain<br />
Rated frequency Hz 50/60 50/60 50/60<br />
Nominal current A 200 200 200<br />
Manual opening current A 200 200 200<br />
Actuating current A 6 – 215 6 – 215 6 – 215<br />
Number of counts before operation 1 – 4 1 – 4 1 – 4<br />
Short time current, 1 sec (effective) kA rms 4 4 4<br />
Asymmetrical initial (peak) kA 10 10 10<br />
Dead line detection mA < 200 < 200 < 200<br />
Maximum memory time with dead line min 3,5 3,5 3,5<br />
Memory <strong>res</strong>et sec 30 30 30<br />
Standard tested to: ANSI (IEEE) C37.63.<br />
The 15/27 kV version is applicable on systems of up to 15 kV phase-phase or 27kV phase-earth.<br />
22 Electronic sectionalizers | ABB Medium Voltage Products
Single-phase switches<br />
DCD single-phase disconnect switch<br />
−−Double insulator single-phase disconnect switch<br />
−−15 kV – 38 kV, 600 or 900 A continuous loads with a 40 kA<br />
momentary rating<br />
−−Loadbreak tool-operated switch used for sectionalizing or<br />
isolating equipment on electrical distribution systems up to<br />
38 kV<br />
−−Can be mounted vertically or underhung, or on a single or<br />
double crossarm<br />
−−Porcelain or silicone rubber insulator (<strong>11</strong>0 – 150 kV BIL)<br />
−−90° or 160° blade stop available<br />
−−Mounting kit available<br />
Technical data<br />
DCD<br />
Voltage class kV 15 27 38<br />
BIL kV <strong>11</strong>0 125 150<br />
Porcelain creep mm (inch) 441 (17.6) 583 (22.95) 606 (23.87)<br />
Silicone creep mm (inch) 496 (19.53) 719 (28.3) 1003 (39.52)<br />
Porcelain strike mm (inch) 196 (7.71) 217 (8.55) 249 (9.81)<br />
Silicone strike mm (inch) 198 (7.79) 234 (9.26) 270 (10.62)<br />
Continuous current 600/900 600/900 600/900<br />
Peak withstand current kA Asym 65 65 65<br />
Silicone weight lb [kg] 21 (900 A) [9.5] 23 (600 A) [10] 26 (900 A) [12]<br />
Porcelain weight lb [kg] 40 (600 A) [<strong>18</strong>] 42 (600 A) [19] 44 (600 A) [20]<br />
All testing is in accordance with IEEE C37.34.<br />
ABB Medium Voltage Products | Single-phase switches 23
Single-phase switches<br />
SID single-phase disconnect switch<br />
−−Single insulator disconnect with a double blade door and<br />
two 2-hole extended NEMA pad terminals<br />
−−15 kV – 38 kV, 600 or 900 A continuous load with a 40 kA<br />
momentary rating<br />
−−Single-phase disconnect on overhead distribution feeders<br />
and in <strong>outdoor</strong> distribution substations<br />
−−Can be mounted like a standard cutout<br />
−−Porcelain, polymer concrete, or silicone rubber insulator<br />
(<strong>11</strong>0 – 170 kV BIL)<br />
−−Mounting kit available<br />
−−90° or 160° blade stop available<br />
Technical data<br />
SID<br />
Voltage class kV 15.5 27 38<br />
BIL kV <strong>11</strong>0 125 150<br />
Porcelain creep mm (inch) 231 (9.1) 325 (12.8) 432 (17)<br />
Silicone creep mm (inch) 380 (15) 480 (<strong>18</strong>.9) 600 (23.6)<br />
Polymer concrete creep mm (inch) 231 (9.1) 325 (12.8) – –<br />
Momentary withstand current kA Asym 40 40 40<br />
Continuous current 600 900 600 900 600 900<br />
Silicone weight lb [kg] 10.9 [4.9] 12 [5.4] 13.1 [5.9] 14 [6.4] 19.9 [9.0] 20.8 [9.4]<br />
Porcelain weight lb [kg] 14.7 [6.7] 15.6 [7.1] <strong>18</strong>.4 [8.3] 19.3 [8.8] 25.2 [<strong>11</strong>.4] 26.1 [<strong>11</strong>.8]<br />
Polymer concrete weight lb [kg] 14.1 [6.4] 15 [6.8] 17.6 [8.0] <strong>18</strong>.5 [8.4] – –<br />
All testing is in accordance with IEEE C37.34.<br />
24 Single-phase switches | ABB Medium Voltage Products
Single-phase switches<br />
LSID single-phase load break disconnect switch<br />
−−Loadbreak single insulator disconnect with self-contained<br />
loadbreak capabilities, a double blade door, and two 2-hole<br />
NEMA pad terminals<br />
−−15.5 kV – 15/27 kV, 600 A continuous and loadbreak with a<br />
40 kA momentary rating<br />
−−Single-phase disconnect on overhead distribution feeders<br />
and in <strong>outdoor</strong> distribution substations<br />
−−Self-contained loadbreak enables utility personnel to<br />
interrupt load current with a hookstick<br />
−−Can be mounted like a standard cutout<br />
−−Porcelain, polymer concrete, or silicone rubber insulator<br />
(<strong>11</strong>0 – 170 kV BIL)<br />
−−Mounting kit available<br />
−−90° or 160° blade stop available<br />
Technical data<br />
LSID<br />
Voltage class kV 15.5 15/27<br />
BIL kV <strong>11</strong>0 125 150<br />
Porcelain creep mm (inch) 231 (9.1) 325 (12.8) 432 (17)<br />
Silicone creep mm (inch) 380 (15) 480 (<strong>18</strong>.9) 600 (23.6)<br />
Polymer concrete creep mm (inch) 231 (9.1) 325 (12.8) –<br />
Momentary withstand current kA Asym 40 40 40<br />
Continuous current 600 900 600 900 600 900<br />
Silicone weight lb [kg] 12.8 [5.8] 13.7 [6.2] 15.1 [6.8] 16 [7.3] 21.9 [9.9] 22.8 [10.3]<br />
Porcelain weight lb [kg] 16.7 [7.6] 17.6 [8.0] 20.4 [9.3] 21.3 [9.7] 27.2 [12.3] 28.1 [12.7]<br />
Polymer concrete weight lb [kg] 15.8 [7.2] 16.7 [7.6] 19.6 [8.9] 20.5 [9.3] – –<br />
All testing is in accordance with IEEE C37.34.<br />
ABB Medium Voltage Products | Single-phase switches 25
Single-phase switches<br />
RBD single phase bypass disconnect switch<br />
−−Single-phase bypass disconnect switch<br />
−−15 kV – 38 kV, 600 or 900 A continuous loads with a 40 kA<br />
momentary rating<br />
−−Provides a means for bypassing and disconnecting<br />
reclosers or voltage regulators, al<strong>low</strong>ing maintenance on<br />
equipment without service interruption<br />
−−Can be mounted in the fol<strong>low</strong>ing configurations: vertical or<br />
underhung, pole-mounted, or single or double crossarm<br />
−−Porcelain or silicone rubber insulator (<strong>11</strong>0 – 150 kV BIL)<br />
−−90° or 160° blade stop available<br />
−−Mounting kit available<br />
Technical data<br />
RBD<br />
Voltage class kV 15 27 38<br />
BIL kV <strong>11</strong>0 125 150<br />
Porcelain creep mm (inch) 441 (17.6) 583 (22.95) 606 (23.87)<br />
Silicone creep mm (inch) 496 (19.53) 719 (28.3) 1003 (39.52)<br />
Porcelain strike mm (inch) 196 (7.71) 217 (8.55) 249 (9.81)<br />
Silicone strike mm (inch) 198 (7.79) 234 (9.26) 270 (10.62)<br />
Continuous current 600/900 600/900 600/900<br />
Peak withstand current kA Asym 65 65 65<br />
Silicone weight lb [kg] 54 [24] 55 [25] 57 [26]<br />
Porcelain weight lb [kg] 91 [41] 99 [45] 103 [47]<br />
All testing is in accordance with IEEE C37.34.<br />
26 Single-phase switches | ABB Medium Voltage Products
Single-phase switches<br />
ITD Inline tension disconnect switch<br />
−−Single-phase, non-loadbreak, inline tension disconnect<br />
switch with silicone insulator<br />
−−Maximum voltage ratings: 15 kV (150 kV BIL), 27 kV (150<br />
kV BIL), or 38 kV (200 kV BIL)<br />
−−Continuous current rating of 600 A or 900 A<br />
−−Used for manual switching of parallel or de-energized<br />
circuits on overhead distribution lines rated 15-38 kV<br />
−−Loadbreak hooks al<strong>low</strong> for operation with a portable<br />
loadbreak tool<br />
−−90° or 160° blade stop available<br />
Technical data<br />
ITD<br />
Voltage class kV 15 and 27 27 and 38<br />
BIL kV 150 200<br />
Silicone creep mm (inch) 590 (23.23) 991 (39)<br />
Continuous current 600/900 600/900<br />
Peak withstand current kA Asym 65 65<br />
Silicone weight lb [kg] <strong>11</strong> [5] 14 [6]<br />
All testing is in accordance with IEEE C37.34.<br />
ABB Medium Voltage Products | Single-phase switches 27
Fuse cutouts<br />
ICX interchangeable fuse cutout<br />
−−Distribution cutout for use on overhead distribution system<br />
to provide overcurrent protection<br />
−−Fusetube interchangeable with S&C type XS, Cooper Type<br />
L, and AB Chance type C cutouts<br />
−−15 kV – 38 kV, up to 16 kAIC<br />
−−Provides visible indication of fuse operation and a visible<br />
break sectionalizing point for maintenance personnel<br />
−−Can function as a loadbreak switch when used in<br />
conjunction with a portable loadbreak tool<br />
−−Porcelain, silicone rubber (<strong>11</strong>0 – 170 kV BIL), or polymer<br />
concrete insulator (<strong>11</strong>0 and 125 kV BIL)<br />
−−Stainless steel seacoast design<br />
−−Cutout/ar<strong>res</strong>ter combination<br />
−−100 and 200 A fuse available<br />
−−300 A disconnect blade<br />
−−Kickout spring (100 A only)<br />
Technical data<br />
ICX<br />
Voltage class kV 15 27 38<br />
Maximum BIL kV <strong>11</strong>0 150 170<br />
Continuous current A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/300 A<br />
Maximum interrupting rating (disconnect blade) kA 16/12 8/12 10<br />
Porcelain creep mm (inch) 231 (9.1) 432 (17.0) 665 (26.2)<br />
Silicone creep mm (inch) 380 (14.96) 480 (<strong>18</strong>.90) n/a<br />
Porcelain weight lbs [kg] 14 [6.4] 26.5 [12] 35.5 [16.1]<br />
Silicone weight lbs [kg] 9.3 [4.2] 10.2 [4.6] n/a<br />
All testing is in accordance with IEEE C37.41.<br />
28 Fuse cutouts | ABB Medium Voltage Products
Fuse cutouts<br />
NCX fuse cutout<br />
−−Distribution cutout for overcurrent protection on overhead<br />
distribution systems<br />
−−15 kV – 38 kV, up to 20 kAIC<br />
−−Provides visible indication of fuse operation and a visible<br />
break sectionalizing point for maintenance personnel<br />
−−Can function as a loadbreak switch when used in<br />
conjunction with a portable loadbreak tool<br />
−−Porcelain, silicone rubber (<strong>11</strong>0 – 150 kV BIL), or polymer<br />
concrete insulator (<strong>11</strong>0 and 125 kV BIL)<br />
−−Cutout/ar<strong>res</strong>ter combination<br />
−−100 and 200 A fuse available<br />
−−300 A disconnect blade<br />
Technical data<br />
NCX<br />
Voltage class kV 7.8/15 15 15/27 20/34.5 27<br />
Maximum BIL kV <strong>11</strong>0 <strong>11</strong>0 125 150 150<br />
Continuous current A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/300 A 100 A/300 A<br />
Maximum interrupting rating (disconnect blade) kA 12/20 16/12 16/10 12 12<br />
Porcelain creep mm (inch) 231 (9.1) 231 (9.1) 325 (12.8) 432 (17.0) 432 (17.0)<br />
Silicone creep mm (inch) 380 (14.96) 380 (14.96) 480 (<strong>18</strong>.90) 480 (<strong>18</strong>.90) 480 (<strong>18</strong>.90)<br />
Porcelain weight lbs [kg] 13.1[5.91] 13.1[5.91] 16.5 [7.5] 24.3 [<strong>11</strong>.00] 24.3 [<strong>11</strong>.00]<br />
Silicone weight lbs [kg] 10.1 [4.60] 10.1 [4.60] <strong>11</strong>.1 [5.03] <strong>11</strong>.1 [5.03] <strong>11</strong>.1 [5.03]<br />
All testing is in accordance with IEEE C37.41.<br />
ABB Medium Voltage Products | Fuse cutouts 29
Fuse cutouts<br />
LBU-II loadbreak fuse cutout<br />
−−Distribution cutout for use on overhead distribution system<br />
to provide overcurrent protection<br />
−−Loadbreak interruption is accomplished by means of a selfcontained<br />
loadbreak arc chute, which confines the arc and<br />
provides a deionizing action<br />
−−15, 27, or 20/34.5 kV, up to 20 kAIC<br />
−−Provides overcurrent protection for capacitor banks and<br />
gives visible indication that the equipment is energized<br />
−−Used for switching the magnetizing currents of single and<br />
three-phase transformer banks and switching capacitive<br />
currents associated with underground feeder cable at the<br />
riser pole<br />
−−Porcelain, silicone rubber (<strong>11</strong>0 – 150 kV BIL), or polymer<br />
concrete insulator (<strong>11</strong>0 and 125 kV BIL)<br />
−−Cutout/ar<strong>res</strong>ter combination<br />
−−100 and 200 A fuse available<br />
−−300 A disconnect blade<br />
Technical data<br />
LBU-II<br />
Voltage class kV 7.8/15 15 15/27 20/34.5 27<br />
Maximum BIL kV <strong>11</strong>0 <strong>11</strong>0 125 150 150<br />
Continuous current A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/300 A 100 A/300 A<br />
Maximum interrupting rating (disconnect blade) kA 12/20 16/12 16/10 12 12<br />
Porcelain creep mm (inch) 231 (9.1) 231 (9.1) 325 (12.8) 432 (17.0) 432 (17.0)<br />
Silicone creep mm (inch) 380 (14.96) 380 (14.96) 480 (<strong>18</strong>.90) 480 (<strong>18</strong>.90) 480 (<strong>18</strong>.90)<br />
Porcelain weight lbs [kg] 13.1[5.91] 13.1[5.91] 16.5 [7.5] 24.3 [<strong>11</strong>.00] 24.3 [<strong>11</strong>.00]<br />
Silicone weight lbs [kg] 10.1 [4.60] 10.1 [4.60] <strong>11</strong>.1 [5.03] <strong>11</strong>.1 [5.03] <strong>11</strong>.1 [5.03]<br />
All testing is in accordance with IEEE C37.41.<br />
30 Fuse cutouts | ABB Medium Voltage Products
Instrument transformers<br />
Outdoor ANSI medium voltage instrument transformers<br />
Encapsulated in hydrophobic cycloaliphatic epoxy (HCEP)<br />
−−Current and voltage instrument transformers, 46 kV through<br />
52 kV<br />
−−Reduced contamination-related leakage currents<br />
−−Reduced probability of flashover<br />
−−Improved water beading and runoff<br />
−−Improved life expectancy due to reduced insulation<br />
−−Improved quality and system reliability<br />
−−Increased creep distance<br />
−−Improved performance in cold climates (-50°C)<br />
High accuracy/extended range offering<br />
−−15 through 34.5 kV<br />
−−0.15 accuracy to 1%<br />
−−200:5 and 1000:5 ratios with rating factor of 1.5<br />
−−Exceeds IEEE C57.13.6 improved accuracy standards<br />
Technical data Outdoor MV current transformers Outdoor MV voltage transformers<br />
Insulation voltage kV 5 – 69 5 – 69<br />
Impulse withstand voltage kV 60 – 350 60 – 350<br />
Rated frequency Hz 50 – 60 50 – 60<br />
Rated primary 5 – 5000 A 2400 – 46000 V<br />
Dynamic <strong>res</strong>istance <strong>18</strong>0 x rated current –<br />
Thermal <strong>res</strong>istance 80 x rated current x 1s up to 3000 VA<br />
Rating factor 1.0 up to 3.0 –<br />
Accuracy/burden class 0.3B – 1.8* 0.3W – 0.3ZZ and 0.15Y<br />
*Higher accuracies available<br />
- 48/52 kV units available in HCEP or CEP (cycloaliphatic epoxy) material<br />
- 69 kV units available in CEP material only<br />
- CEP units available in US and Canada markets only<br />
1 VOZZ 25 | 2 VOZZ 25G | 3 KOTD 250<br />
1 2 3<br />
ABB Medium Voltage Products | Instrument transformers 31
Instrument transformers<br />
Outdoor IEC medium voltage instrument transformers<br />
IEC product portfolio is encapsulated in hydrophobic<br />
cycloaliphatic epoxy (HCEP) ensuring correct operation in<br />
heavily polluted conditions.<br />
−−Reduced contamination-related leakage currents<br />
−−Reduced probability of flashover<br />
−−Improved water beading and runoff<br />
−−Improved life expectancy<br />
−−Improved quality and system reliability<br />
−−Improved performance in cold climate<br />
Our product offering<br />
−−Multi-core current transformers<br />
−−Single pole (line – ground) insulated voltage transformers<br />
−−Double pole (line – line) insulated voltage transformers<br />
−−Current transformer for NPS three-phase <strong>outdoor</strong> switch<br />
disconnector<br />
Technical data Outdoor medium voltage current transformers Outdoor medium voltage transformers<br />
Insulation voltage kV 7.2 – 40.5 7.2 – 40.5<br />
Impulse withstand voltage kV 60 – 200 60 – 200<br />
Rated frequency Hz 50 – 60 50 – 60<br />
Rated primary<br />
10 – 2500 A<br />
10 000/√3 – 35 000/√3<br />
10 000 – 22 000 V<br />
Dynamic <strong>res</strong>istance kA up to 125 –<br />
Thermal <strong>res</strong>istance up to 50kA/1s 750 VA<br />
Rating factor as per IEC 1.9 for 8h<br />
Burden class as per IEC as per IEC<br />
1 TDO | 2 TJO | 3 TPO<br />
1 2 3<br />
32 Instrument transformers | ABB Medium Voltage Products
Service<br />
Reliable, trouble-free and efficient operation<br />
ABB ensu<strong>res</strong> that customers enjoy reliable, trouble-free<br />
and efficient operation over a full service life.<br />
Diagnosis<br />
Inspection and analysis to improve operating efficiencies and<br />
extend asset life.<br />
Environmental services<br />
Plant, equipment, PCB disposal, pollution prevention/control,<br />
waste minimization.<br />
Installation and commissioning<br />
Cold and hot commissioning including protection and control<br />
systems.<br />
Migration and upgrades<br />
Services and products to evolve or upgrade to the next<br />
generation of hardware and software.<br />
Retrofit<br />
Exchange of worn parts or outdated components while<br />
maintaining original configuration.<br />
Support and remote services<br />
On demand expert support for ABB equipment using<br />
telephone consultations, online knowledge management<br />
and remote equipment monitoring services.<br />
Engineering and consulting<br />
Identify opportunities and implementing solutions to improve<br />
performance, processes and compliance.<br />
Extension<br />
Expansions and extensions to installed systems by adding<br />
new equipment or functionality.<br />
Maintenance and field services<br />
Preventative, predictive and corrective services to maximize<br />
the performance, reliability and availability of equipment.<br />
Repair and refurbish<br />
Factory approved repair, partial or complete reconditioning of<br />
products or systems.<br />
Spare parts<br />
Spare parts, emergency support, repair and exchange,<br />
inventory management and logistics solutions.<br />
Training<br />
Training for personnel including supervisors, engineers,<br />
technicians, operators, programmers, maintenance personnel<br />
on all aspects of ABB products, systems, processes and<br />
technology.<br />
ABB’s wide range of world class medium voltage <strong>outdoor</strong> <strong>apparatus</strong> products come<br />
with unrivalled service support that covers every requirement from installation and<br />
commissioning to through-life preventive and corrective maintenance.<br />
ABB Medium Voltage Products | Service 33
34 ABB Medium Voltage Products
ABB’s Medium Voltage Products<br />
business unit provides utility, industrial<br />
and commercial customers with safe,<br />
reliable and smart technologies for the<br />
distribution of electricity. The extensive<br />
global offering includes distribution<br />
automation products, switching,<br />
limiting, measuring and sensing devices,<br />
switchgear, modular substation packages<br />
and related services.<br />
ABB Medium Voltage Products 35
Contact us<br />
Your sales contact:<br />
www.<strong>abb</strong>.com/contacts<br />
More product information:<br />
www.<strong>abb</strong>.com/productguide<br />
The data and illustrations are not binding. We<br />
<strong>res</strong>erve the right to modify the contents of this<br />
document on the basis of technical development<br />
of the products, without prior notice.<br />
No part of this publication may be reproduced<br />
or transmitted in any form or by means, electronic,<br />
mechanical, photocopying, recording or otherwise<br />
without prior written permission of ABB.<br />
© Copyright 2<strong>01</strong>1 ABB.<br />
All rights <strong>res</strong>erved.<br />
Document ID 2NAA000<strong>01</strong>9 – ABB Medium Voltage Products. General product <strong>cataloge</strong>. <strong>01</strong>.2<strong>01</strong>1