Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Outdoor three-phase load break switches<br />
SECTOS 36kV NXA SF6 load break switch<br />
−−Full options for sectionalizer: current and voltage based<br />
logic<br />
−−ABB patent spiral spring operation mechanism with clear<br />
indication<br />
−−Reliable, stable gas density switch and gauge with<br />
temperature compensation<br />
−−Gas-<strong>low</strong> locking device/manual locking device as options<br />
−−Completely sealed stainless steel tank<br />
−−Easily upgraded from manual operated to motor operated<br />
and remote control<br />
Technical data<br />
NXA<br />
Nominal operating voltage kV 36<br />
Power frequency withstand voltage, 50 Hz to earth and between phases kV 70<br />
Power frequency withstand voltage, 50 Hz across the isolating distance kV 80<br />
Lightning impulse withstand voltage to earth and between phases kV 170<br />
Lightning impulse withstand voltage across the isolating distance kV 195<br />
Rated power frequency Hz 50/60<br />
Rated normal current A 630<br />
Mainly active load breaking current A 630/400<br />
Number of breaking operations CO n 50/400<br />
Line-charging breaking current A 40<br />
Cable-charging breaking current A 40<br />
Earth fault breaking current A 175<br />
Cable-charging breaking current under earth fault conditions A 80<br />
No-load transformer breaking current A 20<br />
Short-time withstand current (3 sec) kA 12.5<br />
Peak withstand current kA 31.5<br />
Short-circuit making current kA 31.5<br />
Number of making operations CO main switch 31,5 kA (CL E3) n 5<br />
Creepage distance mm 960/1440<br />
Operating temperature celsius -40 … +60<br />
Mechanical endurance (number of close-open operation) main switch n 5000<br />
Filling p<strong>res</strong>sure (+20 Celsius) bar (abs) 1.5<br />
Alarm p<strong>res</strong>sure (+20 Celsius) density switch bar (abs) 1.2<br />
Alarm p<strong>res</strong>sure (+20 Celsius) density gauge bar (abs) 1.2<br />
Alarm p<strong>res</strong>sure (+20 Celsius) <strong>low</strong> gas lock-out mechanism bar (abs) 1.1<br />
Weight kg <strong>11</strong>7<br />
Standard tested to: ANSI C37.63 and 37.71 and IEC 6<strong>01</strong>29, IEC 60265-1 and IEC 60694.<br />
<strong>18</strong> Outdoor three-phase load break switches | ABB Medium Voltage Products