Outdoor three-phase load break switches<br />

SECTOS 36kV NXA SF6 load break switch<br />

−−Full options for sectionalizer: current and voltage based<br />

logic<br />

−−ABB patent spiral spring operation mechanism with clear<br />

indication<br />

−−Reliable, stable gas density switch and gauge with<br />

temperature compensation<br />

−−Gas-<strong>low</strong> locking device/manual locking device as options<br />

−−Completely sealed stainless steel tank<br />

−−Easily upgraded from manual operated to motor operated<br />

and remote control<br />

Technical data<br />

NXA<br />

Nominal operating voltage kV 36<br />

Power frequency withstand voltage, 50 Hz to earth and between phases kV 70<br />

Power frequency withstand voltage, 50 Hz across the isolating distance kV 80<br />

Lightning impulse withstand voltage to earth and between phases kV 170<br />

Lightning impulse withstand voltage across the isolating distance kV 195<br />

Rated power frequency Hz 50/60<br />

Rated normal current A 630<br />

Mainly active load breaking current A 630/400<br />

Number of breaking operations CO n 50/400<br />

Line-charging breaking current A 40<br />

Cable-charging breaking current A 40<br />

Earth fault breaking current A 175<br />

Cable-charging breaking current under earth fault conditions A 80<br />

No-load transformer breaking current A 20<br />

Short-time withstand current (3 sec) kA 12.5<br />

Peak withstand current kA 31.5<br />

Short-circuit making current kA 31.5<br />

Number of making operations CO main switch 31,5 kA (CL E3) n 5<br />

Creepage distance mm 960/1440<br />

Operating temperature celsius -40 … +60<br />

Mechanical endurance (number of close-open operation) main switch n 5000<br />

Filling p<strong>res</strong>sure (+20 Celsius) bar (abs) 1.5<br />

Alarm p<strong>res</strong>sure (+20 Celsius) density switch bar (abs) 1.2<br />

Alarm p<strong>res</strong>sure (+20 Celsius) density gauge bar (abs) 1.2<br />

Alarm p<strong>res</strong>sure (+20 Celsius) <strong>low</strong> gas lock-out mechanism bar (abs) 1.1<br />

Weight kg <strong>11</strong>7<br />

Standard tested to: ANSI C37.63 and 37.71 and IEC 6<strong>01</strong>29, IEC 60265-1 and IEC 60694.<br />

<strong>18</strong> Outdoor three-phase load break switches | ABB Medium Voltage Products