Construct the injection point<br />

<strong>Chlorine</strong> <strong>Monitoring</strong> <strong>and</strong> Dechlorinating <strong>Techniques</strong> H<strong>and</strong>book<br />

The injection point should be constructed to intercept the inlet pipe to the pond. This allows<br />

mixing prior to the water entering the pond.<br />

A chemical metering pump 6 can be fitted to the top of the injection point to allow the<br />

operator to control the flow rate of dechlorinating chemicals into the injection point. Some<br />

specifications for pumps are attached in Appendix C. To calculate the dosing rate of<br />

dechlorinating agent in solution, refer to Section 3.0. Routine monitoring of the water for<br />

chlorine residuals should occur to ensure proper dechlorination.<br />

In the case of a pond, the structure is likely to be permanent. In this case it is recommended<br />

that a shed be constructed to house the dechlorinating chemicals, <strong>and</strong> the chemical metering<br />

pump. Power would need to be provided to the site. The shed should be kept locked to<br />

prevent tampering. The shed will also ensure that the chemical metering pump is protected<br />

from the elements.<br />

It is also recommended that some rip-rap be placed at the base of where the inlet pipe will<br />

discharge water into the pond. This will prevent erosion of sediments on the base of the pond<br />

<strong>and</strong> discourage sediments from being churned up by the energy of the incoming water.<br />

5.2 In-line Injection<br />

The in-line injection method involves mechanically injecting dechlorinating agent into some<br />

type of piping system. As the type of systems that may require this approach varies greatly,<br />

only general concepts can be provided in this h<strong>and</strong>book.<br />

Injection Point<br />

The injection point should be constructed to intercept the existing piping a minimum of 10<br />

m from the point of discharge to a receiving water body. The system must ensure sufficient<br />

mixing of the chlorinated water with the dechlorinating agent while the water is still inside<br />

the pipe. The method of injection should also ensure throughout mixing of the water with the<br />

dechlorinating agent.<br />

Flow Measurement<br />

In a pipe with relatively constant flow, a metering system can be set at one specific addition<br />

rate. No monitoring of the flow in the pipe would be required. However, if large variations<br />

6<br />

Chemical metering pumps are available from local suppliers.<br />