Appendix 1: Rules governing selection<br />
of a fuse to protect a transformer<br />
The selection guides offered by fuse and<br />
switchgear manufacturers take account of the<br />
following rules, for the part that concerns them,<br />
as well as any particularities of the switchgear in<br />
question (confining of fuses modifying their<br />
conditions of cooling for example) (see IEC 787).<br />
I nt : rated current of the transformer.<br />
I sc LV : primary current in case of an LV shortcircuit.<br />
I nf : rated current of the fuse.<br />
I f (): t current leading to melting in time t (the<br />
fuse's characteristic time-current curve).<br />
I 3 : minimal breaking current of the fuse.<br />
Rules to avoid spurious melting<br />
c Withstand operating current (and possible<br />
overloads)<br />
1.4 In<br />
< I<br />
t n . f<br />
c Withstand inrush currents<br />
12 I < I (0.1s)<br />
nt f .<br />
Rule to eliminate a major LV fault<br />
c Act before the destruction of the transformer<br />
If<br />
(2s) < Isc LV .<br />
Rule for correct functioning of the fuse in the absence of a combination<br />
c Do not operate the fuse in its critical zone.<br />
Manage situations with In f<br />
< I < I 3 using a<br />
complementary means.<br />
Rules for coordination to ensure the correct functioning of a fuseswitch<br />
combination<br />
(see IEC 420)<br />
t s : minimal opening time of the combined switch<br />
caused by the striker.<br />
t d : opening time of the combined device under<br />
the action of the tripping device.<br />
I 4 : rated transfer current of the combination.<br />
I 5 : rated take-over current of the combination.<br />
c Do not operate the switch beyond its<br />
performance levels: transfer current less than the<br />
rated value<br />
Itransfer < I4<br />
.<br />
See appendix 2 for details of the calculation.<br />
c Do not operate the switch beyond its<br />
performance levels: transfer current less than<br />
current in the instance of a fault across the low<br />
voltage terminals,<br />
Itransfer<br />
< Isc LV<br />
(this rule does not cover all cases of faults only<br />
involving two phases on the low voltage side).<br />
c Do not operate the switch above its<br />
performance levels: take-over current less than<br />
the rated value<br />
1.065 If ( t d + 002 . s ) < I5<br />
.<br />
See appendix 2 for the details of this calculation.<br />
Cahier Technique Schneider n° 192 / p.29