Appendix 1: Rules governing selection<br />

of a fuse to protect a transformer<br />

The selection guides offered by fuse and<br />

switchgear manufacturers take account of the<br />

following rules, for the part that concerns them,<br />

as well as any particularities of the switchgear in<br />

question (confining of fuses modifying their<br />

conditions of cooling for example) (see IEC 787).<br />

I nt : rated current of the transformer.<br />

I sc LV : primary current in case of an LV shortcircuit.<br />

I nf : rated current of the fuse.<br />

I f (): t current leading to melting in time t (the<br />

fuse's characteristic time-current curve).<br />

I 3 : minimal breaking current of the fuse.<br />

Rules to avoid spurious melting<br />

c Withstand operating current (and possible<br />

overloads)<br />

1.4 In<br />

< I<br />

t n . f<br />

c Withstand inrush currents<br />

12 I < I (0.1s)<br />

nt f .<br />

Rule to eliminate a major LV fault<br />

c Act before the destruction of the transformer<br />

If<br />

(2s) < Isc LV .<br />

Rule for correct functioning of the fuse in the absence of a combination<br />

c Do not operate the fuse in its critical zone.<br />

Manage situations with In f<br />

< I < I 3 using a<br />

complementary means.<br />

Rules for coordination to ensure the correct functioning of a fuseswitch<br />

combination<br />

(see IEC 420)<br />

t s : minimal opening time of the combined switch<br />

caused by the striker.<br />

t d : opening time of the combined device under<br />

the action of the tripping device.<br />

I 4 : rated transfer current of the combination.<br />

I 5 : rated take-over current of the combination.<br />

c Do not operate the switch beyond its<br />

performance levels: transfer current less than the<br />

rated value<br />

Itransfer < I4<br />

.<br />

See appendix 2 for details of the calculation.<br />

c Do not operate the switch beyond its<br />

performance levels: transfer current less than<br />

current in the instance of a fault across the low<br />

voltage terminals,<br />

Itransfer<br />

< Isc LV<br />

(this rule does not cover all cases of faults only<br />

involving two phases on the low voltage side).<br />

c Do not operate the switch above its<br />

performance levels: take-over current less than<br />

the rated value<br />

1.065 If ( t d + 002 . s ) < I5<br />

.<br />

See appendix 2 for the details of this calculation.<br />

Cahier Technique Schneider n° 192 / p.29