Technical Specifications<br />

<strong>Steam</strong> Boilers ESBH-H<br />

Technical data boiler without economizer<br />

Model 10000 12000 14000 16000 18000 20000<br />

<strong>Steam</strong> output<br />

kg/h 10000 12000 14000 16000 18000 20000<br />

Operating output<br />

at 10 bar(g) kW<br />

at 13 bar(g) kW<br />

at 16 bar(g) kW<br />

6520<br />

6542<br />

6557<br />

7824<br />

7850<br />

7868<br />

9128<br />

9159<br />

9180<br />

10432<br />

10467<br />

10491<br />

11736<br />

11776<br />

11802<br />

13040<br />

13084<br />

13114<br />

Boiler efficiency Natural gas at 10 bar(g) %<br />

at 13 bar(g) %<br />

at 16 bar(g) %<br />

Boiler efficiency at 10 bar(g) %<br />

Diesel Oil (35 secs) at 13 bar(g) %<br />

at 16 bar(g) %<br />

Technical data Natural gas<br />

89.9<br />

89.4<br />

89.2<br />

89.9<br />

89.4<br />

89.1<br />

Flue gas resistance mbar 11.0 10.0 10.0 10.0 11.0 11.0<br />

Model 10000 12000 14000 16000 18000 20000<br />

Natural gas calorific value kJ/Nm 3 36000 36000 36000 36000 36000 36000<br />

Fuel consumption at at 10 bar(g) Nm 3 /h<br />

at 13 bar(g) Nm 3 /h<br />

at 16 bar(g) Nm 3 /h<br />

725.7<br />

732.2<br />

728.0<br />

89.8<br />

89.5<br />

89.1<br />

89.89<br />

89.5<br />

89.0<br />

871.4<br />

877.4<br />

883.6<br />

89.8<br />

89.4<br />

89.0<br />

89.9<br />

89.5<br />

89.0<br />

1016.7<br />

1024.6<br />

1031.7<br />

89.9<br />

89.4<br />

89.0<br />

89.8<br />

89.5<br />

89.0<br />

1162.1<br />

1171.1<br />

1179.3<br />

89.6<br />

89.2<br />

89.0<br />

89.7<br />

89.2<br />

89.0<br />

1310.0<br />

1320.1<br />

1329.4<br />

89.9<br />

89.4<br />

89.0<br />

89.9<br />

89.4<br />

89.0<br />

1451.5<br />

1464.5<br />

1474.7<br />

Flue gas volume, at 10 bar(g) Nm 3 /h<br />

excess air @10% at 13 bar(g) Nm 3 /h<br />

at 16 bar(g) Nm 3 /h<br />

8084<br />

8156<br />

8110<br />

9707<br />

9774<br />

9843<br />

11327<br />

11414<br />

11494<br />

12946<br />

13046<br />

13137<br />

14594<br />

14706<br />

14809<br />

16170<br />

16315<br />

16429<br />

Fuel heat input<br />

at 10 bar(g) kW<br />

at 13 bar(g) kW<br />

at 16 bar(g) kW<br />

7253<br />

7318<br />

7351<br />

8713<br />

8771<br />

8831<br />

10165<br />

10245<br />

10315<br />

11604<br />

11708<br />

11788<br />

13098<br />

13020<br />

13291<br />

14505<br />

14635<br />

14735<br />

Technical data Diesel Oil (35 secs)<br />

Model 10000 12000 14000 16000 18000 20000<br />

Diesel Oil calorific value kJ/kg 42700 42700 42700 42700 42700 42700<br />

Fuel consumption at<br />

full capacity<br />

at 10 bar(g) kg/h<br />

at 13 bar(g) kg/h<br />

at 16 bar(g) kg/h<br />

611.5<br />

617.0<br />

613.6<br />

734.3<br />

739.5<br />

744.7<br />

856.8<br />

863.5<br />

869.7<br />

979.3<br />

987.0<br />

994.0<br />

1103.8<br />

1112.4<br />

1120.3<br />

1223.2<br />

1234.2<br />

1245.9<br />

Flue gas volume, at 10 bar(g) Nm 3 /h<br />

excess air @12% at 13 bar(g) Nm 3 /h<br />

at 16 bar(g) Nm 3 /h<br />

8259<br />

8333<br />

8287<br />

9916<br />

9987<br />

10057<br />

11571<br />

11662<br />

11745<br />

13226<br />

13329<br />

13424<br />

14907<br />

15023<br />

15129<br />

16520<br />

16667<br />

16756<br />

Fuel heat input<br />

at 10 bar(g) kW<br />

at 13 bar(g) kW<br />

at 16 bar(g) kW<br />

7253<br />

7318<br />

7359<br />

8703<br />

8771<br />

8860<br />

10154<br />

10234<br />

10338<br />

11617<br />

11695<br />

11788<br />

13084<br />

13202<br />

13291<br />

14505<br />

14635<br />

14735<br />

Technical data with integral economizer, fuel natural gas and low sulphur fuel oil<br />

Model 10000 12000 14000 16000 18000 20000<br />

Additional operating output<br />

with economizer<br />

at 10 bar(g) kW<br />

at 13 bar(g) kW<br />

at 16 bar(g) kW<br />

Boiler efficiency with economizer %<br />

Flue gas resistance of economizer<br />

mbar<br />

326<br />

366<br />

382<br />

94.4<br />

2.5<br />

Flue gas temperature after economizer °C 140 140 140 140 140 140<br />

399<br />

432<br />

464<br />

94.4<br />

2.5<br />

465<br />

513<br />

557<br />

94.4<br />

2.5<br />

522<br />

586<br />

637<br />

94.4<br />

3.0<br />

622<br />

686<br />

716<br />

94.4<br />

3.0<br />

652<br />

732<br />

796<br />

94.4<br />

3.0<br />

44 ECOTHERM <strong>Steam</strong> <strong>Solutions</strong>