13 Protection Control<br />

13.1. Protection Control For All Operations<br />

13.1.1. Time Delay Safety Control<br />

1. The compressor starts the operation, it will not stop its operation for 30 seconds.<br />

2. This control is not applicable if the power supply is cut <strong>of</strong>f and on again or after 4-way valve deices condition.<br />

13.1.2. 30 Seconds Forced Operation<br />

1. Once compressor starts the operation, it will not stop its operation for 30 seconds.<br />

2. However, it can be stopped with the remote control or the Auto Switch on the indoor unit.<br />

13.1.3. Total Running Current Control<br />

1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be<br />

decreased.<br />

2. If the running current does not exceed X value for ten seconds, the frequency instructed will be increased.<br />

3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.<br />

Model TE9HK TE12HK<br />

Operation Mode X (A) Y (A) X (A) Y (A)<br />

Cooling/S<strong>of</strong>t Dry (A) 4.13 15.35 6.15 15.35<br />

Cooling/S<strong>of</strong>t Dry (B) 3.63 15.35 5.65 15.35<br />

Heating 4.75 15.35 6.24 15.35<br />

4. The first 30 minutes <strong>of</strong> cooling operation, (A) will be applied.<br />

13.1.4. IPM (Power transistor) Prevention Control<br />

A. Overheating Prevention Control<br />

1. When the IPM temperature rises to 110�C, compressor operation will stop immediately.<br />

2. Compressor operation restarts after three minutes the temperature decreases to 95�C.<br />

B. DC Peak Current Control<br />

1. When electric current to IPM exceeds set value <strong>of</strong> 30.0 ± 5.0 A, the compressor will stop operate. Then, operation will<br />

restart after 3 minutes.<br />

2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two<br />

minutes.<br />

3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If<br />

this condition repeats continuously for seven times, all indoor and outdoor relays will be cut <strong>of</strong>f.<br />

13.1.5. Compressor Overheating Prevention Control<br />

Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes <strong>of</strong> frequency<br />

are as below figure.<br />

If compressor discharge temperature exceeds 110�C, compressor will stop, occurs 4 times per 20 minutes, timer LED will be<br />

blinking. (“F97” is to be confirmed.)<br />