Chapter 1 – Installation

1.7 Power Terminals

• Type A Configuration: 1 ~ 5 HP (230/460/480V)

DB Resistor integrated

R S T G N B1 B2 U V W

• Type B Configuration: 7.5 ~ 10 HP (230/460/480V)

R S T G P N B1 B2 U V W

• Type C Configuration: 15 ~ 30 HP (230/460/480V)

R S T G P1 P2 N U V W

• Type C Configuration: 15 ~ 30 HP (230/460/480V), Built-in DBU model

R S T G P1 B1 B2 U V W

• Type D Configuration: 40~ 75 HP (230V), 40 ~ 100 HP (460/480V)

R S T G U V W P1 P2 N

* Jumper should be removed to connect a DC reactor

Symbols

R

S

T

G

P

P1

P2

N

B1

B2

U

V

W

Functions

AC Line Voltage Input

(3 Phase, 200 ~ 230VAC or 380 ~ 460/480 VAC)

Earth Ground

Positive DC Bus Terminal

DB Unit (P-P 7 ) Connection Terminals

(DB Unit may be added when more braking duty (More than 30%ED) is required)

External DC Reactor (P1-P2) and DB Unit (P2-N) Connection Terminals

Negative DC Bus Terminal

DB Unit (N-N 8 ) Connection Terminal

Dynamic Braking Resistor (B1-B2) Terminals for 1-30HP inverters

3 Phase Power Output Terminals to Motor

(3 Phase, 200 ~ 230VAC or 380 ~ 460/480 VAC)

“Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical amperes,

240 volts maximum for 230V class models and 480 volts maximum for 460V class models.”

7

This P terminal is provided on optional Dynamic Braking Unit.

8 This N terminal is provided on optional Dynamic Braking Unit.