Chapter 2 - Operation

Operation

Freq Setting via Keypad + Run/Stop via Terminal (FX/RX)

Example (1)

[Operation condition]

-. Control mode: V/F control

-. Ref. Frequency: 50[Hz] setting via keypad

-. Accel/Decel time: Accel – 10 [Sec], Decel – 20 [Sec]

-. Drive mode: Run/Stop via FX/RX terminal

[Wiring]

3P

AC

input

R

S

T

G

B1

B2

U

V

W

IM

S/W

Potentiometer

1[kohm],1/2W

FX

RX

BX

RST

JOG

P1

P2

P3

CM

VR

V1

5G

FM

5G

30A

30C

30B

AXA

AXC

Step Parameter setting Code Description

1 Control Mode Selection FU2-39 Set it to 0 {V/F}.

2 Drive Mode DRV-3 Set it to 1 Fx/Rx-1.

3 Frequency Mode DRV-4 Set it to 0 Keypad-1.

4

50[Hz] freq command

setting

5 Accel/Decel time

6 Terminal FX

7 Terminal RX

DRV-0

DRV-2

DRV-3

Set freq command 50[Hz] via Keypad.

Set Accel time to 10 [Sec] in DRV-2.

Set Decel time to 20 [Sec] in DRV-3.

Motor starts to rotate in Forward direction at 50Hz with Accel time

10 [sec] when FX terminal is turned ON.

Motor decelerates to stop with Decel time 25[sec] when FX

terminal is turned OFF.

When RX terminal is turned ON motor starts to rotate in Reverse

direction at 50[Hz] with Accel time 10 [Hz]. When it is OFF, motor

decelerates to stop with Decel time 20 [Sec].

34