Chapter 1 – Installation

• Wires and Terminal Lugs

Refer to the following table for wires, terminal lugs, and screws used to connect the inverter power input (R, S, T) and

output (U, V, W). Input and motor output terminal blocks are intended only for use with ring type connectors.

Inverter Capacity

200V

Class

400V

Class

Terminal

Screw Size

Screw

Torque 9

(Kgf·cm)/lb-in

Ring Terminals

mm

Wire 10

AWG

R,S,T U,V,W R,S,T U,V,W R,S,T U,V,W

1 ~ 3 HP M3.5 15 / 10 2-4 2-4 2 2 14 14

5 HP M3.5 15 / 10 2-4 2-4 3.5 3.5 12 12

7.5 HP M4 15 / 10 5.5-5 5.5-5 5.5 5.5 10 10

10 HP M4 15 / 10 14-5 8-5 14 8 6 8

15 HP M5 26 / 18 14-5 14-5 14 14 6 6

20 HP M5 26 / 18 22-6 22-6 22 22 4 4

25 HP M6 45 / 31 38-8 38-8 30 30 2 2

30 HP M6 45 / 31 38-8 38-8 38 30 2 2

40-50HP M8 100 / 70 60-8 60-8 60 60 2/0 2/0

60-75HP M10 200 / 139 100-10 100-10 100 100 4/0 4/0

1 ~ 5 HP M3.5 15 / 10 2-4 2-4 2 2 14 14

7.5 HP M4 15 / 10 5.5-5 5.5-5 3.5 2 12 14

10 HP M4 15 / 10 14-5 8-5 3.5 3.5 12 12

15 HP M5 26 / 18 14-5 14-5 5.5 5.5 10 10

20 HP M5 26 / 18 22-6 22-6 14 8 6 8

25 HP M6 45 / 31 38-8 38-8 14 8 6 8

30 HP M6 45 / 31 38-8 38-8 22 14 4 6

40-50HP M8 100 / 70 38-8 38-8 22 22 4 4

60-75HP M8 100 / 70 38-8 38-8 38 38 2 2

100HP M8 100 / 70 60-8 60-8 60 60 2/0 2/0

• Power and Motor Connection

R S T G N B1 B2 U V W

3 Phase

Power Input

Power supply must be connected

to the R, S, and T terminals.

Connecting it to the U, V, and W

terminals causes internal damages

to the inverter. Arranging the phase

sequence is not necessary.

Motor

Motor should be connected to the

U, V, and W terminals.

If the forward command (FX) is on,

the motor should rotate counter

clockwise when viewed from the load

side of the motor. If the motor rotates

in the reverse, switch the U and V

terminals.

9

Apply the rated torque to terminal screws. Loose screws can cause of short circuit or malfunction. Tightening the screws too much

can damage the terminals and cause a short circuit or malfunction.

10 Use copper wires only with 600V, 75ratings .