19.06.2020 Views

Manual iS5 (ingles)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 1 – Installation

1.8.1 Wiring Control Terminals

• Wiring Precautions

• CM and 5G terminals are insulated to each other. Do not connect these terminals with each other and do not

connect these terminals to the power ground. Terminal 5G is indicated as CM from 30kW inverters and has the

same potential as CM (Sequence Common Terminal).

• Use shielded wires or twisted wires for control circuit wiring, and separate these wires from the main power circuits

and other high voltage circuits.

• It is recommended to use the cables of 1.25 mm(22 AWG) for connection to the control circuit terminals.

• Control Circuit Terminal

• The control input terminal of the control circuit is ON when the circuit is configured to the current flows out of the

terminal, as shown in the following illustration. CM terminal is the common terminal for the contact input signals.

Resistor

Current

FX

24 VDC

Resistor

RX

CM

External Sequence

Inverter Circuitry

Do not apply voltage to any control input terminals (FX, RX, P1, P2, P3, JOG, BX, RST, CM).

20

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!