<strong>Safety</strong> controllers and fieldbus systems<br />
Ordering information<br />
7024240<br />
Functionality<br />
Remote I/O device<br />
Detailed technical specifications<br />
General system data<br />
<strong>Safety</strong> remote I/Os UE4420/4450/4455<br />
UE4420-03DC9F0 UE4450-03DC9F0 UE4455-03DC9F0<br />
Fieldbus DeviceNet <strong>Safety</strong><br />
<strong>Safety</strong> category Up to category 4 accord. EN 954-1<br />
<strong>Safety</strong> integrity level Up to SIL 3 (IEC 61508)<br />
Supply voltage 19.2 V DC ... 28.8 V DC<br />
Connection type supply voltage Mini 7/8" × 4<br />
Ambient operating temperature from ... to –10 °C ... +55 °C<br />
Enclosure rating IP 67<br />
Protection class III (IEC 61131-2)<br />
Vibration resistance according to IEC 60068-2-6 0.35 mm, 10 Hz ... 57 Hz, 50 m/sec², 57 Hz ... 150 Hz<br />
Shock resistance 150 g, 11 ms (IEC 60068-2-27)<br />
Mounting Location in the vincinity of the equipment<br />
Weight 522 g 582 g<br />
Field-signal connections<br />
Number of<br />
safety inputs<br />
6 dual-channel<br />
resp.<br />
12 single-channel<br />
Number of<br />
safety capable<br />
outputs<br />
2 dualchannel,<br />
bipolar type<br />
Connection type 5-pole M12 connector<br />
Number of safety inputs<br />
Type of output on the field-signal input<br />
Input voltage HIGH<br />
Input voltage LOW<br />
Input current HIGH<br />
Input delay<br />
Usage of the<br />
expanded functions<br />
on the SDL<br />
Number of test/<br />
signal outputs (with<br />
current monitoring) Type Part number<br />
UE4420-03DC9F0 1028302<br />
UE4450-03DC9F0 1028305<br />
— 12 (1)<br />
✔ 12 (1) UE4455-03DC9F0 1028306<br />
6 dual-channel resp. 12 single-channel<br />
PNP or contact<br />
11 V DC ... 30 V DC<br />
–30 V DC ... 5 V DC<br />
5 mA<br />
0 ms ... 635 ms, configurable<br />
Number of SDL connections<br />
<strong>Safety</strong> outputs<br />
— 2<br />
Number of safety capable outputs<br />
2 dual-channel<br />
Type of output<br />
Bipolar type<br />
Maximum response time<br />
15 ms<br />
Switching current<br />
2 A<br />
Leakage current<br />
0.5 mA<br />
Test/signal outputs<br />
Number of test/signal outputs (with current<br />
monitoring)<br />
12<br />
Output current per channel<br />
700 mA<br />
Leakage current<br />
Max. 0.5 mA<br />
© <strong>SICK</strong>, Inc., USA. All rights, including changes to technical specifications<br />
and or to the equipment without prior notification, are reserved.<br />
O - 59<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
H<br />
I<br />
J<br />
K<br />
L<br />
M<br />
N<br />
O<br />
P<br />
Q<br />
R