Water Piping<br />

As with any water system, it is important that the system<br />

be clean. The pipe work installer must remove weld scale,<br />

rust and contamination during pipe work fabrication.<br />

The system water piping must be fl ushed thoroughly<br />

with recommended alkaline fl ush or other chemicals that<br />

are compatible with 316 stainless steel prior to making<br />

connections to the <strong>ClimaCool</strong> chiller. There are certain<br />

necessary components that should always be installed in<br />

the chilled water system. (See Figures 1 and 2 on page 13 -<br />

Water Piping Confi gurations for confi gurations with multiple<br />

modules). All water piping must be installed in accordance<br />

with applicable codes and standards.<br />

Temperature Sensor and Wells<br />

<strong>ClimaCool</strong> provides (2) temperature sensors and wells with<br />

each chiller system confi gured by the CoolLogic Control<br />

System. They must be fi eld installed 36” - 60” away from the<br />

bank and before the strainer on the chilled water inlet and<br />

chilled water outlet (See Water Piping Confi gurations – page<br />

13). Sensors must be fully inserted into the well to obtain<br />

proper readings.<br />

Pressure Diff erential Flow Sensor or Switch<br />

It is imperative that minimum and maximum water fl ow<br />

rates, as defi ned in the Physical Data tables on page 6,<br />

are not exceeded. To prevent the operation of the chiller<br />

without suffi cient water fl ow to the evaporator it is a<br />

required safety device to install a pressure diff erential fl ow<br />

sensor or switch in the chilled water circuit, downstream of<br />

the strainer (See Water Piping Confi gurations – page 13).<br />

12<br />

Pressure Taps<br />

The installing contractor must provide access ports for<br />

connecting the pressure diff erential fl ow sensor or switch<br />

and pressure gauges for the chilled water system. A 1/4”<br />

pressure tap is required on the inlet and the outlet of the<br />

chilled water system for a total of four taps. If a port is<br />

shared by the pressure diff erential fl ow sensor or switch and<br />

the pressure gauge it will require two 1/2” taps. (See Water<br />

Piping Confi gurations – page 13).<br />

Water Isolation Valves<br />

It is recommended to provide bank water isolation valves for<br />

proper isolation and maintenance of the chiller, pump and<br />

strainer (See Water Piping Confi gurations – page 13).<br />

Strainers – Minimum 60 Mesh Screen Required<br />

<strong>ClimaCool</strong> chillers utilize brazed plate heat exchangers<br />

which are extremely sensitive to debris. Therefore, it is<br />

mandatory that all chilled water systems include a strainer<br />

with a minimum of 60 mesh screen for proper fi ltration at<br />

all times when the chiller is operating. The strainers must<br />

be installed as shown in the Water Piping Confi gurations on<br />

page 13.<br />

<strong>ClimaCool</strong>’s warranty does not cover and does not apply to<br />

products which have defects or damages due to freezing<br />

of the water supply, an inadequate or interrupted water<br />

supply, corrosives or abrasives in the water supply, or<br />

improper or inadequate fi ltration or treatment of the<br />

water supply.<br />