12 <strong>Cable</strong> Construction & Continuous Current Ratings<br />

3.00 <strong>Cable</strong> Construction &<br />

Continuous Current Ratings<br />

The continuous current capacity is calculated in accordance with IEC 60287.<br />

Laying Conditions<br />

1) Ground Temperature : 25<br />

2) Depth of Laying : 1.5m<br />

3) Soil Thermal Resistivity : 1.0 m/W<br />

4) Ambient Temperature : 40<br />

5) Max. Conductor Temperature : 90<br />

6) <strong>Cable</strong> Formation : Flat (S=2D)<br />

S : Distance between cables / D : <strong>Cable</strong> diameter<br />

7) Frequency : 50Hz<br />

8) Load factor : 100%<br />

Maximum Permissible Conductor Temperature<br />

Normal Operation Emergency Operation Short Circuit<br />

90 105 250<br />

1) Normal Operation<br />

Normal operation is meant to be maintained through out a given period of<br />

time everyday or continuously, without affecting the operation.<br />

2) Emergency Load<br />

Emergency load is meant to be maintained for a short time under the<br />

condition of system breakdown or under the state of excessively loaded<br />

operation, without causing a defect.<br />

3) Short Circuit<br />

Short circuit is meant to cause no defect of the cable when an irregular<br />

current, flows for short time due to shorting or earthing.