7.08 Transition Joint<br />

52 Accessories for <strong>EHV</strong> <strong>Cable</strong> <strong>System</strong>s<br />

Bell Mouth<br />

Epoxy Unit Spring Unit<br />

Ferrule Stress relief cone<br />

The transition joint connects between existing oil-filled cables and extruded dielectric cables. They comprise the stop joint with<br />

oil-impregnated paper insulation and epoxy bell mouth at side of oil-filled cables. They also comprise prefabricated type joint<br />

with stress relief cone based EPR(Ethylene-Propylene Rubber) and mechanical devices at side of extruded dielectric cables. They<br />

are designed to fit with controlled interference over the cable insulation and is able to follow the cable's diameter variations<br />

still guaranteeing under any service condition a sufficient positive pressure to control the electric field concentration. Each<br />

components fully examined and tested in the factory. They are currently available at the voltage range up to 300kV and the<br />

maximum allowable cable conductor size is 3000mm 2 (6000kcmil).<br />

Rating & Dimension<br />

Max. Voltage<br />

Max. Lenght<br />

Max. Outer Dia. Max. Weight<br />

kV<br />

mm<br />

mm mm<br />

145 1800 290 220<br />

170 1800 320 250<br />

245 2000 360 300