Electrical Design<br />

2.7 Electrical connection<br />

Clockwise-/counter-clockwise direction<br />

The motors are suitable for clockwise and counter-clockwise rotation. The motors<br />

rotate in the clockwise direction when viewing the drive end (DE) when they are<br />

connected-up according to the circuit diagram.<br />

<strong>1FU8</strong>/2-30<br />

Wiring for clockwise rotation (standard):<br />

– U1 = orange (OG)<br />

– V1 = black (BK)<br />

– W1 = red (RD)<br />

Counter-clockwise rotation can be selected by interchanging two phases.<br />

Line feeder cables<br />

The line feeder cables must be dimensioned acc. to DIN VDE 0298. The number of<br />

required feeder cables, if necessary in parallel, is defined by:<br />

� The max. cable cross-section which can be connected<br />

� The cable type and cable routing<br />

� The ambient temperature<br />

� The permissible current acc. to DIN VDE 0298.<br />