Technical Data<br />

Supply Voltage Nominal 24 Vdc Sensor lifetime<br />

A2.5.1/0604/E<br />

Range (polarity protected) 8... 30 Vdc at full stroke at 25°C 5.000.000 cycles<br />

Operating current max. 20 mA output Burst pressure >150 bar<br />

Protection class acc. to EN 60529 IP65 Medium compatibility HFC, HCFC<br />

Load resistance<br />

R ≤ L<br />

U - 8.0V<br />

B<br />

0.02A<br />

not suitable for ammonia and<br />

inflammable refrigerants!<br />

Temperatures Materials<br />

Operating ambient housing -40.....80 °C Housing cover, pressure connector, Stainless steel<br />

Medium -50...135 °C diaphragm with medium contact 1.4435 / AISI 316L<br />

Transportation and storage -40.....85 °C Vibration at 10 ... 2000 Hz max. 4 g<br />

Accuracy Performance<br />

Temperature range Total error*<br />

PT4-07S -40 ... 0°C ≤ ± 1 % FS<br />

0 ... +60°C ≤ ± 2 % FS<br />

-40 ... +80°C typically ≤ ±2 % FS<br />

PT4-18S -20 ... +20°C ≤ ± 1 % FS<br />

-40 ... +60°C ≤ ± 2 % FS<br />

-40 ... +80°C typically ≤ ±2 % FS<br />

PT4-30S 0 ... +40°C ≤ ± 1 % FS<br />

-20 ... +60°C ≤ ± 2 % FS<br />

-40 ... +80°C typically ≤ ±2 % FS<br />

PT4-50S 0 ... +40°C ≤ ± 1 % FS<br />

-20 ... +60°C ≤ ± 2 % FS<br />

-30 ... +80°C typically ≤ ±2 % FS<br />

*) Total error includes non-linearity, hysteresis, repeatability as well as offset and span<br />

drift due to the temperature changes.<br />

Note: % FS is related to Percentage of Full sensor Scale.<br />

Electrical connection<br />

Pressure transmitters PT4 with current output (2-wire connection)<br />

offer following advantages:<br />

1. More suitable for signal transmission over long<br />

distances<br />

2. Higher immunity to electromagnetic interference<br />

Note: Changing the length of the electrical connection<br />

lead beyond 1.5 m can have a negative impact on electromagnetic<br />

compatibility. Additional protection may be<br />

required.<br />

Electronic Controller<br />

Part Supply, +24Vdc Signal, 4-20mA<br />

PT4-xxS (Pressure transmitter) Pin (terminal) 3 Pin (terminal) 1<br />

PT4-Lxx (Plug/Cable) Brown wire White wire<br />

Former PT3 (Transmitter with fixed cable) Brown wire White wire<br />

47