BA18 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA18<br />

<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

For Rigid <strong>Conduit</strong> & IMC<br />

Type <strong>GUA</strong><br />

With internally threaded bodies<br />

(Cover threads into box)<br />

Use:<br />

To provide access to conductors for pulling,<br />

splicing, maintenance and future changes/<br />

upgrades. Allows connection of straight<br />

conduit runs, branch conduit runs and<br />

90° bends.<br />

Features:<br />

• O-Ring gasket provided to assure<br />

NEMA 4 rating.<br />

• Smooth hub bushings protect insulation<br />

when pulling conductors.<br />

• Cast-in brackets on cover for use with<br />

breaker-bar tools for tightening/loosening.<br />

• Tapered threaded hubs (NPT)<br />

• Threaded for Rigid <strong>Conduit</strong> or IMC<br />

• For additional covers, see Pages BA24-28.<br />

• Functions as a 25% fill sealing fitting when<br />

used with <strong>GUA</strong>SC sealing covers on page<br />

BA26. (Splices and taps are not allowed in<br />

sealing fittings.)<br />

Material/Finish:<br />

1 ⁄2” - 1” Copper-free Aluminum cover with<br />

Malleable Iron body/Zinc Electroplated<br />

Aluminum Enamel<br />

11 ⁄4” - 2” Malleable Iron cover and body/Zinc<br />

Electroplated Aluminum Enamel<br />

Optional Material:<br />

1 ⁄2” - 1” Malleable Iron cover available. Add<br />

suffix “MC” - see table.<br />

For Aluminum cover and body, see page<br />

BB2.<br />

Optional Finish:<br />

Hot Dip or Mechanical Galvanize. Add<br />

Suffix “G” to Malleable Iron catalog number.<br />

Example: <strong>GUA</strong>T-50MCG. Contact your local<br />

representative for pricing and availability.<br />

Third Party Certification:<br />

UL Listed: E-30513<br />

Listed for:<br />

Class I, Div. 1, 2, Groups C, D<br />

Class I, Zone 1, 2, Groups IIA, IIB<br />

Class II, Div. 1, 2, Groups E, F, G<br />

Class III<br />

NEMA 4, 7CD, 9EFG<br />

CSA Certified: 020945<br />

Applicable Third Party Standards:<br />

UL Standard: 886<br />

CSA: C22.2 No. 30<br />

NEC Articles 500-503 & 505<br />

Mil. Spec: Mil-F-28675<br />

Fed. Spec: A-A-50563<br />

Effective December, 2007<br />

Copyright 2007<br />

Trade<br />

Size Catalog Catalog Catalog<br />

(inches) Number Number Number<br />

Aluminum Malleable Iron Malleable Iron<br />

Cover/ Cover/Body Cover/Body<br />

Malleable UL/CSA/FM<br />

Iron Body Certified with<br />

Ground Screw/Lug<br />

1 ⁄2 <strong>GUA</strong>T-50 <strong>GUA</strong>T-50MC <strong>GUA</strong>T-50CS<br />

3 ⁄4 <strong>GUA</strong>T-75 <strong>GUA</strong>T-75MC <strong>GUA</strong>T-75CS<br />

1 <strong>GUA</strong>T-100 <strong>GUA</strong>T-100MC <strong>GUA</strong>T-100CS<br />

1 1 ⁄4 <strong>GUA</strong>T-125 <strong>GUA</strong>T-125CS<br />

1 1 ⁄2 <strong>GUA</strong>T-150 <strong>GUA</strong>T-150CS<br />

2 <strong>GUA</strong>T-200 <strong>GUA</strong>T-200CS<br />

1 ⁄2 <strong>GUA</strong>E-50 <strong>GUA</strong>E-50MC <strong>GUA</strong>E-50 CS<br />

3 ⁄4 <strong>GUA</strong>E-75 <strong>GUA</strong>E-75MC <strong>GUA</strong>E-75 CS<br />

1 <strong>GUA</strong>E-100 <strong>GUA</strong>E-100MC <strong>GUA</strong>E-100CS<br />

1 ⁄2 <strong>GUA</strong>L-50 <strong>GUA</strong>L-50MC <strong>GUA</strong>L-50 CS<br />

3 ⁄4 <strong>GUA</strong>L-75 <strong>GUA</strong>L-75MC <strong>GUA</strong>L-75 CS<br />

1 <strong>GUA</strong>L-100 <strong>GUA</strong>L-100MC <strong>GUA</strong>L-100CS<br />

1 1 ⁄4 <strong>GUA</strong>L-125 <strong>GUA</strong>L-125CS<br />

1 1 ⁄2 <strong>GUA</strong>L-150 <strong>GUA</strong>L-150CS<br />

2 <strong>GUA</strong>L-200 <strong>GUA</strong>L-200CS<br />

1 ⁄2 <strong>GUA</strong>C-50 <strong>GUA</strong>C-50MC <strong>GUA</strong>C-50 CS<br />

3 ⁄4 <strong>GUA</strong>C-75 <strong>GUA</strong>C-75MC <strong>GUA</strong>C-75 CS<br />

1 <strong>GUA</strong>C-100 <strong>GUA</strong>C-100MC <strong>GUA</strong>C-100CS<br />

1 1 ⁄4 <strong>GUA</strong>C-125 <strong>GUA</strong>C-125CS<br />

1 1 ⁄2 <strong>GUA</strong>C-150 <strong>GUA</strong>C-150CS<br />

2 <strong>GUA</strong>C-200 <strong>GUA</strong>C-200CS<br />

1 ⁄2 <strong>GUA</strong>LB-50 <strong>GUA</strong>LB-50MC <strong>GUA</strong>LB-50CS<br />

3 ⁄4 <strong>GUA</strong>LB-75 <strong>GUA</strong>LB-75MC <strong>GUA</strong>LB-75CS<br />

1 <strong>GUA</strong>LB-100 <strong>GUA</strong>LB-100MC <strong>GUA</strong>LB-100CS<br />

1 1 ⁄4 <strong>GUA</strong>LB-125 <strong>GUA</strong>LB-125CS<br />

1 1 ⁄2 <strong>GUA</strong>LB-150 <strong>GUA</strong>LB-150CS<br />

2 <strong>GUA</strong>LB-200 <strong>GUA</strong>LB-200CS<br />

1 ⁄2 <strong>GUA</strong>X-50 <strong>GUA</strong>X-50MC <strong>GUA</strong>X-50 CS<br />

3 ⁄4 <strong>GUA</strong>X-75 <strong>GUA</strong>X-75MC <strong>GUA</strong>X-75 CS<br />

1 <strong>GUA</strong>X-100 <strong>GUA</strong>X-100MC <strong>GUA</strong>X-100CS<br />

1 1 ⁄4 <strong>GUA</strong>X-125 <strong>GUA</strong>X-125CS<br />

1 1 ⁄2 <strong>GUA</strong>X-150 <strong>GUA</strong>X-150CS<br />

2 <strong>GUA</strong>X-200 <strong>GUA</strong>X-200CS<br />

Suggested Specifications:<br />

Hazardous location conduit outlet boxes<br />

shall be used in hazardous locations to<br />

provide for change in conduit direction,<br />

access to conductors, and as pull and splice<br />

boxes. They shall be malleable iron, with<br />

internally threaded bodies and cast in brackets<br />

on the cover. The boxes shall be UL<br />

Listed and suitable for wet locations. Hazardous<br />

location conduit outlet boxes shall<br />

be O-Z/Gedney Type <strong>GUA</strong>.<br />

Dimensional Data:<br />

See Pages BA19 and BA20.<br />

Type <strong>GUA</strong>T<br />

Type <strong>GUA</strong>E<br />

Type <strong>GUA</strong>L<br />

Type <strong>GUA</strong>C<br />

Type <strong>GUA</strong>LB<br />

Type <strong>GUA</strong>X<br />

800-621-1506<br />

www.o-zgedney.com


BA19 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA19<br />

<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

For Rigid <strong>Conduit</strong> & IMC<br />

Dimensional Data:<br />

Type <strong>GUA</strong>T<br />

Type <strong>GUA</strong>E<br />

Type <strong>GUA</strong>L<br />

Effective December, 2007<br />

Copyright 2007<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>T-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>T-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>T-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

<strong>GUA</strong>T-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />

<strong>GUA</strong>T-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />

<strong>GUA</strong>T-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>E-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>E-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>E-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>L-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>L-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>L-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

<strong>GUA</strong>L-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />

<strong>GUA</strong>L-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄8 3 3 ⁄4 5 1 ⁄8 70.0<br />

<strong>GUA</strong>L-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />

800-621-1506<br />

www.o-zgedney.com


BA20 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA20<br />

<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

For Rigid <strong>Conduit</strong> & IMC<br />

Dimensional Data:<br />

Type <strong>GUA</strong>C<br />

Type <strong>GUA</strong>LB<br />

Type <strong>GUA</strong>X<br />

Effective December, 2007<br />

Copyright 2007<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>C-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>C-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>C-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

<strong>GUA</strong>C-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />

<strong>GUA</strong>C-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />

<strong>GUA</strong>C-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>LB-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>LB-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>LB-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

<strong>GUA</strong>LB-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />

<strong>GUA</strong>LB-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />

<strong>GUA</strong>LB-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />

Dimensions in Inches<br />

Catalog Trade Cover Volume<br />

Number Size A B C D E Opening Cu. In.<br />

<strong>GUA</strong>X-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />

<strong>GUA</strong>X-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />

<strong>GUA</strong>X-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />

<strong>GUA</strong>X-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />

<strong>GUA</strong>X-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />

<strong>GUA</strong>X-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />

800-621-1506<br />

www.o-zgedney.com


BA24 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA24<br />

Hub Covers<br />

For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

Type <strong>GUA</strong>HC<br />

Use:<br />

Provides NPT thread hub for mounting pendant<br />

light fixtures (luminaires) on 1 ⁄2”, 3 ⁄4” and<br />

1” trade size Type <strong>GUA</strong> outlet boxes.<br />

Features:<br />

• O-Ring gasket provided to assure watertightness.<br />

• Tapered threaded hub (NPT)<br />

• Provided with anti-rotation set-screws.<br />

• Maximum weight capacity: 50 lbs. per<br />

NEC Section 314-27(B).<br />

Material/Finish:<br />

Malleable Iron/Zinc Electroplated<br />

Steel Set Screws<br />

Buna-N O-Ring<br />

Optional Finish:<br />

Hot Dip or Mechanical Galvanized.<br />

Add suffix “G” to standard catalog number.<br />

Contact your local representative for pricing<br />

and availability.<br />

Third Party Certification:<br />

UL Listed: E-97032<br />

Class I, Div. 1, 2, Groups C, D<br />

Class I, Zone 1, 2, Groups IIA, IIB<br />

Class II, Div. 1, 2, Groups E, F, G<br />

Class III<br />

Suitable for wet locations<br />

CSA Certified: 020945<br />

Applicable Third Party Standards:<br />

UL Standard: 886<br />

CSA Standard: C22.2 No. 30<br />

NEC Articles 500-503 & 505<br />

Mil. Spec: Mil-F-28675<br />

Fed. Spec: A-A-50563<br />

Suggested Specifications:<br />

Where accessory covers for hazardous<br />

location outlet boxes are required for<br />

sealing, increasing volume or mounting<br />

pendant lighting fixtures (luminaires), they<br />

shall be malleable iron construction and UL<br />

Listed. These accessory covers shall be<br />

O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />

<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />

Note:<br />

<strong>GUA</strong>HE-50 and <strong>GUA</strong>HC-75 are suitable<br />

for use with 1 ⁄2”, 3 ⁄4” and 1” trade size Type<br />

<strong>GUA</strong> malleable iron outlet boxes only. See<br />

page BA18.<br />

Effective December, 2007<br />

Copyright 2007<br />

Hub Dimensions in Inches<br />

Trade Size Catalog Max. Dia.<br />

(inches) Number C A<br />

1 ⁄2 <strong>GUA</strong>HC-50 3 1 ⁄2 1 5 ⁄8<br />

3 ⁄4 <strong>GUA</strong>HC-75 3 1 ⁄2 1 5 ⁄8<br />

TYPE <strong>GUA</strong> OUTLET BOX - PAGE BA18<br />

<strong>GUA</strong>HC <strong>GUA</strong>HC<br />

ECHF - PAGE BA17<br />

800-621-1506<br />

www.o-zgedney.com


BA25 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA25<br />

Fixture Canopy<br />

For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

Type <strong>GUA</strong>FC<br />

Use:<br />

Provides additional wiring space and<br />

NPT threaded hub for mounting pendant<br />

light<br />

fixtures (luminaires) on 1 ⁄2”, 3 ⁄4” and 1” trade<br />

size Type <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong>.<br />

Features:<br />

• Increases internal wiring volume (12.5 cu. in.)<br />

• Side port allows access to conductors<br />

after fixture is mounted.<br />

• O-Ring gasket provided to assure<br />

watertightness.<br />

• Provided with anti-rotation set-screws.<br />

• Maximum weight capacity: 50 lbs. per<br />

NEC Section 314-27(B).<br />

Material/Finish:<br />

Malleable Iron/Zinc Electroplated<br />

Steel Set Screws<br />

Buna-N O-Ring<br />

Optional Finish:<br />

Hot Dip or Mechanical Galvanized.<br />

Add suffix “G” to standard catalog number.<br />

Contact your local representative for pricing<br />

and availability.<br />

Third Party Certification:<br />

UL Listed: E-97032<br />

Class I, Div. 1, 2, Groups C, D<br />

Class I, Zone 1, 2, Groups IIA, IIB<br />

Class II, Div. 1, 2, Groups E, F, G<br />

Class III<br />

Suitable for wet locations<br />

CSA Certified: 020945<br />

Applicable Third Party Standards:<br />

UL Standards: 886<br />

CSA Standard: C22.2 No. 30<br />

NEC Articles 500-503 & 505<br />

Mil. Spec: Mil-F-28675<br />

Fed. Spec: A-A-50563<br />

Suggested Specifications:<br />

Where accessory covers for hazardous<br />

location outlet boxes are required for<br />

sealing, increasing volume or mounting<br />

pendant lighting fixtures, they shall be<br />

malleable iron construction and UL<br />

Listed. These accessory covers shall be<br />

O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />

<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />

Effective December, 2007<br />

Copyright 2007<br />

Hub Dimensions in Inches<br />

Trade Size Catalog<br />

(inches) Number A B<br />

1 ⁄2 <strong>GUA</strong>FC-50 3 3 ⁄4” 3 1 ⁄2”<br />

3 ⁄4 <strong>GUA</strong>FC-75 3 3 ⁄4” 3 1 ⁄2”<br />

TYPE <strong>GUA</strong> <strong>GUA</strong> OUTLET BOX - PAGE - PAGE BA18 BA18<br />

<strong>GUA</strong>HC <strong>GUA</strong>FC<br />

Note:<br />

<strong>GUA</strong>FC-50 and <strong>GUA</strong>FC-75 are suitable<br />

for use with 1 ⁄2”, 3 ⁄4” and 1” trade size Type<br />

<strong>GUA</strong> malleable iron outlet boxes only. See<br />

page BA18.<br />

ECHF - PAGE BA17<br />

800-621-1506<br />

www.o-zgedney.com


BA26 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA26<br />

Sealing Cover<br />

For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />

Type <strong>GUA</strong>SC<br />

Use:<br />

Converts 1 ⁄2”, 3 ⁄4” and 1” trade size Type <strong>GUA</strong><br />

malleable iron outlet boxes into 25% fill<br />

sealing fittings.<br />

Features:<br />

• Removable plug for pouring sealing<br />

compound.<br />

• O-Ring gasket provided to assure<br />

watertightness.<br />

• Can be used with O-Z/Gedney EYC<br />

sealing compound.<br />

Material/Finish:<br />

Malleable Iron/Zinc Electroplated<br />

Steel Set Screws<br />

Buna-N O-Ring<br />

Optional Finish:<br />

Hot Dip or Mechanical Galvanized.<br />

Add suffix “G” to standard catalog number.<br />

Contact your local representative for pricing<br />

and availability.<br />

Third Party Certification:<br />

UL Listed: E-97032<br />

Class I, Div. 1, 2, Groups C, D<br />

Class I, Zone 1, 2, Groups IIA, IIB<br />

Class II, Div. 1, 2, Groups E, F, G<br />

Class III<br />

Suitable for wet locations<br />

CSA Certified: 020945<br />

Applicable Third Party Standards:<br />

UL Standard: 886<br />

CSA Standard: C22.2 No. 30<br />

NEC Articles 500-503 & 505<br />

Mil. Spec: Mil-F-28675<br />

Fed. Spec: A-A-50563<br />

Suggested Specifications:<br />

Where accessory covers for hazardous<br />

location outlet boxes are required for<br />

sealing, increasing volume or mounting<br />

pendant lighting fixtures, they shall be<br />

malleable iron construction and UL<br />

Listed. These accessory covers shall be<br />

O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />

<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />

Note:<br />

1 <strong>GUA</strong>SC-1 is suitable for use with 1 ⁄2”, 3 ⁄4”<br />

and 1” trade size Type <strong>GUA</strong> malleable iron<br />

outlet boxes only. See page BA18.<br />

2 Splices and taps not allowed in sealing<br />

fittings per NEC Article 501.<br />

Effective December, 2007<br />

Copyright 2007<br />

Catalog Turning Maximum<br />

Number Radius “R” Body Height “A”<br />

<strong>GUA</strong>SC-1 2 1 ⁄2” 1 3 ⁄4”<br />

800-621-1506<br />

www.o-zgedney.com


BA27 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA27<br />

Threaded Extension<br />

For <strong>GUA</strong> & GUJ <strong>Outlet</strong> <strong>Boxes</strong><br />

Type <strong>GUA</strong>TE<br />

Use:<br />

Use with standard <strong>GUA</strong> malleable iron or<br />

aluminum outlet box cover on malleable<br />

<strong>GUA</strong> box to increase depth and internal<br />

volume.<br />

Features:<br />

• Increased internal wiring volume<br />

(6.5 cu. in.)<br />

• O-Ring gasket provided to assure<br />

watertightness<br />

Material/Finish:<br />

Malleable Iron/Zinc Electroplated<br />

Buna-N O-Ring<br />

Optional Finish:<br />

Hot Dip or Mechanical Galvanized.<br />

Add suffix “G” to standard catalog number.<br />

Contact your local representative for pricing<br />

and availability.<br />

Third Party Certification:<br />

UL Listed: E-97032<br />

Class I, Div. 1, 2, Groups C, D<br />

Class I, Zone 1, 2, Groups IIA, IIB<br />

Class II, Div. 1, 2, Groups E, F, G<br />

Class III<br />

Suitable for wet locations<br />

CSA Certified: 043437<br />

Applicable Third Party Standards:<br />

UL Standard: 886<br />

CSA Standard: C22.2 No. 30<br />

NEC Articles 500-503 & 505<br />

Mil. Spec: Mil-F-28675<br />

Fed. Spec: A-A-50563<br />

Note:<br />

<strong>GUA</strong>TE-1 is suitable for use with 1 ⁄2”, 3 ⁄4”<br />

and 1” trade size Type <strong>GUA</strong> malleable iron<br />

outlet boxes only. See page BA18.<br />

Suggested Specifications:<br />

Where accessory covers for hazardous<br />

location outlet boxes are required for sealing,<br />

increasing volume or mounting pendant<br />

lighting fixtures, they shall be malleable<br />

iron construction and UL Listed. These<br />

accessory covers shall be O-Z/Gedney Type<br />

<strong>GUA</strong>SC, <strong>GUA</strong>TE, <strong>GUA</strong>DC, GUJDC, <strong>GUA</strong>FC<br />

or <strong>GUA</strong>HC.<br />

Effective December, 2007<br />

Copyright 2007<br />

Dimensions in Inches<br />

Catalog Max. Dia. Volume<br />

Number A B Cu. In.<br />

<strong>GUA</strong>TE-1 1 9 ⁄16” 3 1 ⁄2 6.5<br />

B<br />

A<br />

Type <strong>GUA</strong>TE<br />

800-621-1506<br />

www.o-zgedney.com