GUA Conduit Outlet Boxes - Emerson Industrial Automation
GUA Conduit Outlet Boxes - Emerson Industrial Automation
GUA Conduit Outlet Boxes - Emerson Industrial Automation
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
BA18 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA18<br />
<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
For Rigid <strong>Conduit</strong> & IMC<br />
Type <strong>GUA</strong><br />
With internally threaded bodies<br />
(Cover threads into box)<br />
Use:<br />
To provide access to conductors for pulling,<br />
splicing, maintenance and future changes/<br />
upgrades. Allows connection of straight<br />
conduit runs, branch conduit runs and<br />
90° bends.<br />
Features:<br />
• O-Ring gasket provided to assure<br />
NEMA 4 rating.<br />
• Smooth hub bushings protect insulation<br />
when pulling conductors.<br />
• Cast-in brackets on cover for use with<br />
breaker-bar tools for tightening/loosening.<br />
• Tapered threaded hubs (NPT)<br />
• Threaded for Rigid <strong>Conduit</strong> or IMC<br />
• For additional covers, see Pages BA24-28.<br />
• Functions as a 25% fill sealing fitting when<br />
used with <strong>GUA</strong>SC sealing covers on page<br />
BA26. (Splices and taps are not allowed in<br />
sealing fittings.)<br />
Material/Finish:<br />
1 ⁄2” - 1” Copper-free Aluminum cover with<br />
Malleable Iron body/Zinc Electroplated<br />
Aluminum Enamel<br />
11 ⁄4” - 2” Malleable Iron cover and body/Zinc<br />
Electroplated Aluminum Enamel<br />
Optional Material:<br />
1 ⁄2” - 1” Malleable Iron cover available. Add<br />
suffix “MC” - see table.<br />
For Aluminum cover and body, see page<br />
BB2.<br />
Optional Finish:<br />
Hot Dip or Mechanical Galvanize. Add<br />
Suffix “G” to Malleable Iron catalog number.<br />
Example: <strong>GUA</strong>T-50MCG. Contact your local<br />
representative for pricing and availability.<br />
Third Party Certification:<br />
UL Listed: E-30513<br />
Listed for:<br />
Class I, Div. 1, 2, Groups C, D<br />
Class I, Zone 1, 2, Groups IIA, IIB<br />
Class II, Div. 1, 2, Groups E, F, G<br />
Class III<br />
NEMA 4, 7CD, 9EFG<br />
CSA Certified: 020945<br />
Applicable Third Party Standards:<br />
UL Standard: 886<br />
CSA: C22.2 No. 30<br />
NEC Articles 500-503 & 505<br />
Mil. Spec: Mil-F-28675<br />
Fed. Spec: A-A-50563<br />
Effective December, 2007<br />
Copyright 2007<br />
Trade<br />
Size Catalog Catalog Catalog<br />
(inches) Number Number Number<br />
Aluminum Malleable Iron Malleable Iron<br />
Cover/ Cover/Body Cover/Body<br />
Malleable UL/CSA/FM<br />
Iron Body Certified with<br />
Ground Screw/Lug<br />
1 ⁄2 <strong>GUA</strong>T-50 <strong>GUA</strong>T-50MC <strong>GUA</strong>T-50CS<br />
3 ⁄4 <strong>GUA</strong>T-75 <strong>GUA</strong>T-75MC <strong>GUA</strong>T-75CS<br />
1 <strong>GUA</strong>T-100 <strong>GUA</strong>T-100MC <strong>GUA</strong>T-100CS<br />
1 1 ⁄4 <strong>GUA</strong>T-125 <strong>GUA</strong>T-125CS<br />
1 1 ⁄2 <strong>GUA</strong>T-150 <strong>GUA</strong>T-150CS<br />
2 <strong>GUA</strong>T-200 <strong>GUA</strong>T-200CS<br />
1 ⁄2 <strong>GUA</strong>E-50 <strong>GUA</strong>E-50MC <strong>GUA</strong>E-50 CS<br />
3 ⁄4 <strong>GUA</strong>E-75 <strong>GUA</strong>E-75MC <strong>GUA</strong>E-75 CS<br />
1 <strong>GUA</strong>E-100 <strong>GUA</strong>E-100MC <strong>GUA</strong>E-100CS<br />
1 ⁄2 <strong>GUA</strong>L-50 <strong>GUA</strong>L-50MC <strong>GUA</strong>L-50 CS<br />
3 ⁄4 <strong>GUA</strong>L-75 <strong>GUA</strong>L-75MC <strong>GUA</strong>L-75 CS<br />
1 <strong>GUA</strong>L-100 <strong>GUA</strong>L-100MC <strong>GUA</strong>L-100CS<br />
1 1 ⁄4 <strong>GUA</strong>L-125 <strong>GUA</strong>L-125CS<br />
1 1 ⁄2 <strong>GUA</strong>L-150 <strong>GUA</strong>L-150CS<br />
2 <strong>GUA</strong>L-200 <strong>GUA</strong>L-200CS<br />
1 ⁄2 <strong>GUA</strong>C-50 <strong>GUA</strong>C-50MC <strong>GUA</strong>C-50 CS<br />
3 ⁄4 <strong>GUA</strong>C-75 <strong>GUA</strong>C-75MC <strong>GUA</strong>C-75 CS<br />
1 <strong>GUA</strong>C-100 <strong>GUA</strong>C-100MC <strong>GUA</strong>C-100CS<br />
1 1 ⁄4 <strong>GUA</strong>C-125 <strong>GUA</strong>C-125CS<br />
1 1 ⁄2 <strong>GUA</strong>C-150 <strong>GUA</strong>C-150CS<br />
2 <strong>GUA</strong>C-200 <strong>GUA</strong>C-200CS<br />
1 ⁄2 <strong>GUA</strong>LB-50 <strong>GUA</strong>LB-50MC <strong>GUA</strong>LB-50CS<br />
3 ⁄4 <strong>GUA</strong>LB-75 <strong>GUA</strong>LB-75MC <strong>GUA</strong>LB-75CS<br />
1 <strong>GUA</strong>LB-100 <strong>GUA</strong>LB-100MC <strong>GUA</strong>LB-100CS<br />
1 1 ⁄4 <strong>GUA</strong>LB-125 <strong>GUA</strong>LB-125CS<br />
1 1 ⁄2 <strong>GUA</strong>LB-150 <strong>GUA</strong>LB-150CS<br />
2 <strong>GUA</strong>LB-200 <strong>GUA</strong>LB-200CS<br />
1 ⁄2 <strong>GUA</strong>X-50 <strong>GUA</strong>X-50MC <strong>GUA</strong>X-50 CS<br />
3 ⁄4 <strong>GUA</strong>X-75 <strong>GUA</strong>X-75MC <strong>GUA</strong>X-75 CS<br />
1 <strong>GUA</strong>X-100 <strong>GUA</strong>X-100MC <strong>GUA</strong>X-100CS<br />
1 1 ⁄4 <strong>GUA</strong>X-125 <strong>GUA</strong>X-125CS<br />
1 1 ⁄2 <strong>GUA</strong>X-150 <strong>GUA</strong>X-150CS<br />
2 <strong>GUA</strong>X-200 <strong>GUA</strong>X-200CS<br />
Suggested Specifications:<br />
Hazardous location conduit outlet boxes<br />
shall be used in hazardous locations to<br />
provide for change in conduit direction,<br />
access to conductors, and as pull and splice<br />
boxes. They shall be malleable iron, with<br />
internally threaded bodies and cast in brackets<br />
on the cover. The boxes shall be UL<br />
Listed and suitable for wet locations. Hazardous<br />
location conduit outlet boxes shall<br />
be O-Z/Gedney Type <strong>GUA</strong>.<br />
Dimensional Data:<br />
See Pages BA19 and BA20.<br />
Type <strong>GUA</strong>T<br />
Type <strong>GUA</strong>E<br />
Type <strong>GUA</strong>L<br />
Type <strong>GUA</strong>C<br />
Type <strong>GUA</strong>LB<br />
Type <strong>GUA</strong>X<br />
800-621-1506<br />
www.o-zgedney.com
BA19 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA19<br />
<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
For Rigid <strong>Conduit</strong> & IMC<br />
Dimensional Data:<br />
Type <strong>GUA</strong>T<br />
Type <strong>GUA</strong>E<br />
Type <strong>GUA</strong>L<br />
Effective December, 2007<br />
Copyright 2007<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>T-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>T-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>T-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
<strong>GUA</strong>T-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />
<strong>GUA</strong>T-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />
<strong>GUA</strong>T-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>E-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>E-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>E-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>L-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>L-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>L-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
<strong>GUA</strong>L-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />
<strong>GUA</strong>L-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄8 3 3 ⁄4 5 1 ⁄8 70.0<br />
<strong>GUA</strong>L-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />
800-621-1506<br />
www.o-zgedney.com
BA20 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA20<br />
<strong>Conduit</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
For Rigid <strong>Conduit</strong> & IMC<br />
Dimensional Data:<br />
Type <strong>GUA</strong>C<br />
Type <strong>GUA</strong>LB<br />
Type <strong>GUA</strong>X<br />
Effective December, 2007<br />
Copyright 2007<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>C-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>C-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>C-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
<strong>GUA</strong>C-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />
<strong>GUA</strong>C-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />
<strong>GUA</strong>C-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>LB-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>LB-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>LB-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
<strong>GUA</strong>LB-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />
<strong>GUA</strong>LB-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />
<strong>GUA</strong>LB-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />
Dimensions in Inches<br />
Catalog Trade Cover Volume<br />
Number Size A B C D E Opening Cu. In.<br />
<strong>GUA</strong>X-50 1 ⁄2 2 3 5 ⁄8 3 ⁄4 5 ⁄8 2 3 13.5<br />
<strong>GUA</strong>X-75 3 ⁄4 2 1 ⁄4 3 5 ⁄8 3 ⁄4 3 ⁄4 2 1 ⁄8 3 15.0<br />
<strong>GUA</strong>X-100 1 2 1 ⁄2 3 5 ⁄8 7 ⁄8 7 ⁄8 2 3 ⁄8 3 17.0<br />
<strong>GUA</strong>X-125 1 1 ⁄4 3 1 ⁄8 4 1 ⁄4 1 1 ⁄8 1 1 ⁄8 3 3 3 ⁄4 30.0<br />
<strong>GUA</strong>X-150 1 1 ⁄2 3 3 ⁄4 5 5 ⁄8 1 1 ⁄8 1 1 ⁄4 3 3 ⁄4 5 1 ⁄8 70.0<br />
<strong>GUA</strong>X-200 2 4 1 ⁄8 5 5 ⁄8 7 ⁄8 7 ⁄8 4 1 ⁄8 5 1 ⁄8 75.0<br />
800-621-1506<br />
www.o-zgedney.com
BA24 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA24<br />
Hub Covers<br />
For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
Type <strong>GUA</strong>HC<br />
Use:<br />
Provides NPT thread hub for mounting pendant<br />
light fixtures (luminaires) on 1 ⁄2”, 3 ⁄4” and<br />
1” trade size Type <strong>GUA</strong> outlet boxes.<br />
Features:<br />
• O-Ring gasket provided to assure watertightness.<br />
• Tapered threaded hub (NPT)<br />
• Provided with anti-rotation set-screws.<br />
• Maximum weight capacity: 50 lbs. per<br />
NEC Section 314-27(B).<br />
Material/Finish:<br />
Malleable Iron/Zinc Electroplated<br />
Steel Set Screws<br />
Buna-N O-Ring<br />
Optional Finish:<br />
Hot Dip or Mechanical Galvanized.<br />
Add suffix “G” to standard catalog number.<br />
Contact your local representative for pricing<br />
and availability.<br />
Third Party Certification:<br />
UL Listed: E-97032<br />
Class I, Div. 1, 2, Groups C, D<br />
Class I, Zone 1, 2, Groups IIA, IIB<br />
Class II, Div. 1, 2, Groups E, F, G<br />
Class III<br />
Suitable for wet locations<br />
CSA Certified: 020945<br />
Applicable Third Party Standards:<br />
UL Standard: 886<br />
CSA Standard: C22.2 No. 30<br />
NEC Articles 500-503 & 505<br />
Mil. Spec: Mil-F-28675<br />
Fed. Spec: A-A-50563<br />
Suggested Specifications:<br />
Where accessory covers for hazardous<br />
location outlet boxes are required for<br />
sealing, increasing volume or mounting<br />
pendant lighting fixtures (luminaires), they<br />
shall be malleable iron construction and UL<br />
Listed. These accessory covers shall be<br />
O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />
<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />
Note:<br />
<strong>GUA</strong>HE-50 and <strong>GUA</strong>HC-75 are suitable<br />
for use with 1 ⁄2”, 3 ⁄4” and 1” trade size Type<br />
<strong>GUA</strong> malleable iron outlet boxes only. See<br />
page BA18.<br />
Effective December, 2007<br />
Copyright 2007<br />
Hub Dimensions in Inches<br />
Trade Size Catalog Max. Dia.<br />
(inches) Number C A<br />
1 ⁄2 <strong>GUA</strong>HC-50 3 1 ⁄2 1 5 ⁄8<br />
3 ⁄4 <strong>GUA</strong>HC-75 3 1 ⁄2 1 5 ⁄8<br />
TYPE <strong>GUA</strong> OUTLET BOX - PAGE BA18<br />
<strong>GUA</strong>HC <strong>GUA</strong>HC<br />
ECHF - PAGE BA17<br />
800-621-1506<br />
www.o-zgedney.com
BA25 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA25<br />
Fixture Canopy<br />
For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
Type <strong>GUA</strong>FC<br />
Use:<br />
Provides additional wiring space and<br />
NPT threaded hub for mounting pendant<br />
light<br />
fixtures (luminaires) on 1 ⁄2”, 3 ⁄4” and 1” trade<br />
size Type <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong>.<br />
Features:<br />
• Increases internal wiring volume (12.5 cu. in.)<br />
• Side port allows access to conductors<br />
after fixture is mounted.<br />
• O-Ring gasket provided to assure<br />
watertightness.<br />
• Provided with anti-rotation set-screws.<br />
• Maximum weight capacity: 50 lbs. per<br />
NEC Section 314-27(B).<br />
Material/Finish:<br />
Malleable Iron/Zinc Electroplated<br />
Steel Set Screws<br />
Buna-N O-Ring<br />
Optional Finish:<br />
Hot Dip or Mechanical Galvanized.<br />
Add suffix “G” to standard catalog number.<br />
Contact your local representative for pricing<br />
and availability.<br />
Third Party Certification:<br />
UL Listed: E-97032<br />
Class I, Div. 1, 2, Groups C, D<br />
Class I, Zone 1, 2, Groups IIA, IIB<br />
Class II, Div. 1, 2, Groups E, F, G<br />
Class III<br />
Suitable for wet locations<br />
CSA Certified: 020945<br />
Applicable Third Party Standards:<br />
UL Standards: 886<br />
CSA Standard: C22.2 No. 30<br />
NEC Articles 500-503 & 505<br />
Mil. Spec: Mil-F-28675<br />
Fed. Spec: A-A-50563<br />
Suggested Specifications:<br />
Where accessory covers for hazardous<br />
location outlet boxes are required for<br />
sealing, increasing volume or mounting<br />
pendant lighting fixtures, they shall be<br />
malleable iron construction and UL<br />
Listed. These accessory covers shall be<br />
O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />
<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />
Effective December, 2007<br />
Copyright 2007<br />
Hub Dimensions in Inches<br />
Trade Size Catalog<br />
(inches) Number A B<br />
1 ⁄2 <strong>GUA</strong>FC-50 3 3 ⁄4” 3 1 ⁄2”<br />
3 ⁄4 <strong>GUA</strong>FC-75 3 3 ⁄4” 3 1 ⁄2”<br />
TYPE <strong>GUA</strong> <strong>GUA</strong> OUTLET BOX - PAGE - PAGE BA18 BA18<br />
<strong>GUA</strong>HC <strong>GUA</strong>FC<br />
Note:<br />
<strong>GUA</strong>FC-50 and <strong>GUA</strong>FC-75 are suitable<br />
for use with 1 ⁄2”, 3 ⁄4” and 1” trade size Type<br />
<strong>GUA</strong> malleable iron outlet boxes only. See<br />
page BA18.<br />
ECHF - PAGE BA17<br />
800-621-1506<br />
www.o-zgedney.com
BA26 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA26<br />
Sealing Cover<br />
For <strong>GUA</strong> <strong>Outlet</strong> <strong>Boxes</strong><br />
Type <strong>GUA</strong>SC<br />
Use:<br />
Converts 1 ⁄2”, 3 ⁄4” and 1” trade size Type <strong>GUA</strong><br />
malleable iron outlet boxes into 25% fill<br />
sealing fittings.<br />
Features:<br />
• Removable plug for pouring sealing<br />
compound.<br />
• O-Ring gasket provided to assure<br />
watertightness.<br />
• Can be used with O-Z/Gedney EYC<br />
sealing compound.<br />
Material/Finish:<br />
Malleable Iron/Zinc Electroplated<br />
Steel Set Screws<br />
Buna-N O-Ring<br />
Optional Finish:<br />
Hot Dip or Mechanical Galvanized.<br />
Add suffix “G” to standard catalog number.<br />
Contact your local representative for pricing<br />
and availability.<br />
Third Party Certification:<br />
UL Listed: E-97032<br />
Class I, Div. 1, 2, Groups C, D<br />
Class I, Zone 1, 2, Groups IIA, IIB<br />
Class II, Div. 1, 2, Groups E, F, G<br />
Class III<br />
Suitable for wet locations<br />
CSA Certified: 020945<br />
Applicable Third Party Standards:<br />
UL Standard: 886<br />
CSA Standard: C22.2 No. 30<br />
NEC Articles 500-503 & 505<br />
Mil. Spec: Mil-F-28675<br />
Fed. Spec: A-A-50563<br />
Suggested Specifications:<br />
Where accessory covers for hazardous<br />
location outlet boxes are required for<br />
sealing, increasing volume or mounting<br />
pendant lighting fixtures, they shall be<br />
malleable iron construction and UL<br />
Listed. These accessory covers shall be<br />
O-Z/Gedney Type <strong>GUA</strong>SC, <strong>GUA</strong>TE,<br />
<strong>GUA</strong>DC, <strong>GUA</strong>FC or <strong>GUA</strong>HC.<br />
Note:<br />
1 <strong>GUA</strong>SC-1 is suitable for use with 1 ⁄2”, 3 ⁄4”<br />
and 1” trade size Type <strong>GUA</strong> malleable iron<br />
outlet boxes only. See page BA18.<br />
2 Splices and taps not allowed in sealing<br />
fittings per NEC Article 501.<br />
Effective December, 2007<br />
Copyright 2007<br />
Catalog Turning Maximum<br />
Number Radius “R” Body Height “A”<br />
<strong>GUA</strong>SC-1 2 1 ⁄2” 1 3 ⁄4”<br />
800-621-1506<br />
www.o-zgedney.com
BA27 Hazardous Location Fittings & <strong>Outlet</strong> <strong>Boxes</strong> BA27<br />
Threaded Extension<br />
For <strong>GUA</strong> & GUJ <strong>Outlet</strong> <strong>Boxes</strong><br />
Type <strong>GUA</strong>TE<br />
Use:<br />
Use with standard <strong>GUA</strong> malleable iron or<br />
aluminum outlet box cover on malleable<br />
<strong>GUA</strong> box to increase depth and internal<br />
volume.<br />
Features:<br />
• Increased internal wiring volume<br />
(6.5 cu. in.)<br />
• O-Ring gasket provided to assure<br />
watertightness<br />
Material/Finish:<br />
Malleable Iron/Zinc Electroplated<br />
Buna-N O-Ring<br />
Optional Finish:<br />
Hot Dip or Mechanical Galvanized.<br />
Add suffix “G” to standard catalog number.<br />
Contact your local representative for pricing<br />
and availability.<br />
Third Party Certification:<br />
UL Listed: E-97032<br />
Class I, Div. 1, 2, Groups C, D<br />
Class I, Zone 1, 2, Groups IIA, IIB<br />
Class II, Div. 1, 2, Groups E, F, G<br />
Class III<br />
Suitable for wet locations<br />
CSA Certified: 043437<br />
Applicable Third Party Standards:<br />
UL Standard: 886<br />
CSA Standard: C22.2 No. 30<br />
NEC Articles 500-503 & 505<br />
Mil. Spec: Mil-F-28675<br />
Fed. Spec: A-A-50563<br />
Note:<br />
<strong>GUA</strong>TE-1 is suitable for use with 1 ⁄2”, 3 ⁄4”<br />
and 1” trade size Type <strong>GUA</strong> malleable iron<br />
outlet boxes only. See page BA18.<br />
Suggested Specifications:<br />
Where accessory covers for hazardous<br />
location outlet boxes are required for sealing,<br />
increasing volume or mounting pendant<br />
lighting fixtures, they shall be malleable<br />
iron construction and UL Listed. These<br />
accessory covers shall be O-Z/Gedney Type<br />
<strong>GUA</strong>SC, <strong>GUA</strong>TE, <strong>GUA</strong>DC, GUJDC, <strong>GUA</strong>FC<br />
or <strong>GUA</strong>HC.<br />
Effective December, 2007<br />
Copyright 2007<br />
Dimensions in Inches<br />
Catalog Max. Dia. Volume<br />
Number A B Cu. In.<br />
<strong>GUA</strong>TE-1 1 9 ⁄16” 3 1 ⁄2 6.5<br />
B<br />
A<br />
Type <strong>GUA</strong>TE<br />
800-621-1506<br />
www.o-zgedney.com