Date Description Effect Accident<br />

Type<br />

24/01/1997Damage to steam injector on the<br />

water supply to the seals on a<br />

gas holder led, indirectly, to loss<br />

<strong>of</strong> water from the seal <strong>and</strong><br />

release <strong>of</strong> gas. No ignition.<br />

07/02/1997Confusion over instructions led<br />

to overfilling <strong>of</strong> a storage tank<br />

with ethanol during ship <strong>of</strong>floading.<br />

No ignition.<br />

04/05/1997High pressure naptha entered a<br />

low pressure 'brine string' on a<br />

brine storage cavity. Release<br />

through relief valve <strong>and</strong> burst<br />

flange seal.<br />

01/07/1997Release from LNG tank during<br />

modification work on piping.<br />

Site Type Category Comment<br />

None Release Gas holder 1 Seal fires addressed (in <strong>protection</strong> <strong>based</strong><br />

assessment)<br />

None<br />

Release Storage <strong>of</strong><br />

flammable liquids<br />

4 injured (on site) Release Brine Cavity<br />

Storage<br />

1 This is a precursor to a pool fire, which sould be<br />

covered by a <strong>protection</strong> <strong>based</strong> assessment for<br />

bulk storage <strong>of</strong> flammable liquids<br />

1 Potential magnitude <strong>of</strong> event similar to that for<br />

the representative event(s) for this type <strong>of</strong><br />

installation<br />

None Release LNG Storage 1 QRA methodology addresses leaks from<br />

storage tanks<br />

06/07/1997Slug catcher shut in <strong>and</strong> pressure None Release Gas Terminal 4 The assessment approach for this type <strong>of</strong><br />

increased due to thermal<br />

expansion. Pressure relieved<br />

through PRV, which failed to reseat.<br />

installation depends on site-specific details.<br />

16/09/1997Failure <strong>of</strong> wall / floor weld on<br />

storage tank led to release <strong>of</strong><br />

xylene. No ignition<br />

01/11/1997Petrol storage tank overfilled<br />

after failure <strong>of</strong> gauging system,<br />

material spilt into bund. No<br />

ignition.<br />

09/03/1998Valve opened during<br />

maintenance work giving release<br />

<strong>of</strong> organic substances. Wrong<br />

valve had been isolated. No<br />

ignition.<br />

22/08/1998Weld failed on floating ro<strong>of</strong><br />

drain on a gasoline storage tank.<br />

Liquid released into bund, no<br />

ignition.<br />

None<br />

None<br />

None<br />

None<br />

Release Storage <strong>of</strong><br />

flammable liquids<br />

Release Storage <strong>of</strong><br />

flammable liquids<br />

Release Chemicals<br />

manufacturing<br />

Release Storage <strong>of</strong><br />

flammable liquids<br />

1 This is a precursor to a pool fire, which sould be<br />

covered by a <strong>protection</strong> <strong>based</strong> assessment for<br />

bulk storage <strong>of</strong> flammable liquids<br />

1 This is a precursor to a pool fire, which sould be<br />

covered by a <strong>protection</strong> <strong>based</strong> assessment for<br />

bulk storage <strong>of</strong> flammable liquids<br />

1 Potential magnitude <strong>of</strong> event less than that for<br />

the representative event(s) for this type <strong>of</strong><br />

installation<br />

1 This is a precursor to a pool fire, which sould be<br />

covered by a <strong>protection</strong> <strong>based</strong> assessment for<br />

bulk storage <strong>of</strong> flammable liquids