11.01.2013 Views

Enclosed Switches and Safety Switches - Elektroskandia

Enclosed Switches and Safety Switches - Elektroskandia

Enclosed Switches and Safety Switches - Elektroskandia

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Ratings<br />

IEC 60 947-3<br />

<strong>Safety</strong> switches type LBAS ( > 125A)<br />

Metal enclosure (aluminium alloy)<br />

I e AC23A 63–630 A<br />

I th 160–630 A<br />

For motors P e up to 355 kW<br />

U e 400–690V<br />

Degree of protection: IP 65<br />

Ratings KSE 3160 KSE 3250 KSE 3315 KSE 3500 KSE 3630<br />

LBAS 125/S LBAS 160/S LBAS 200/S LBAS 250/S LBAS 400/S LBAS 630/S<br />

LBAS 125/SK 1) LBAS 160/SK 1)<br />

Isolation<br />

voltage V 690 690 1000 1000 1000 1000<br />

Uimp kV 12 12 12 12 12 12<br />

Rated thermal<br />

current, I th A 160 160 270 315 500 630<br />

Operating<br />

voltage, U e V 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690 400 500 690<br />

Rated current,<br />

I e at AC23A A 125 90 70 160 125 80 250 250 250 315 315 315 500 500 350 630 580 350<br />

Max fuse A 200 200 200 250 250 250 400 400 400 400 400 400 630 630 630 800 800 800<br />

Conditional short<br />

circuit current kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50<br />

Fuse protected<br />

short-circuit making<br />

capacity kA 18 18 18 18 18 18 35 35 35 35 35 35 50 50 50 60 60 60<br />

Rated making<br />

capacity<br />

≤ 100 A cos ϕ = 0,45<br />

> 100 A cos ϕ = 0,35 A 1250 900 700 1600 1250 800 2500 2500 2500 3150 3150 3150 5000 5000 3500 6300 5800 3500<br />

Rated breaking<br />

capacity<br />

≤ 100 A cos ϕ = 0,45<br />

> 100 A cos ϕ = 0,35 A 1000 720 560 1280 1000 640 2000 2000 2000 2520 2520 2520 4000 4000 2800 5760 4800 2800<br />

Max motor power kW 55 55 55 75 75 75 132 160 200 160 200 250 250 315 315 315 355 355<br />

Terminals for cable mm 2 10–70 (Cu) 10–70 (Cu) 2) 2) 2) 2) 2)<br />

section or 1) or 1)<br />

Earth terminal mm 2 50 50 2x300 2x300 2x300 2x300<br />

Exp<strong>and</strong>er washes<br />

for safety protection<br />

in case of shortcircuit<br />

Included Included Included Included Included Included<br />

1) Terminal screw for cable lugs.(M8)<br />

2) Terminal screw for cable lugs. (M12)<br />

10<br />

ABB Cewe

Hooray! Your file is uploaded and ready to be published.

Saved successfully!