Class 9422 Devices<br />
16<br />
Class 9422 Dimensions for 30A, 60A, <strong>and</strong> 100A <strong>Switches</strong><br />
1.00<br />
B<br />
1.50*<br />
4.50<br />
A<br />
0.30<br />
* .30 for 100A Class J fuses<br />
Lug Data<br />
Switch Type Maximum Voltage Fuse Type Class Dimension A Dimension B<br />
30A<br />
60A<br />
100A<br />
1.41<br />
<strong>Disconnect</strong><br />
Switch Size<br />
4.00<br />
5.50<br />
6.20<br />
1.41<br />
30A, 250V<br />
30A, 600V<br />
30A, 600V<br />
60A, 250V<br />
60A, 600V<br />
60A, 600V<br />
100A, 250V<br />
100A, 600V<br />
100A, 600V<br />
1.00<br />
30A, 60A = 3 .50<br />
100A = 5.7 5<br />
H, K, R<br />
H, K, R<br />
J<br />
H, K, R<br />
H, K, R<br />
J<br />
H, K, R<br />
H, K, R<br />
J<br />
© 1997 <strong>Square</strong> D All Rights Reserved<br />
1.625<br />
4.25<br />
1.625<br />
2.25<br />
4.75<br />
1.625<br />
Wire Size<br />
Minimum — Maximum<br />
30A #14-#2 Cu, #10-#2 Al<br />
60A #14-#2 Cu, #10-#2 Al<br />
100A #10-#0 Cu, #6-#0 Al<br />
200A #6-300 KcmiL Cu or Al<br />
400A #4-500 KcmiL Cu<br />
8.80"<br />
D<br />
4.00"<br />
100A = 5.10"<br />
D = Distance from h<strong>and</strong>le mechanism<br />
mounting surface to disconnect switch<br />
surface. D min. = 6 5/8" D max. = 18"<br />
3.25<br />
5.25<br />
3.25<br />
12/97