Setting instruction Manual<br />

for boilers with<br />

<strong>SM</strong> <strong>30001</strong><br />

Printed Circuit board<br />

mod.<br />

RBC 24 (open chamber)<br />

RBS 24 (room sealed)<br />

CE 0694 TA99E009.A0704<br />

<strong>Technical</strong> Specification RADIANT BRUCIATORI S.p.A. Montelabbate (PU) ITALY ENGLISH


INDEX<br />

CONTROL PANEL page 1<br />

<strong>SM</strong> <strong>30001</strong> ELECTRONIC PRINTED CIRCUIT BOARD:<br />

FUNCTIONS SETTING PROCEDURE page 2<br />

BOILER TYPE SETTING PROCEDURE page 2<br />

MAXIMUM GAS PRESSURE SETTING page 4<br />

MINIMUM GAS PRESSURE SETTING page 4<br />

HEATING OUTPUT SETTING page 4<br />

CENTRAL HEATING / D.H.W. MODE OPERATION page 4<br />

RESET PROCEDURE page 4<br />

TECHNICAL SPECIFICATIONS page 5<br />

GAS DATA TABLE page 6<br />

GAS PRESSURE SETTING page 6<br />

HEATING OUTPUT PRESSURE DIAGRAM page 6<br />

ELECTRICAL WIRING DIAGRAM page 7<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings


1<br />

ON / OFF POWER BUTTON<br />

2<br />

HEATING TEMPERATURE ADJUSTMENT KNOB<br />

3<br />

DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT<br />

KNOB<br />

4<br />

STABLE LIGHT: POWER ON<br />

FLASHING LIGHT: FLAME ON<br />

5<br />

STABLE LIGHT: 40°C TEMPERATURE<br />

FLASHING LIGHT: WATER DEFICIENCY<br />

LIGHT OFF: WATER PRESSURE LEVEL 1 bar<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings<br />

CONTROL PANEL<br />

1<br />

6<br />

STABLE LIGHT: 50°C TEMPERATURE<br />

FLASHING LIGHT: FLUE SAFETY THERMOSTAT LOCK-<br />

OUT (for open chamber model only)<br />

7<br />

STABLE LIGHT: 60°C TEMPERATURE<br />

FLASHING LIGHT: FLAME LOCK-OUT<br />

8<br />

STABLE LIGHT: 70°C TEMPERATURE<br />

FLASHING LIGHT: HIGH LIMIT THERMOSTAT LOCK-OUT<br />

9<br />

STABLE LIGHT: 80°C TEMPERATURE<br />

FLASHING LIGHT: D. HOT WATER / HEATING SENSOR<br />

FAILURE


P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings<br />

M12<br />

M11<br />

M1<br />

M2<br />

<strong>SM</strong> <strong>30001</strong> PRINTED CIRCUIT BOARD<br />

cod. 76666LA<br />

M13 M3<br />

M8<br />

M6<br />

M4<br />

M9<br />

FUNCTIONS SETTING<br />

1-A STANDARD 30-80°C - OFF<br />

REDUCED 25-40°C - ON<br />

2-B ACTIVE - OFF<br />

DISCONNECTED - ON<br />

3-C DISCONNECTED - OFF<br />

ACTIVE - ON<br />

4-D 64-65°C - OFF<br />

58-61°C - ON<br />

BOILER TYPE SETTING<br />

5-E OFF<br />

ON<br />

6-F OFF<br />

ON<br />

6-F OFF<br />

2<br />

ON<br />

�<br />

�<br />

�<br />

�<br />

M5<br />

M7<br />

M10<br />

HEATING TEMPERATURE<br />

SETTING<br />

SHORT-CYCLING Function<br />

TIMER (3 min.)<br />

WATER-HAMMER Prevention<br />

� Function<br />

HOT WATER<br />

TEMPERATURE<br />

SETTING<br />

NOT APPLICABLE<br />

DUAL CIRCUIT EXCHANGER type<br />

� INSTANTANEOUS TYPE BOILER<br />

�<br />

NOT APPLICABLE<br />

NATURAL GAS OPERATION<br />

L.P.G. OPERATION


CONTROL<br />

PANEL<br />

CONTROLS (fig. 1-2)<br />

8 9 10 11 12 13<br />

1 2 3 4<br />

1. “MAXR” MAXIMUM HEATING POTENTIOMETER<br />

2. “MIN” MINIMUM GAS POTENTIOMETER<br />

3. “RLA” STARTING STEP POTENTIOMETER<br />

4. “SPAZ” CHIMNEY-SWEEPER FUNCTION<br />

5. GAS PRESSURE POINT - OUTLET<br />

6. GAS ADJUSTMENT SCREW<br />

7. GAS PRESSURE POINT – INLET<br />

8. STABLE LIGHT: POWER ON<br />

FLASHING LIGHT: FLAME ON<br />

9. STABLE LIGHT: 40°C TEMPERATURE<br />

FLASHING LIGHT: WATER DEFICIENCY<br />

LIGHT OFF: WATER PRESSURE LEVEL 1.2 bar<br />

10. STABLE LIGHT: 50°C TEMPERATURE<br />

Fig. 2<br />

GAS VALVE<br />

NORDGAS<br />

NV0111122901<br />

FLASHING LIGHT: FLUE SAFETY THERMOSTAL LOCK-OUT (for open chamber model only)<br />

11. STABLE LIGHT: 60°C TEMPERATURE<br />

FLASHING LIGHT: FLAME LOCK-OUT<br />

12. STABLE LIGHT: 70°C TEMPERATURE<br />

FLASHING LIGHT: HIGH LIMIT THERMOSTAT LOCK-OUT<br />

13. STABLE LIGHT: 80°C TEMPERATURE<br />

FLASHING LIGHT: D. HOT WATER / HEATING SENSOR FAILURE<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings 3<br />

5<br />

6<br />

7<br />

Fig. 1


MAXIMUM GAS PRESSURE SETTING<br />

• Unscrew 5 gas pressure point screw (fig. 1) on the gas valve and insert a manometer;<br />

• Turn heating and domestic hot water setting knobs to the maximum and remove the 2 knob by<br />

extracting them with a pliers:<br />

• Use a Ø2.5 ÷ 3 mm cross-type screwdriver and turn “maxR” 1 potentiometer (fig. 2) clockwise to the<br />

maximum;<br />

• Switch the boiler ON;<br />

• Keep 4 potentiometer (chimney sweeper function) (fig. 2) pressed for 10 seconds;<br />

• The manometer will show the maximum gas pressure value; if that value is different than the one<br />

stated on the Data Plate (see Gas pressure adjustment table pag. 6), modify it as follows: turn the 6<br />

gas adjustment screw (fig. 1) clockwise to increase gas pressure and counter clockwise to decrease<br />

gas pressure to reach the data Plate pressure value.<br />

MINIMUM GAS PRESSURE SETTING<br />

• Turn “maxR” 1 potentiometer (fig. 2) counter clockwise to the minimum;<br />

• Turn 2 potentiometer (minimum gas) (fig. 2) clockwise to increase or counter clockwise to decrease<br />

the gas pressure;<br />

• Turn 3 potentiometer (starting step) (fig. 2) to the middle position of its full setting;<br />

HEATING OUTPUT SETTING<br />

• Turn the “maxR” 1 potentiometer (maximum heating) (fig. 2) clockwise and set the pressure value<br />

according to the system requirement. (see Heating Output Pressure Diagram at page 6);<br />

• Remove the silicon pipe from the pressure point 5 (fig. 1);<br />

• Close tightly the pressure point screw and make sure there are no gas leaks;<br />

• Fit the 2 plastic knobs back to position;<br />

• Put ON/OFF button in OFF and than ON position.<br />

CENTRAL HEATING / DOMESTIC HOT WATER MODE OPERATION<br />

If the boiler has to operate on both central heating and domestic hot water mode, do NOT set the central<br />

heating and d.h. water knobs to the minimum (zero);<br />

• Set the domestic hot water knob to ‘0’ (zero) for a HEATING ONLY mode;<br />

• Set the central heating knob to ‘0’ (zero) for a WATER ONLY mode;<br />

RESET PROCEDURE<br />

In case of a ‘Flame Lock-out’ (indicator 11 or 12 fig. 2 page 3), reset the boiler by putting the ON/OFF<br />

button in OFF and than ON position.<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings 4


TECHNICAL SPECIFICATION<br />

New generation printed circuit board with easy settings of boiler parameters.<br />

Special features:<br />

Main functions / features<br />

� Chimney-sweeper function (15 minutes)<br />

� Pump over-run function (2 minutes)<br />

� Pump inactivity protection system<br />

� Water-Hammer prevention function<br />

� Suitable for outside temperature sensor connection<br />

� Suitable for remote control system connection<br />

� Self-diagnostic<br />

� Continuous electronic modulation for central heating and domestic hot water<br />

� Adjustable heating output<br />

� Adjustable starting step<br />

Exclusively for technicians settings<br />

� Standard / reduced heating temperature from 30 to 80 °C / 25 to 40°C<br />

• Water-Hammer prevention function<br />

• Short cycling function-3 minutes stand-by, heating circuit<br />

• Maximum gas pressure setting<br />

• Minimum gas pressure setting<br />

• Heating output setting<br />

User Settings<br />

• On / Off operation<br />

• Heating temperature adjustment from 30 to 80 °C / 25 to 45°C<br />

• Domestic Hot Water adjustment from 35 to 65 °C<br />

• Mode selection knob: summer/winter/heating only<br />

• Lock-out<br />

• Normal water pressure<br />

• Water deficiency safety switch<br />

• Temperature indicator<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings 5


model: RBC 24 RBS 24<br />

GAS DATA TABLE<br />

NATURAL GAS<br />

G 20<br />

LIQUID BUTAN GAS<br />

G 30<br />

LIQUID PROPANE<br />

GAS G 31<br />

Lower Wobbe index (15°C; 1013<br />

mbar)<br />

MJ/Nm 3 45.67 80.58 70.69<br />

Rated feed pressure mbar 20 30 37<br />

Minimum feed pressure mbar 17 20 25<br />

Main burner: 12 Jets - Ø jet mm 1.30 0.77 0.77<br />

Consuption (15°C; 1013 mbar) m 3 /h 2.71 - -<br />

Consuption (15°C; 1013 mbar) kg/h - 2.019 1.99<br />

GAS PRESSURE SETTING<br />

models Natural Gas G 20 G.P.L. G 30/31<br />

min. max. min. max<br />

RBC 24 mbar 2.2 10.8 5 30<br />

RBS 24 mbar 1.5 10.4 5 30<br />

Heating Output in kW<br />

28<br />

26<br />

24<br />

22<br />

20<br />

18<br />

16<br />

14<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

NATURAL GAS<br />

HEATING OUTPUT MAXIMUM PRESSURE DIAGRAM<br />

(G20 Natural Gas - G30/31 L.P.G.)<br />

L.P.G.<br />

0<br />

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33<br />

Gas pressure in mbar<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings 6<br />

mod.<br />

RBC 24<br />

(open<br />

chamber)<br />

RBS 24<br />

(room<br />

sealed)


lack<br />

PRINTED CIRCUIT BOARD <strong>SM</strong><strong>30001</strong> (COD. 76666LA)<br />

brown<br />

M12<br />

M11<br />

M1<br />

M2<br />

PAC<br />

1,5bar<br />

18<br />

SS<br />

red/black<br />

light-blue<br />

light-blue<br />

19<br />

black<br />

M13<br />

light-blue<br />

white/black<br />

EA TR<br />

5<br />

brown<br />

+ -<br />

M10<br />

black<br />

brown<br />

M8<br />

SR MF<br />

black<br />

45 46 47 48 49 50<br />

C<br />

6 7 8 9<br />

brown<br />

grey<br />

M5<br />

TS<br />

VG<br />

OP<br />

M3<br />

black<br />

M6<br />

light-blue<br />

M4<br />

1 4<br />

VG<br />

3<br />

green<br />

white<br />

45 46 47 48 49 50<br />

M12<br />

L<br />

N<br />

WIRING DIAGRAM<br />

red<br />

PA<br />

51<br />

blue<br />

52<br />

52 T P<br />

1 2 3 4<br />

P.C.B. <strong>SM</strong> <strong>30001</strong> – boiler settings 7<br />

light-blue<br />

orange<br />

brown<br />

IG<br />

orange<br />

2<br />

230V<br />

50 Hz<br />

L N<br />

light-blue<br />

M5<br />

M7<br />

M9 M10<br />

M9<br />

M8<br />

M2<br />

black<br />

230V<br />

50 Hz<br />

TF<br />

52 T<br />

brown<br />

P<br />

TA SE<br />

black<br />

18<br />

orange<br />

M3<br />

orange<br />

51 52 53 54<br />

18<br />

ER<br />

KEY<br />

L<br />

N<br />

PAC<br />

IG<br />

SS<br />

SR<br />

C<br />

TS<br />

M.F.<br />

TA<br />

TF<br />

PA<br />

EV<br />

VG<br />

EA<br />

ER<br />

TR<br />

Optional<br />

TERMINAL<br />

BLOCK<br />

M7<br />

M13<br />

M8<br />

- LINE<br />

- NEUTRAL<br />

- WATER PRESSURE SWITCH<br />

- MAIN SWITCH<br />

- D.H. WATER SENSOR<br />

- HEATING SENSOR<br />

- CIRCULATION PUMP<br />

- SAFETY THERMOSTAT<br />

- ELECTRONIC FLOWSWITCH<br />

- ROOM THERMOSTAT<br />

- SAFETY FLUE THERMOSTAT<br />

- AIR PRESSURE SWITCH<br />

- FAN<br />

- GAS VALVE<br />

- IGNITION ELECTRODE<br />

- IONISATION ELECTRODE<br />

- TRANSFORMER<br />

brown<br />

L<br />

18<br />

EV<br />

light-blue<br />

N<br />

19<br />

M11


RADIANT BRUCIATORI s.p.a.<br />

Via Pantanelli, 164/166 - 61025 Loc. Montelabbate (PU)<br />

Tel. +39 0721 9079.1 • fax. +39 0721 9079279<br />

e-mail: tecnico@radiant • Internet: http://www.radiant.it<br />

ALL DESCRIPTIONS AND ILLUSTRATIONS CONTAINED IN THIS LEAFLET HAVE<br />

BEEN CAREFULLY PREPARED BUT WE RESERVE THE RIGHT TO MAKE CHANGES<br />

AND IMPROVEMENTS IN OUR PRODUCTS WHITCH MAY AFFECT THE<br />

ACCURANCY OF THE INFORMATION CONTAINED IN THIS LEAFLET. E + OE<br />

ALL RIGHTS RESERVED. NO PART OF THIS DOCUMENT MAY BE REPRODUCED,<br />

SAVED IN STORAGE SYSTEMS OR TRAN<strong>SM</strong>ITTED IN ANY FORM OR BY ANY<br />

MEANS, WHETHER ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING<br />

OR OTHERS, WITHOUT THE MANUFACTURER'S PRIOR AUTHORISATION IN<br />

WRITING.<br />

TA99E009.A0704