6.3.3 Grounding by Off-Shore-Plates<br />
If armoured cables are used in connection with junction boxes, the metal glands of the<br />
incoming and outgoing cables are electrically connected with each other by so-called<br />
off-shore plates at the junction boxes and are connected to the local ground (potential<br />
equalization). This is admissible only within each PA area.<br />
Please, also note our instructions as per item 6.2!<br />
Off-shore plates are brass plates in the junction box housing with cut threads where the<br />
glands are screwed in and thus grounded.<br />
Off-shore plates must not be inserted into INDUSTRONIC EX intercom stations!<br />
Example:<br />
Plastic junction box with off-shore technology, metal EX armouring glands, grounded<br />
by an inserted off-shore plate.<br />
Grounding connection of the off-shore<br />
plate, e.g. to the grounding terminal and,<br />
by another gland, directly to the local<br />
ground (PA)<br />
Off-Shore plate (brass)<br />
Armouring gland, screwed through<br />
the housing into the off-shore plate<br />
Steel wire armoured cable<br />
<strong>Cabling</strong> <strong>Guidelines</strong> <strong>for</strong> <strong>INTRON</strong>-D / <strong>INTRON</strong>-D plus 16 / 24<br />
Doc. no. 330-001-403 • Rev. 9 • EN • 15.10.2010