3.3 Common data classes<br />

12<br />

The following tables indicate mandatory, conditional and optional attributes of each Common<br />

Data Class (CDC) that are supported by the <strong>EM920</strong>. Mandatory attributes (M) are always<br />

present.<br />

Single point status (SPS)<br />

Attribute Name Attribute Type FC M/O/C<br />

stVal BOOLEAN ST M<br />

q Quality ST M<br />

t TimeStamp ST M<br />

d VISIBLE STRING64 DC O<br />

Double point status (DPS)<br />

Common data class is not supported.<br />

Integer status (INS)<br />

Attribute Name Attribute Type FC M/O/C<br />

stVal INT32 ST M<br />

q Quality ST M<br />

t TimeStamp ST M<br />

d VISIBLE STRING64 DC O<br />

Protection activation information (ACT)<br />

Common data class is not supported.<br />

Directional protection activation information (ACD)<br />

Common data class is not supported.<br />

Security violation counting (SEC)<br />

Common data class is not supported.<br />

Binary counter reading (BCR)<br />

Attribute Name Attribute Type FC M/O/C Comments<br />

actVal INT32 ST M<br />

q Quality ST M<br />

t TimeStamp ST M<br />

units Unit CF O<br />

pulsQty FLOAT32 CF M<br />

d VISIBLE STRING64 DC O<br />

Measured value (MV)<br />

Attribute Name Attribute Type FC M/O/C Comments<br />

mag AnalogueValue MX M Only one of the attributes (i or f) of<br />

the AnalogueValue may be present<br />

for a given instance of DATA<br />

q Quality MX M<br />

t TimeStamp MX M<br />

units Unit CF O<br />

db INT32U CF O<br />

d VISIBLE STRING64 DC O