<strong>Instruction</strong> Manual <strong>McSMOKE</strong> <strong>RF</strong><br />

PROGRAMMING<br />

Adjust the settings of all smoke alarms that are to be connected together at the same address. There are 8<br />

possible coding settings, selectable using a 3-pole DIP switch (1). Each combination represents a different radio<br />

channel.<br />

The MCSMOKE <strong>RF</strong> has a test button (2) for testing the correct functioning of the smoke alarm. After connection<br />

to the radio module, test all smoke alarms together.<br />

LED-status indicator<br />

Test procedure:<br />

Reset (3)<br />

Acoustic alarm<br />

LED-status indicator<br />

Test (2)<br />

LED functional indicator<br />

Press the RESET button (3) on the radio module. The red and green indicators should light once.<br />

Press the TEST button on the smoke alarm and keep it pressed. The smoke alarm that was triggered<br />

will now light, and the red indicator will flash. The red indicator on the radio module will now stay lit<br />

continuously.<br />

Do not release the TEST button, since the radio transmission is performed sequentially. Wait until the alarm<br />

is sounded at all the smoke alarms at the same address. The alarm at the REMOTE smoke alarms will<br />

sound, but the red indicator will not light. The red indicator on the radio module that was triggered will<br />

remain lit continuously .<br />

Release the TEST button on the smoke alarm that was triggered. The red indicator on the radio module<br />

will now stay lit until the RESET button is pressed. All indicators on the REMOTE smoke alarms will now be<br />

switched off automatically.<br />

Identification of the smoke alarm that has been triggered<br />

The smoke alarm that has been triggered can be identified by the red LED indicator staying lit continuously.<br />

POPP <strong>GmbH</strong> • Bad Berneck • Germany • www.popp-elektro.de<br />

McSmoke_<strong>RF</strong>.indd 13 18.10.2004 13:04:43 Uhr