Focolare <strong>80</strong> <strong>Idro</strong> <strong>Crystal</strong> - <strong>DSA</strong><br />
50 cm<br />
Roof slope<br />
CHIMNEY CAP: DISTANCES AND POSITIONING UNI 10683/98<br />
6. CONNECTION TO THE FLUE<br />
Distance between roof ridge and<br />
chimney<br />
Minimum height of chimney<br />
(measured from the outlet )<br />
¡ A (m) H (m)<br />
15°<br />
30°<br />
45°<br />
60°<br />
2 m 10 m<br />
1<br />
m<br />
min. H<br />
(1) In the case of adjacent flues, one chimney cap must rise above<br />
the other by at least 50 cm to prevent the transfer of pressure<br />
between the flues.<br />
(1) The chimney cap must not have any obstacles within 10 m from<br />
walls, pitch, and trees. In such case, it must be raised at least 1 m<br />
above the obstacles.<br />
The chimney cap must rise above the roof ridge by at least 1 m.<br />
¡<br />
>A<br />
< 1,85 m 0.50 m above the ridge<br />
> 1,85 m 1.00 m from roof<br />
< 1,50 m 0.50 m above the ridge<br />
> 1,50 m 1.30 m from roof<br />
< 1,30 m 0.50 m above the ridge<br />
> 1,30 m 2.00 m from roof<br />
< 1,20 m 0.50 m above the ridge<br />
> 1,20 m 2.60 m from roof<br />
Picture 10<br />
Picture 11<br />
Picture 12<br />
The connection to the flue (exhaust channel or pipe fitting) must be made using rigid pipes in aluminium plated steel<br />
with minimum thickness of 2 mm or in 316 stainless steel with minimum thickness of 1 mm.<br />
It is prohibited to use flexible metal pipes or asbestos cement pipes because they are subject to splitting or<br />
breakage, which can lead to fume leakage, jeopardising the safety of the connection itself.<br />
The diameter of opening for the connection to the connection of chimney must correspond to the smoke pipe diameter<br />
at least. The opening should have a connection to the wall to put inside the outlet pipe and a rose window.<br />
><br />
_ A<br />
(1)Ridge axis<br />
colmo<br />
(2)Roof<br />
6097811 Rev.06 – EN 25<br />
0.5 m