Bypass Model Installation<br />
STEP FIVE: Bypass Duct Installation<br />
1<br />
2<br />
On the duct opposite the humidifier Bypass install, cut<br />
a 6-in. diameter duct hole.<br />
• If the humidifier is on the supply duct, the 6-in.<br />
diameter hole should be on the return.<br />
• If the humidifier is on the return duct, the 6-in.<br />
diameter hole should be on the supply.<br />
Secure a 6-in. round duct starter collar into the 6-in.<br />
duct hole.<br />
MOUNTING<br />
MCR29933<br />
1<br />
2<br />
Use rigid or aluminized flexible 6-in. duct to connect<br />
the starter collar to the humidifier bypass port.<br />
Secure the duct to the humidifier port with self-drilling<br />
sheet metal screws using the pre-drilled holes on the<br />
bypass port. For added seal, wrap sheet metal tape<br />
around the duct to port connection point.<br />
2<br />
MCR29878<br />
Bypass mounting is complete. Go to page 11.<br />
Before proceeding to the next step:<br />
I secured the humidifier to the duct as instructed.<br />
<strong>Humidifier</strong> <strong>69</strong>-<strong>2413EF</strong>—<strong>01</strong> 9