VOLTA 100 / VOLTA 133 Notice de montage - Sammode
VOLTA 100 / VOLTA 133 Notice de montage - Sammode
VOLTA 100 / VOLTA 133 Notice de montage - Sammode
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>VOLTA</strong> <strong>100</strong> / <strong>VOLTA</strong> <strong>133</strong><br />
Replacement lighting<br />
Automatic Testing System:<br />
<strong>de</strong>scription and instruction notes<br />
<strong>VOLTA</strong> light fittings are provi<strong>de</strong>d with an emergency unit able to run tests automatically, in or<strong>de</strong>r to check the<br />
working or<strong>de</strong>r of the emergency system:<br />
- Function test (30 seconds): Once a week, it checks the good working or<strong>de</strong>r of components, including lamps.<br />
- Duration test (1 or 3 hours): Once a year, it <strong>de</strong>termines whether the batteries are able to fulfill the<br />
requirements.<br />
When possible, these tests are <strong>de</strong>signed to happen during a period of non-occupancy, in or<strong>de</strong>r to avoid<br />
annoyance. The test result is indicated by the colour of the LED insi<strong>de</strong> the luminaire:<br />
LED colour Status What must be done ?<br />
permanent green Everything is OK Nothing<br />
fast blinking green<br />
(0,1s on / 0,1s off)<br />
Function test in progress<br />
Nothing<br />
slow blinking green<br />
(1s on / 1s off)<br />
Duration test in progress<br />
Nothing<br />
permanent red<br />
slow blinking red<br />
(1s on / 1s off)<br />
fast blinking red<br />
(0,1s on / 0,1s off)<br />
Lamp failure<br />
Open circuit, or lamp <strong>de</strong>fault<br />
Battery failure<br />
Battery failed the duration test or the<br />
function test<br />
Incorrect charging current<br />
Batteries cannot charge<br />
Change the lamp if nee<strong>de</strong>d, or check the<br />
position of the lamp<br />
If batteries are new, the connection<br />
poles may have been inverted.<br />
If not, batteries need to be changed.<br />
Batteries need to be changed.<br />
N.B.: After commissioning, the luminaire is <strong>de</strong>signed to launch a commissioning test in or<strong>de</strong>r to check the<br />
good working or<strong>de</strong>r of components and the emergency duration. This test will run from 5 to 30 days after the<br />
commissioning of luminaires.<br />
- WARNING: AFTER COMMISSIONING, DO NOT FORGET TO RECONNECT THE BATTERY.<br />
- AFTER EACH RELAMPING, RECONNECT THE CONNECTOR AND PUSH THE RED BUTTON TO<br />
LAUNCH A 30 SECONDS AUTO-TEST. THE LED LIGHT MUST THEN GO PERMANENT GREEN.<br />
Sammo<strong>de</strong> Sammo<strong>de</strong> SA SA<br />
SAT SAT Gamme Gamme <strong>VOLTA</strong> <strong>VOLTA</strong><br />
24 24 rue rue <strong>de</strong>s <strong>de</strong>s Amandiers, Amandiers, F-75020 F-75020 Paris Paris 3/4 4/4 Octobre Octobre 2011 2011