ELENCO WRITE REGISTER:<br />
COMANDI SCRITTURA DISPONIBILI<br />
Preset Single Register<br />
Preset Multiple Registers<br />
INDIRIZZO DESCRIZIONE LIMITI MIN MAX<br />
38 Setpoint Freddo -200 ÷ 260 [°C]<br />
39 Banda Setpoint Freddo 10 ÷ 200 [°C]<br />
40 Setpoint Caldo 250 ÷ 650 [°C]<br />
41 Banda Setpoint Caldo 10 ÷ 200 [°C]<br />
42 Correzione Setpoint 0 ÷ 3<br />
43 Set Freddo 1 -200 ÷ 260 [°C]<br />
44 TA Esterna freddo 1 400 ÷ 500 [°C]<br />
45 Set Freddo 2 -200 ÷ 260 [°C]<br />
46 TA Esterna freddo 2 -400 ÷ 500 [°C]<br />
47 Set Caldo 1 250 ÷ 650 [°C]<br />
48 TA Esterna Caldo 1 -400 ÷ 500 [°C]<br />
49 Set Caldo 2 250 ÷ 650 [°C]<br />
50 TA Esterna Caldo 2 -400 ÷ 500 [°C]<br />
51 Set Acqua Sanitaria -250 ÷ 650 [°C]<br />
52 Banda Acqua Sanitaria 10 ÷ 200 [°C]<br />
53 Percentuale potenza richiesta da termostato 0 ÷ 100 [%]<br />
54 PWD_SET_VMF -32768 ÷ 32767<br />
ELENCO ECCEZIONI:<br />
!<br />
Di seguito si riportano i codici di errore restituiti dalla scheda Modu Control:<br />
ECCEZIONE DESCRIZIONE<br />
ILLEGAL FUNCTION Il codice funzione richiesto non gestito dalla scheda.<br />
ILLEGAL DATA ADDRESS La richiesta dati contiene un riferimento ad un indirizzo non<br />
disponibile nella scheda.<br />
ILLEGAL DATA VALUE La richiesta di scrittura del dato contiene un valore fuori range<br />
non è quindi premessa la scrittura.<br />
IT 6343831_00 / Ver - 4.10