ELENCO WRITE REGISTER:<br />

COMANDI SCRITTURA DISPONIBILI<br />

Preset Single Register<br />

Preset Multiple Registers<br />

INDIRIZZO DESCRIZIONE LIMITI MIN MAX<br />

38 Setpoint Freddo -200 ÷ 260 [°C]<br />

39 Banda Setpoint Freddo 10 ÷ 200 [°C]<br />

40 Setpoint Caldo 250 ÷ 650 [°C]<br />

41 Banda Setpoint Caldo 10 ÷ 200 [°C]<br />

42 Correzione Setpoint 0 ÷ 3<br />

43 Set Freddo 1 -200 ÷ 260 [°C]<br />

44 TA Esterna freddo 1 400 ÷ 500 [°C]<br />

45 Set Freddo 2 -200 ÷ 260 [°C]<br />

46 TA Esterna freddo 2 -400 ÷ 500 [°C]<br />

47 Set Caldo 1 250 ÷ 650 [°C]<br />

48 TA Esterna Caldo 1 -400 ÷ 500 [°C]<br />

49 Set Caldo 2 250 ÷ 650 [°C]<br />

50 TA Esterna Caldo 2 -400 ÷ 500 [°C]<br />

51 Set Acqua Sanitaria -250 ÷ 650 [°C]<br />

52 Banda Acqua Sanitaria 10 ÷ 200 [°C]<br />

53 Percentuale potenza richiesta da termostato 0 ÷ 100 [%]<br />

54 PWD_SET_VMF -32768 ÷ 32767<br />

ELENCO ECCEZIONI:<br />

!<br />

Di seguito si riportano i codici di errore restituiti dalla scheda Modu Control:<br />

ECCEZIONE DESCRIZIONE<br />

ILLEGAL FUNCTION Il codice funzione richiesto non gestito dalla scheda.<br />

ILLEGAL DATA ADDRESS La richiesta dati contiene un riferimento ad un indirizzo non<br />

disponibile nella scheda.<br />

ILLEGAL DATA VALUE La richiesta di scrittura del dato contiene un valore fuori range<br />

non è quindi premessa la scrittura.<br />