MIN<br />
value<br />
MAX<br />
value<br />
Supervisor write enabled<br />
Parameter function<br />
0 1 This parameter enables the write commands for the supervisor; this enablement is set<br />
on the basis of the value selected for this parameter:<br />
0 = write command disabled<br />
1 = write command enabled<br />
Remember that the read commands are always active.<br />
MIN<br />
value<br />
MAX<br />
value<br />
Air temperature limit 1 (*)<br />
Parameter function<br />
-25°C 45°C This parameter indicates the external air temperature at which the machine can produce<br />
its maximum water value (this value is specified in parameter P - St1).<br />
MIN<br />
value<br />
MAX<br />
value<br />
Water temperature limit 1 (*)<br />
Parameter function<br />
0°C 70°C This parameter indicates the maximum temperature of the water produced, in line with<br />
the outside air temperature specified in parameter O - LA1.<br />
MIN<br />
value<br />
MAX<br />
value<br />
Air temperature limit 2 (*)<br />
Parameter function<br />
-25°C 45°C This parameter indicates the external air temperature at which the machine can produce<br />
its maximum water value (this value is specified in parameter R - St2).<br />
MIN<br />
value<br />
MAX<br />
value<br />
Water temperature limit 2 (*)<br />
Parameter function<br />
0°C 70°C This parameter indicates the maximum temperature of the water produced, in line with<br />
the outside air temperature specified in parameter Q - LA2.<br />
MIN<br />
value<br />
MAX<br />
value<br />
Maximum heating set point<br />
Parameter function<br />
15°C 65°C This parameter indicates the maximum temperature of the water produced by the unit in<br />
heat mode.<br />
(*) these parameters describe the operating limits (in heat mode) of the compressor, beyond which it is automatically<br />
switched off and, when necessary, heat operation is guaranteed by the supplementary electric heater;<br />
j<br />
j j Parameters only visible in heat pump models<br />
Parameters only visible in the models with DCP installed<br />
Parameters only visible in models set for<br />
Parameters only visible in bicompressor models<br />
hot domestic water production<br />
Parameters only visible in the models with inverter compressor<br />
6343831_00 / Ver - 4.10<br />
GB<br />