WRITE LIST REGISTER:<br />

COMANDI SCRITTURA DISPONIBILI<br />

Preset Single Register<br />

Preset Multiple Registers<br />

ADDRESS DESCRIPTION MIN-MAX LIMITS<br />

38 Cooling setpoint -200 - 260 [°C]<br />

39 Cooling setpoint band 10 - 200 [°C]<br />

40 Heating setpoint 250 - 650 [°C]<br />

41 Heating setpoint band 10 - 200 [°C]<br />

42 Setpoint correction 0 - 3<br />

43 Cooling setpoint 1 -200 - 260 [°C]<br />

44 External AT in cool mode 1 400 - 500 [°C]<br />

45 Cooling setpoint 2 -200 - 260 [°C]<br />

46 External AT in cool mode 2 -400 - 500 [°C]<br />

47 Heating setpoint 1 250 - 650 [°C]<br />

48 External AT in heat mode 1 -400 - 500 [°C]<br />

49 Heating setpoint 2 250 - 650 [°C]<br />

50 External AT in heat mode 2 -400 - 500 [°C]<br />

51 Domestic water setpoint -250 - 650 [°C]<br />

52 Domestic water band 10 - 200 [°C]<br />

53 Power percentage requested from the thermostat 0 - 100 [%]<br />

54 PWD_SET_VMF -32768 - 32767<br />

LIST OF EXCEPTIONS:<br />

!<br />

The error codes highlighted by the Modu Control card are shown below:<br />

EXCEPTION DESCRIPTION<br />

The requested function code is not managed by the card.<br />

The data request contains a reference to an address that is not<br />

available on the card.<br />

The data write request contains a value that is out of range,<br />

so writing is not allowed.<br />

6343831_00 / Ver - 4.10<br />