Safety procedures and norms for the use of voltage transformers<br />

1. Transport:<br />

• All installation and transport operations must be carried out in compliance with the applicable safety precautions.<br />

2. Installation:<br />

• Make sure the specifications on the label are compatible with the system’s electrical parameters.<br />

• Make sure that the transformers are physically intact and undamaged in all their parts before attempt<strong>ing</strong> to put<br />

them in operation.<br />

• Maintain the required insulation distance between primary connections and the body of the system.<br />

• Make sure the connections between primary and secondary clips are made properly, both in terms of tightness<br />

and in terms of polarity.<br />

• Make sure the secondary terminals of the VT are always connected to the nominal sett<strong>ing</strong> or in open circuit.<br />

• Ground the support plates and a secondary coil terminal (ex. b).<br />

3. Maintenance:<br />

• Before carry<strong>ing</strong> out any operation, make sure that the VTs are not connected to the power grid or draw<strong>ing</strong> power<br />

in any way.<br />

• Verify the state of the connections.<br />

• Make sure there are no traces of carbonization on the insulat<strong>ing</strong> surfaces.<br />

• Verify the absence of halo effects near the primary connections.<br />

• It is advisable to remove dust and/or other deposits that may be present on the surfaces of the transformers,<br />

us<strong>ing</strong> a dry cloth and avoid<strong>ing</strong> the use of solvents.<br />

4. Disposal:<br />

• In case disposal of obsolete material at an authorized waste disposal site becomes necessary, use materials<br />

code C.E.R. 160214 directive or operate accord<strong>ing</strong> to exist<strong>ing</strong> provisions of local and national.<br />

For any matter not specified should follow the previous instructions of the operat<strong>ing</strong> manuals for download on www.<br />

ftmsrl.it site.<br />

Tabella 5 / Table 5<br />

Limiti dell’errore di tensione e dell’errore d’angolo per i trasformatori di tensione di misura<br />

Limits of voltage error and phase displacement for measur<strong>ing</strong> voltage transformers<br />

Classe<br />

Class<br />

0,1<br />

0,2<br />

0,5<br />

1,0<br />

3,0<br />

Errore di tensione<br />

(rapporto)<br />

Voltage (ratio) error<br />

ε u ±%<br />

0,1<br />

0,2<br />

0,5<br />

1,0<br />

3,0<br />

Minuti<br />

Minutes<br />

±<br />

5<br />

10<br />

20<br />

40<br />

Non specificato<br />

Not specified<br />

Errore d’angolo<br />

Phase displacement<br />

Δφ<br />

Centiradianti<br />

Centiradians<br />

±<br />

0,15<br />

0,3<br />

0,6<br />

1,2<br />

Non specificato<br />

Not specified<br />

pag. 17