TRASFORMATORE DI CORRENTE TIPO AD UN NUCLEO<br />

SINGLE CORE CURRENT TRANSFORMER<br />

17,5 kV<br />

Modello<br />

Type<br />

MTA 15K<br />

Caratteristiche CARATTERISTICHE standard STANDARD<br />

- Isolamento a secco in resina - Funzionamento all’interno<br />

- Installazione esposta<br />

- Installazione anche in clima tropicale<br />

- Uno o due rapporti primari, ottenuti con presa sul secondario<br />

- Tensione di riferimento per l’isolamento 17,5 kV<br />

- Tensione di prova a freq. industriale e ad impulso 38/95 kV<br />

- Frequenza 50 Hz oppure 60 Hz<br />

- Corrente nominale secondaria 5 A oppure 1 A<br />

- Corrente nominale termica di c.to c.to (Ith) 100 Ipn /1”- max 40 kA<br />

- Corrente nominale dinamica (Idyn) 2,5 Ith<br />

- Costruzione in accordo alle norme IEC 61869-1/2<br />

- Coprimorsetti sigillabile sul secondario<br />

ESECUZIONI Esecuzioni REALIZZABILI realizzabili a A richiesta RICHIESTA<br />

- Corrente nominale secondaria diversa da 1 A e 5 A<br />

- Costruzione in accordo alle norme VDE ,BS ,ANSI<br />

- Rapporti e prestazioni diversi da quelli indicati<br />

- Corrente nominale di c.to c.to superiori a 100 Ipn/1” max 40 kA<br />

- Presa capacitiva<br />

<br />

Peso kg 10 circa – Weight kg 10 abt.<br />

Dimensioni d’<strong>ing</strong>ombro ( mm ) - Outline dimensions ( mm )<br />

features FEATURES standard STANDARD<br />

- Dry insulation in resin – Indoor installation<br />

- Exposed installation<br />

- Indoor installation also in tropics<br />

- S<strong>ing</strong>le or double ratios by secondary reconnection<br />

- Highest system voltage up to 17,5 kV<br />

- Test voltage (1’/50Hz) and impulse voltage 38/95 kV<br />

- Frequency 50 Hz or 60 Hz<br />

- Normal secondary rated 5 A or 1 A<br />

- Rated short-time thermal current (Ith) 100 Ipn/1” max 40 kA<br />

- Rated dynamic current (Idyn) 2,5 Ith<br />

- Transformers accord<strong>ing</strong> to IEC 61869-1/2<br />

- Sealable protection on the secondary<br />

Special SPECIAL executions EXECUTIONS on ON request REQUEST<br />

- Rated secondary current different from 1 A and 5 A<br />

- Transformers accord<strong>ing</strong> to VDE ,BS ,ANSI<br />

- Different burdens from the ones indicated<br />

- Rated short-time thermal current different from 100 Ipn/1” max 40 kA<br />

- Capacitive voltage tap<br />

sez. A - - pag. 27 3