Pure Sine Wave Inverters<br />

2.4.1 Using power supplies instead of batteries<br />

It is not recommended to power the inverter directly from a DC power supply when full inverter<br />

performance is required. Most power supplies are not able to supply the huge surge currents<br />

required by the inverter, and are usually generating a too high ripple voltage causing the inverter‘s<br />

high ripple protection to trip.<br />

2.5 Connection to the battery<br />

This inverter is equipped with two 25 mm² wires with a length of 1.5 meters. Unless it is absolutely<br />

necessary, <strong>Alessi</strong> Center advises not to extend the battery wires. Extending the battery wires may<br />

increase system losses and can cause inverter malfunctioning like tripping the input ripple<br />

protection circuit. If it is unavoidable to extend these wires, use a wire gauge of at least 1.5 times<br />

larger than the ones supplied with the inverter. Maximum recommended battery wire length is<br />

approx. 3 meters. Make sure that an eventual joint between the original wires and the extension<br />

wires is made solid and with very low electrical resistance in mind.<br />

CAUTION<br />

TO AVOID FIRE HAZARDS CAUSED BY DAMAGED DC WIRES, ALWAYS<br />

PLACE A BATTERY SYSTEM FUSE AS CLOSE AS POSSIBLE TO YOUR<br />

BATTERY TERMINALS.<br />

Recommended battery fuse size is : 150A..200A for the 12V systems,<br />

125A..150A for the 24V systems and 60A..100A for the 48V systems.<br />

CAUTION<br />

THE RED WIRE MUST BE CONNECTED TO THE POSITIVE (+) TERMINAL<br />

AND THE BLACK WIRE TO THE NEGATIVE (-) TERMINAL OF THE<br />

BATTERY.<br />

Reverse polarity connection of the battery wires can damage the inverter!<br />

Damage caused by reversed polarity is not covered by the warranty. Make sure<br />

the powerswitch is in the OFF ‘0’ position before connecting the battery.<br />

WARNING<br />

IF THE INVERTER IS CONNECTED TO THE BATTERY WITH INCORRECT<br />

POLARITY, THE DC FUSE WILL BLOW.<br />

To replace the internal DC fuse, see chapter 5.2 for further information. If the<br />

fuse blows again, even with the correct polarity applied, the inverter is damaged<br />

and must be returned for service.<br />

2.5.1 General precautions about working with batteries<br />

1. Working in vicinity of a lead acid battery is dangerous. Batteries can generate explosive<br />

gases during operation. Never smoke or allow a spark or flame in vicinity of a battery.<br />

Provide sufficient ventilation aro<strong>und</strong> the battery.<br />

2. Wear eye and clothing protection. Avoid touching eyes while working near batteries.<br />

Wash your hands when done.<br />

3. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid<br />

enters eye, immediately flood eye with running cold water for at least 15 minutes and get<br />