SOLID WALL FIRE-RATING UPGRADE<br />

<strong>FIREX</strong><br />

Wall System<br />

Meets INSULATION AND INTEGRITY CRITERIA of BS 476: Part 22: 1987<br />

Side View<br />

bl<br />

8 1 2 6<br />

Side View<br />

bm<br />

Horizontal View<br />

9 1 2 3 7<br />

Horizontal View<br />

3<br />

4<br />

1<br />

5<br />

2<br />

9<br />

8<br />

4<br />

7<br />

4<br />

5<br />

1<br />

2<br />

6<br />

3<br />

bk<br />

9<br />

5<br />

8<br />

bl<br />

bk<br />

bm<br />

bl<br />

2<br />

Technical Data:<br />

Upgrade fire rating from 1 hour insulation and integrity to<br />

2 hours insulation and integrity in accordance with BS 476: Part<br />

22 with fire on either side.<br />

Nominal thickness of wall:<br />

Concrete wall (75 mm thick): 131 mm<br />

Brick wall (100 mm thick): 156 mm<br />

1) <strong>FIREX</strong> <strong>BOARD</strong> 1 x 6 mm thick<br />

2) Ceramic fiber raw density ≥ 128 kg/m 3 50 mm thick<br />

3) <strong>FIREX</strong> <strong>BOARD</strong> fillet 50 mm wide 6 mm thick<br />

Ceramic fiber seal<br />

4) Top and bottom steel U channels 50 x 32 x 0.6 mm<br />

5) Horizontal steel U channel (1220 mm c/c) 50 x 50 x 0.6 mm<br />

6) Vertical steel U channel (610 mm c/c) 50 x 50 x 0.6 mm<br />

7) Wall steel U channel 50 x 50 x 0.6 mm<br />

8) M4 self-tapping screws at approx. 200 mm centres.<br />

9) 6 mm dia. concrete nail at approx. 600 mm centres.<br />

10) 6 mm dia. concrete nail at approx. 500 mm centres.<br />

11) Brick or concrete wall.<br />

Technical Data:<br />

Upgrade fire rating from 2 hours insulation and integrity to<br />

4 hours insulation and integrity in accordance with BS 476: Part<br />

22 with fire on either side.<br />

Nominal thickness of wall:<br />

Concrete wall (100 mm thick): 168 mm<br />

Brick wall (100 mm thick + 13 mm gypsum<br />

plaster on each side): 194 mm<br />

Brick wall (225 mm thick): 293 mm<br />

1) <strong>FIREX</strong> <strong>BOARD</strong> 1 x 6 mm thick<br />

2) <strong>FIREX</strong> <strong>BOARD</strong> fillet 75 mm wide 6 mm thick<br />

3) Ceramic fiber raw density ≥ 128 kg/m 3 63 mm thick<br />

4) <strong>FIREX</strong> <strong>BOARD</strong> fillet 50 mm wide 6 mm thick<br />

Ceramic fiber seal<br />

5) Top and bottom steel U channels 50 x 32 x 0.6 mm<br />

6) Horizontal steel U channel (1220 mm c/c) 50 x 50 x 0.6 mm<br />

7) Vertical steel U channel (610 mm c/c) 50 x 50 x 0.6 mm<br />

8) Wall steel U channel 50 x 50 x 0.6 mm<br />

9) M4 self-tapping screws at approx. 200 mm centres.<br />

10) 6 mm dia. concrete nail at approx. 600 mm centres.<br />

11) 6 mm dia. concrete nail at approx. 500 mm centres.<br />

12) Brick or concrete wall.