<strong>FPD</strong>-<strong>7024</strong> | Operation and Installation Guide | 5.0 Control Panel Programming<br />
• Temporal: Output turns on and off to implement the ANSI standard evacuation pattern<br />
(Temporal code 3).<br />
• Wheelock: Output is configured to support Wheelock devices with synchronization capability, including<br />
the ability to silence the horn of a combination horn strobe. The Wheelock configuration is not supported<br />
by remote NACs implemented using a Remote NAC power supply.<br />
• Gentex: Output is configured to support Gentex devices with synchronization capability, including the<br />
ability to silence the horn of a horn strobe combination.<br />
54<br />
The Gentex option does not synchronize to the UL864 9 th Edition standard.<br />
• System Sensor: Output is configured to support System Sensor devices with synchronization capability,<br />
including the ability to silence the horn of a horn strobe combination.<br />
After you program the desired pattern configuration, the previous window appears.<br />
If you select 3 from the PROG NACs menu, you are asked to enter four zones to activate this output.<br />
OUTPUT ZONE A (XX)<br />
(00-63):<br />
XX” indicates the existing setting for each of the four output zone settings.<br />
Enter the desired zone to activate this output and press [#/Enter]. You are asked to enter up to four zones (A,<br />
B, C, D). Enter 00 (or leave it set at “00”) for any unused zones to prevent unintentional output activation.<br />
After all four zones are programmed, the previous window appears.<br />
Table 19: Pre-Assigned Zone Quick Reference<br />
Zone Pre-Assigned Condition<br />
52 General <strong>Fire</strong> <strong>Alarm</strong> (non-silencing)<br />
53 General <strong>Fire</strong> <strong>Alarm</strong>, (silencing)<br />
54 Ground Start<br />
55 General Supervisory, (silencing)<br />
56 General Waterflow, (silencing)<br />
57 Communication Trouble<br />
58 General Supervisory <strong>Alarm</strong> (non-silencing)<br />
59 <strong>Alarm</strong> Verification<br />
60 AC Failed<br />
61 General Waterflow <strong>Alarm</strong> (non-silencing)<br />
62 General Trouble<br />
63 General <strong>Alarm</strong>, Waterflow Supervisory (non-silencing)<br />
Bosch <strong>Security</strong> <strong>Systems</strong>, Inc. | 1/10 | F01U008458-03