<strong>FPD</strong>-<strong>7024</strong> | Operation and Installation Guide | 1.0 Overview<br />
8<br />
1.2 Components<br />
1.2.1 On-board Conventional Points<br />
All on-board points and points implemented with<br />
the FPC-7034 work with two- or four-wire<br />
detectors. The system has an optional alarm<br />
verification feature.<br />
Table 1: Two-Wire Circuits<br />
Number of two-wire circuits Four circuits, expandable<br />
to eight using an FPC-7034<br />
Expander<br />
Type of Circuit Class B, Style B and Class<br />
A, Style D as needed)<br />
EOL Resistor 2.21 kΩ (P/N: 25899 or<br />
F01U034504),<br />
UL listed<br />
Supervisory Existing 8 to 20 mA<br />
Required Existing for <strong>Alarm</strong> 25 mA<br />
Maximum Short Circuit 45 mA<br />
Existing<br />
Maximum Line Resistance 150Ω<br />
Circuit Voltage Range 20.4 to 28.2 VDC<br />
Maximum Detectors per 20 detectors (two-wire)<br />
Point<br />
Total Detector Standby 3 mA maximum<br />
Existing<br />
Response Time* Either fast (500 ms) or<br />
programmable (from 1 to<br />
89 seconds)<br />
Dirty Detector Monitoring Implements Bosch <strong>Security</strong><br />
<strong>Systems</strong>, Inc. Chamber<br />
Check ® and GE Interlogix,<br />
Inc. CleanMe protocol to<br />
monitor conventional loops<br />
for dirty detectors.<br />
* Refer to Section 6.4 on page 81.<br />
All on-board points, and points activated with the<br />
FPC-7034 Four Point Expander, are continuously<br />
monitored for detectors signaling a dirty condition<br />
using the Bosch <strong>Security</strong> <strong>Systems</strong>, Inc. Chamber<br />
Check and GE Interlogix, Inc. CleanMe protocols.<br />
To prevent nuisance reports, a two-minute delay<br />
occurs before a dirty detector is annunciated. A sixminute<br />
delay occurs after the detector restores<br />
from the dirty condition before the control panel<br />
restores the condition.<br />
1.2.2 Off-board Addressable Points (with<br />
D7039 Multiplex Expansion Module)<br />
The D7039 Multiplex Expansion Module adds:<br />
• Two Class B, Style 4 or one Class A, Style 6<br />
Signaling Line Circuits (SLCs)<br />
• Each point is individually supervised for proper<br />
connection to the common bus (when over ten<br />
points are troubled, up to ten troubles are<br />
shown per bus and the balance of the troubles<br />
is indicated by a common bus failure<br />
message).<br />
• Response time can be set to fast, or<br />
programmed from 1 to 89 seconds.<br />
• Input points on the SLCs are implemented with<br />
a D7042 Eight Input Remote Module.<br />
1.2.3 Enclosure Housing<br />
The standard enclosure is 18 ga., cold-rolled steel,<br />
and measures 20.75 in. x 15 in. x 4.25 in. (52.7 cm<br />
x 38.1 cm x 10.8 cm). A keyed lock is included, and<br />
the LEDs and LCD display are visible through the<br />
door.<br />
1.2.4 Remote LCD Keypads<br />
Maximum number of keypads: Four FMR-7033<br />
LCD <strong>Fire</strong> Keypads.<br />
Wiring Requirements: Refer to Section 2.2 Option<br />
Bus Wiring Requirements on page 19.<br />
1.2.5 Remote LED Annunciators<br />
Maximum number of annunciators: Eight D7030<br />
eight-zone LED Annunciators.<br />
Wiring Requirements: Refer to Section 2.2 Option<br />
Bus Wiring Requirements on page 19.<br />
1.2.6 D7032 with the D7030X Use<br />
When a D7032 Eight-Zone LED Annunciator<br />
Expander is connected to the D7030X, eight<br />
additional LED zones appear. This allows the<br />
D7030X/D7032 combination to show 16 LED<br />
zones. Up to eight D7030X/D7032 combinations<br />
can be connected to the <strong>FPD</strong>-<strong>7024</strong> <strong>Fire</strong> <strong>Alarm</strong><br />
Control Panel. Refer to Table 2 on page 9 for<br />
zones shown by each D7030X/D7032 combination.<br />
Each D7030X processes 16 zones of<br />
information. If no D7032 is attached, only<br />
the lower eight zones are shown.<br />
The column labeled Shown on D7030X”<br />
In Table 2 on page 9 applies regardless if<br />
an attachment of a D7032 to any D7030X<br />
is made.<br />
Bosch <strong>Security</strong> <strong>Systems</strong>, Inc. | 1/10 | F01U008458-03