<strong>FPD</strong>-<strong>7024</strong> | Operation and Installation Guide | 1.0 Overview<br />

8<br />

1.2 Components<br />

1.2.1 On-board Conventional Points<br />

All on-board points and points implemented with<br />

the FPC-7034 work with two- or four-wire<br />

detectors. The system has an optional alarm<br />

verification feature.<br />

Table 1: Two-Wire Circuits<br />

Number of two-wire circuits Four circuits, expandable<br />

to eight using an FPC-7034<br />

Expander<br />

Type of Circuit Class B, Style B and Class<br />

A, Style D as needed)<br />

EOL Resistor 2.21 kΩ (P/N: 25899 or<br />

F01U034504),<br />

UL listed<br />

Supervisory Existing 8 to 20 mA<br />

Required Existing for <strong>Alarm</strong> 25 mA<br />

Maximum Short Circuit 45 mA<br />

Existing<br />

Maximum Line Resistance 150Ω<br />

Circuit Voltage Range 20.4 to 28.2 VDC<br />

Maximum Detectors per 20 detectors (two-wire)<br />

Point<br />

Total Detector Standby 3 mA maximum<br />

Existing<br />

Response Time* Either fast (500 ms) or<br />

programmable (from 1 to<br />

89 seconds)<br />

Dirty Detector Monitoring Implements Bosch <strong>Security</strong><br />

<strong>Systems</strong>, Inc. Chamber<br />

Check ® and GE Interlogix,<br />

Inc. CleanMe protocol to<br />

monitor conventional loops<br />

for dirty detectors.<br />

* Refer to Section 6.4 on page 81.<br />

All on-board points, and points activated with the<br />

FPC-7034 Four Point Expander, are continuously<br />

monitored for detectors signaling a dirty condition<br />

using the Bosch <strong>Security</strong> <strong>Systems</strong>, Inc. Chamber<br />

Check and GE Interlogix, Inc. CleanMe protocols.<br />

To prevent nuisance reports, a two-minute delay<br />

occurs before a dirty detector is annunciated. A sixminute<br />

delay occurs after the detector restores<br />

from the dirty condition before the control panel<br />

restores the condition.<br />

1.2.2 Off-board Addressable Points (with<br />

D7039 Multiplex Expansion Module)<br />

The D7039 Multiplex Expansion Module adds:<br />

• Two Class B, Style 4 or one Class A, Style 6<br />

Signaling Line Circuits (SLCs)<br />

• Each point is individually supervised for proper<br />

connection to the common bus (when over ten<br />

points are troubled, up to ten troubles are<br />

shown per bus and the balance of the troubles<br />

is indicated by a common bus failure<br />

message).<br />

• Response time can be set to fast, or<br />

programmed from 1 to 89 seconds.<br />

• Input points on the SLCs are implemented with<br />

a D7042 Eight Input Remote Module.<br />

1.2.3 Enclosure Housing<br />

The standard enclosure is 18 ga., cold-rolled steel,<br />

and measures 20.75 in. x 15 in. x 4.25 in. (52.7 cm<br />

x 38.1 cm x 10.8 cm). A keyed lock is included, and<br />

the LEDs and LCD display are visible through the<br />

door.<br />

1.2.4 Remote LCD Keypads<br />

Maximum number of keypads: Four FMR-7033<br />

LCD <strong>Fire</strong> Keypads.<br />

Wiring Requirements: Refer to Section 2.2 Option<br />

Bus Wiring Requirements on page 19.<br />

1.2.5 Remote LED Annunciators<br />

Maximum number of annunciators: Eight D7030<br />

eight-zone LED Annunciators.<br />

Wiring Requirements: Refer to Section 2.2 Option<br />

Bus Wiring Requirements on page 19.<br />

1.2.6 D7032 with the D7030X Use<br />

When a D7032 Eight-Zone LED Annunciator<br />

Expander is connected to the D7030X, eight<br />

additional LED zones appear. This allows the<br />

D7030X/D7032 combination to show 16 LED<br />

zones. Up to eight D7030X/D7032 combinations<br />

can be connected to the <strong>FPD</strong>-<strong>7024</strong> <strong>Fire</strong> <strong>Alarm</strong><br />

Control Panel. Refer to Table 2 on page 9 for<br />

zones shown by each D7030X/D7032 combination.<br />

Each D7030X processes 16 zones of<br />

information. If no D7032 is attached, only<br />

the lower eight zones are shown.<br />

The column labeled Shown on D7030X”<br />

In Table 2 on page 9 applies regardless if<br />

an attachment of a D7032 to any D7030X<br />

is made.<br />

Bosch <strong>Security</strong> <strong>Systems</strong>, Inc. | 1/10 | F01U008458-03