23.02.2013 Views

Mini-X-Purge Size 1 Manual ML 442 - Expo Technologies

Mini-X-Purge Size 1 Manual ML 442 - Expo Technologies

Mini-X-Purge Size 1 Manual ML 442 - Expo Technologies

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Mini</strong>-X-<strong>Purge</strong> � <strong>Size</strong> 1 <strong>Manual</strong><br />

<strong>ML</strong> <strong>442</strong><br />

Contents<br />

1. Specification Sheet – <strong>Mini</strong>-X-<strong>Purge</strong> � Systems<br />

2. Application Suitability<br />

3. Description and Principle of Operation<br />

4. Installation of the System<br />

5. Commissioning<br />

6. Maintenance of the System<br />

7. Fault Finding<br />

8. Approval Documents<br />

9. Glossary<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 1 of 22


1. Specification Sheet – <strong>Mini</strong>-X-<strong>Purge</strong> � Systems<br />

Model No. (Example): 07 1 XLC / ss / PO / WM (Note: Not all codes are applicable)<br />

<strong>Purge</strong> System Type<br />

07 = <strong>Mini</strong><strong>Purge</strong><br />

<strong>Size</strong><br />

1 = Sub <strong>Mini</strong><strong>Purge</strong><br />

<strong>Purge</strong> flow rate 225 Nl /min, 8 scfm<br />

Approval / Certification<br />

X =<br />

Europe<br />

EN60079-0, EN60079-2, EN 61241-0, EN61241-4<br />

Sira 01ATEX1295X<br />

0518 II 2 (2) G D<br />

Ex [px] IIC T6 Gb<br />

Ex [p] IIIC T85ºC Db<br />

Tamb -20ºC +55ºC<br />

IEC<br />

IEC60079-0, IEC60079-2, IEC61241-0, IEC61241-4<br />

IECEx SIR 07.0027X<br />

Ex [px] IIC T6 Gb<br />

Ex [p] IIIC T85ºC Db<br />

Tamb -20ºC +55ºC<br />

USA / Canada NFPA 496<br />

FM 1X8A4AE<br />

Class I Div 1 Groups A, B, C & D<br />

UL E190061<br />

Class I Div 1 Groups A, B, C & D<br />

BRAZIL INMETRO/TUV TÜV 12.1462X<br />

Ex [px] IIC T6 Gb<br />

Ex [p] IIIC T85ºC Db<br />

-20ºC ≤ Ta ≤ +55ºC<br />

For limitations and conditions of use refer to the<br />

applicable certificate at the back of this manual.<br />

Options as Required<br />

AO = Alarm Only<br />

MO = <strong>Manual</strong> Override<br />

MK = MIU Mounting Kit (PO systems only)<br />

WM = Wall Mounting Bars<br />

Power & Alarm (Signals)<br />

PO = Pneumatic Output<br />

“Power” : On <strong>Purge</strong> Complete = 30 psi / 0.2 MPa / 2 bar Signal<br />

“Alarm” : Loss of Pressure = No signal<br />

”Pressurized” = 30 psi / 0.2 MPa / 2 bar Signal<br />

PA = Power and Alarm Terminal Box Ex e IIC T6<br />

“Power” ; 250 Vac 4 Amp AC15 2PNO – Ex d IIC T6<br />

“Alarm” : 250 Vac 4 Amp AC15 SPCO – Ex d IIC T6<br />

(European and IEC Systems Only)<br />

IS = Intrinsically Safe, Ex i & Ex i circuit<br />

“Power” : used with others’ Ex i equipment<br />

“Alarm” : Relay / Barrier<br />

<strong>Mini</strong><strong>Purge</strong> � Housing<br />

ss = 316L Stainless Steel<br />

Neoprene “Top” Mount Gasket<br />

pm = Panel Mount (Side/Front Mount) 316L<br />

Stainless Steel<br />

Presurization Method<br />

CF = Continuous Flow<br />

LC = Leakage Compensation<br />

Supply Pressure: Must be regulated at inlet<br />

<strong>Mini</strong>mum 60 psi / 0.4 MPa / 4 bar<br />

Maximum 115 psi / 0.8 MPa / 8 bar<br />

Air Quality: Compressed air / Nitrogen to instrument quality<br />

Ambient Temperature: -20ºC to + 55ºC<br />

Leakage Compensation: Variable up to 2 scfm / 60 Nl/min to compensate for leakage of enclosure<br />

<strong>Purge</strong> Timer: Stepped adjustable between 1 minute and 30 minutes<br />

Flow & Pressure Sensors: CF: One sensor for both<br />

“Low Pressure and Flow”: 1” WC / 250 Pa (2.5 mbar)<br />

LC: “Low Pressure Sensor” 0.2” WC / 50 Pa (0.5 mbar)<br />

“Flow Sensor” 1.13” WC/ 280 Pa / (2.8 mbar)<br />

Relief Valve: System: CF LC<br />

Model No: RLV25/ss RLV25/FS/ss<br />

Opening Pressure: 4” WC / 1 kPa (10 mbar) 4” WC / 1 kPa (10 mbar)<br />

<strong>Purge</strong> Flow Rate: N/A (see Spark Arrestor) 8 scfm / 225 Nl/min<br />

Material: 316L Stainless Steel, Spark Arrestor: Stainless Steel mesh, Gasket: Neoprene<br />

Spark Arrestor Unit Model No: SAU25<br />

(CF systems only) <strong>Purge</strong> / Dilution Flow Rate: Between 0.4 & 8 scfm / 10 & 225 Nl/min<br />

7 user selectable orifice plates<br />

Material: Stainless Steal<br />

Bulkhead Pipe Fittings: Air Supply: 1/2” NPT<br />

Output: 1/2” NPT<br />

Signal: 1/8” NPT<br />

Visual Indicators: CF: Alarm / Pressurized (Red / Green)<br />

<strong>Purge</strong> Complete (Red / Green)<br />

LC: Alarm / Pressurized (Red / Green)<br />

<strong>Purge</strong> Complete (Black / Amber)<br />

Action on “Loss of Pressure”:<br />

CF: Action on “Loss of Pressure” = “Alarm & Trip”. Option /AO specifies an “Alarm Only” kit.<br />

LC: Action on “Loss of Pressure” = “Alarm & Trip” or “Alarm Only”. LC Model is user selectable.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 2 of 22


2. Application Suitability<br />

<strong>Mini</strong><strong>Purge</strong> � Systems are certified for use in Hazardous Areas, where the Hazardous Area is<br />

non-mining (i.e. above ground) and the hazard is caused by flammable gasses, vapours or dust.<br />

Depending on the model, the systems may be used in IECEx, ATEX Zone 1(21) - Category 2<br />

and NEC 500 Class I, Div 1.<br />

<strong>Mini</strong><strong>Purge</strong> � systems may be used for hazards of any gas group. However, apparatus<br />

associated with the <strong>Mini</strong><strong>Purge</strong> � system, such as Intrinsically Safe signalling circuits and<br />

flameproof enclosures containing switching devices may be limited in their gas group. The<br />

certification documentation supplied with any such devices must be checked to ensure their<br />

suitability.<br />

This system is designed for use primarily with compressed air. Where other inert compressed<br />

gasses are used (Nitrogen, for example) the user must take suitable precautions so that the<br />

build up of the inert gas does not present a hazard to health. Consult the Control of Substances<br />

Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation<br />

exists, a warning label must be fitted to the Pressurized Enclosure.<br />

The following materials are used in the construction of <strong>Mini</strong><strong>Purge</strong> � systems. If substances that<br />

will adversely affect any of these materials are present in the surrounding environment, please<br />

consult <strong>Expo</strong> for further guidance.<br />

Materials of construction:<br />

� Stainless Steel � Aluminium � Acrylic<br />

� Mild (carbon) Steel � Nylon � Silicone Rubber<br />

� Brass � Polyurethane � Neoprene<br />

3. Description and Principle of Operation<br />

All <strong>Expo</strong> <strong>Technologies</strong> <strong>Mini</strong><strong>Purge</strong> � pressurization systems provide:<br />

a) a method of pressurizing a Pressurized Enclosure (PE) while at the same time compensating<br />

for any leakage, together with<br />

b) a method of purging the enclosure, before power is applied, to remove any flammable gas<br />

that may have entered the enclosure while it was not pressurized,<br />

c) visual indication of the <strong>Mini</strong><strong>Purge</strong> � system status, and<br />

d) an output to provide remote indication or control.<br />

The <strong>Mini</strong><strong>Purge</strong> � system comprises a number of component units. The units required depend on<br />

the type of system selected. These are summarised in Table 1. The general description and<br />

function of each is as follows:<br />

3.1 Control Unit (CU)<br />

The Control Unit (CU) is the heart of the system. It contains a pneumatic logic circuit specially<br />

designed and built to control the functions required for purge and pressurization. For all<br />

systems this includes air filtration, pressure and purge flow measurement, purge timing, and<br />

local visual indication of Pressurized/Alarm and flow sensed. It also provides the outputs for<br />

power and remote alarm control corresponding to the output type selected.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 3 of 22


3.2 Relief Valve (RLV)<br />

The Relief Valve unit is fitted to the PE to provide a means of limiting the<br />

maximum pressure experienced by the PE during operation. The RLV<br />

model number has a suffix giving the diameter of the valve aperture in<br />

millimetres e.g. RLV25 (= 25mm bore). The RLV also incorporates a<br />

Spark Arrestor to prevent sparks being ejected from the PE into the<br />

classified area.<br />

In Leakage Compensation systems, the RLV is combined with the flow<br />

measurement mechanism.<br />

Figure 1. LC Relief Valve<br />

3.3 Calibrated Outlet Orifice/Spark Arrestor (SAU)<br />

Continuous Flow systems incorporate the SAU25. This unit has<br />

a range of interchangeable calibrated orifice plates, which are<br />

used to measure the flow through the PE.<br />

3.4 The Methods of Pressurizing<br />

Figure 2 Spark Arrestor Type SAU25<br />

a) CF - Continuous Flow<br />

A Continuous Flow (CF) of protective gas is passed through the PE. Initially this flow is verified<br />

and performs the purging phase of the operation. When the purging phase is completed – i.e.<br />

the purge time has elapsed- the same flow of protective gas maintains the pressurization of the<br />

enclosure. This flow may be required to dilute an internal source of hazardous gas release.<br />

Figure 3 Continuous Flow Circuit Diagram<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 4 of 22


) LC - Leakage Compensation<br />

Initially a high flow of protective gas is passed through the enclosure. This flow is verified and<br />

performs the purging phase of the operation. When the purging phase is completed – i.e. the<br />

purge time has elapsed - the flow of protective gas is provided via an adjustable valve so that it<br />

just compensates for any leakage from the PE in addition to maintaining its pressurization.<br />

If leakage is less than 5 l/min then the LCV will be awkward to set. You will find that the RLV<br />

spring will cycle open and closed. If this happens contact our service department for advice.<br />

Figure 4 Leakage Compensation Circuit Diagram<br />

3.5 Type of Output<br />

The functions of the outputs are power control and alarm/pressurized indication. Power control<br />

provides a signal to switch the power to the PE. Alarm output provides a passive signal to<br />

indicate remotely when the enclosure is not pressurized and an active signal when pressurized.<br />

a) PO- Pneumatic Output<br />

The power control and pressurized outputs are pneumatic signals, which may be used to<br />

operate other devices to provide power switching or alarm indication. The lack of any output<br />

signal indicates incomplete purge and alarm. In many instances these outputs may be<br />

connected to the <strong>Expo</strong> range of <strong>Mini</strong><strong>Purge</strong> � Interface Unit s (MIU).<br />

Figure 6 Pneumatic Output Option<br />

Figure 5 Typical <strong>Mini</strong><strong>Purge</strong> Interface Unit<br />

type (MIU/dA)<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 5 of 22


) IS - Intrinsically Safe Output<br />

The power control and alarm outputs are volt free contacts which form part of an Intrinsically<br />

Safe (IS) circuit which then provides power control or alarm outputs in a safe (unclassified)<br />

area. These contacts must only be connected to IS circuits as the switch contacts are in the<br />

hazardous area. In many instances these outputs may be connected to the <strong>Expo</strong> range of<br />

<strong>Mini</strong><strong>Purge</strong> � Interface Units (MIU).<br />

Figure 7. Intrinsically Safe (IS) Option<br />

c) PA - Power and Alarm<br />

By integral Ex d flameproof switches, terminated in Ex e junction box in accordance with<br />

European standards.<br />

Figure 8. Ex de Power and Alarm (PA) Option<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 6 of 22


4. Installation of the System<br />

This <strong>Mini</strong><strong>Purge</strong> � is designed for use under normal industrial conditions of ambient temperature,<br />

humidity and vibration. Please consult <strong>Expo</strong> before installing this equipment in conditions that<br />

may cause stresses beyond normal industrial conditions.<br />

The <strong>Mini</strong><strong>Purge</strong> � system shall be installed in accordance with relevant standards, such as IEC /<br />

EN 60079-14, NEC 500, NFPA 496 and any local codes of practice that are in force.<br />

There are up to three components for the <strong>Mini</strong><strong>Purge</strong> � system, dependant upon the system type:<br />

System type Control Unit (CU)<br />

Relief Valve<br />

(RLV)<br />

Spark Arrestor<br />

Unit<br />

Leakage Compensation YES YES Integral to RLV<br />

Continuous Flow YES YES YES (SAU25)<br />

Table 1 System Components<br />

4.1 Control Unit (CU)<br />

The <strong>Mini</strong><strong>Purge</strong> � system should be installed either directly on or close to the PE. See mounting<br />

details. Generally the most convenient arrangement is to install the CU on the top of the PE.<br />

Must be mounted vertically as shown in <strong>Mini</strong><strong>Purge</strong> � Configuration XBR-7TD0-003. The CU can<br />

be mounted on the side of the PE using the rear mounting fixings. The piped connections to the<br />

PE should be made using metallic tube through suitable bulkhead connections. The CU can be<br />

remote mounted using the wall mounting bars (/WM option), and should be installed as close as<br />

possible to the PE. It should be installed so that the system indicators and certification labels<br />

may be readily observed.<br />

4.2 Relief Valve (RLV) and Spark Arrestor Unit (SAU)<br />

To achieve efficient purging the points where air enters and exits the PE should normally be at<br />

opposite ends of the PE. These items must be mounted vertically. The RLV or SAU are<br />

recommended to be situated at the bottom, or on the side of the enclosure at the bottom, when<br />

the CU is top mounted on the enclosure, thus achieving top to bottom purging. The purge air<br />

may be piped within the PE to ensure purging of potential dead air spots.<br />

It is important that the interior and exterior of the Spark Arrestor is kept clean and debris is not<br />

allowed to accumulate which might affect the calibration of the device. In particular the exterior<br />

of the Spark Arrestor should not be painted or blocked off in any way.<br />

4.3 Connections to Protective Gas Supply<br />

The <strong>Mini</strong><strong>Purge</strong>� system should be connected to a protective gas supply, which is suitable for<br />

purging and pressurization. The air supply to the filtration system must be clean, nonflammable,<br />

from a non-hazardous area and free from water and oil to BS ISO 8573-1: 2001<br />

Class 2.2.1 or relevant local standards. This is typically referred to as “Instrument Air Quality”.<br />

Solid Particles: 0.5µm < particle size � 1µm, maximum 1000 particles/m3<br />

Humidity: -40ºC* pressure dewpoint<br />

Oil content: �0.01mg/m3 concentration total oil<br />

* For applications where Tamb � 0ºC, the air supply should be Class 2.1.1, with Humidity: -70ºC<br />

pressure dewpoint.<br />

Although equipment will operate with lower air quality, the operational life of the system will be<br />

adversely affected. The equipment that is being protected may also suffer from poor air quality.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 7 of 22


The minimum air supply pressure should be 4 bar/ 60 psig / 4MPa. It is important that the<br />

compressed air / inert gas supply is capable of delivering the quantity required for purging at<br />

normal purge flow rate, maintaining the minimum pressure. This means ensuring adequate size<br />

of pipe and airline accessories. Over 80% of commissioning problems reported to <strong>Expo</strong> are due<br />

to inadequate sized piping or air supply. Although the <strong>Mini</strong><strong>Purge</strong> � unit includes a filter, the<br />

compressed air / inert gas supply should have a dedicated local air pressure regulator.<br />

4.4 <strong>Purge</strong> Air from CU to PE<br />

When the CU is directly top mounted onto the PE, no connection will normally be necessary, as<br />

the purge air will discharge into the PE directly. When the CU is not top mounted, or where<br />

internal air distribution is necessary a connection should be made from the purge air outlet on<br />

the CU (normally ½” NPT Female), via pipe pressure rated at least to the supply pressure, to<br />

the PE. This should be kept as short as possible and should be adequately sized to ensure that<br />

the full purge flow can be delivered.<br />

4.5 CU to Enclosure Pressure Monitor<br />

When the CU is directly top mounted onto the PE, no connection will normally be necessary, as<br />

the enclosure pressure monitor point will sense directly inside the PE. Only if the CU is not<br />

directly mounted or if there are fans, which may create localised low-pressure areas within the<br />

PE, it is necessary to pipe this connection. The connection is made to the enclosure pressure<br />

sensor fitting (normally 1/8” NPT Female) on the CU. There is virtually no flow in this circuit, so<br />

small bore tube may be used. <strong>Expo</strong> recommends 4mm O/D nylon tube. Make sure that all<br />

connections are free of leaks.<br />

4.6 CU to Flow Sensor<br />

In Continuous Flow (CF) systems, a Differential Pressure Sensor is combined with the <strong>Mini</strong>mum<br />

Pressure Sensor and measures the "DP HI (High) / Enclosure Pressure" within the PE and the<br />

pressure in the monitoring device at the back of the SAU "DP LO (Low) SAU Connection". This<br />

connection requires a pipe connection between the CU and the SAU25.<br />

In Leakage Compensation (LC) systems a dedicated <strong>Purge</strong> Flow Sensor measures the<br />

differential pressure between the "DP HI (High) / Enclosure Pressure" and the pressure in the<br />

monitoring device at the back of the RLV "DP LO (Low) RLV Connection". This connection<br />

requires a pipe to connect the CU to the RLV25.<br />

4.7 Power Supplies and their Isolation<br />

All power entering the PE shall be provided with a means of isolation. This requirement also<br />

applies to any external power sources, which are connected to equipment such as "volt-free" or<br />

"dry" contacts within the PE. Printer signal, network cards, etc need isolation.<br />

Exception: Power to other apparatus that is already suitable for the hazardous area need not to<br />

be isolated by the <strong>Mini</strong><strong>Purge</strong>� system.<br />

In all cases the application and the isolation of the power must be controlled by the <strong>Mini</strong><strong>Purge</strong> �<br />

system. Refer to Specification Sheet for output options available.<br />

4.8 Adjustments and Settings<br />

<strong>Purge</strong> Time<br />

If no specific purge test has been performed on the PE, the volume of the PE must be<br />

determined by the manufacturer or user and the necessary purging time calculated based on<br />

the purge flow rate specified by the “standard” being used. It is the user's responsibility to verify<br />

or enter this data on the PE and/or <strong>Mini</strong><strong>Purge</strong> � system nameplate. Ask <strong>Expo</strong> if in doubt. The<br />

IEC / EN 60079-2 permits 5 free volume changes and an example of the calculations is as<br />

follows:<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 8 of 22


If the PE external dimensions indicate an internal free volume of 500 Litres then,<br />

500 litres enclosure volume x 5 volume changes = 12 minutes purge time<br />

225 litres/minute purge flow rate<br />

If the PE is a motor, experience of purge testing shows that it is prudent to multiply the<br />

motor internal "free” volume by ten to get the purging volume.<br />

500 litres enclosure volume x 10 volume changes = 23 minutes purge time<br />

225 litres/minute purge flow rate<br />

The following applies for NFPA 496 standards where 4 complete volume changes are permitted<br />

for enclosures except when the PE contains a motor when 10 volume changes are required.<br />

If the PE external dimensions indicate a total volume of 8 cubic foot, then,<br />

8 cubic foot enclosure volume x 4 volume changes = 4 minutes purge time<br />

8 cubic foot/minute purge flow rate, (see above)<br />

If the same PE contains a motor, then,<br />

8 cubic foot enclosure volume x 10 volume changes = 10 minutes purge time<br />

8 cubic foot/minute purge flow rate, (see above)<br />

Figure 9 <strong>Mini</strong><strong>Purge</strong> � timer block<br />

The standard <strong>Mini</strong><strong>Purge</strong> � units have the patented digital<br />

pneumatic timer system as shown in Figure 9<br />

<strong>Mini</strong><strong>Purge</strong>� timer block. The purge time is set by<br />

opening / closing the pinch valve so that the sum of the<br />

open valve times equals or exceeds the required purge<br />

time. At least one valve must always be open, and<br />

the screws must be at the appropriate limit of travel.<br />

Do not over tighten.<br />

<strong>Purge</strong> Flow Rate (Orifice <strong>Size</strong> Selection) – Only for CF Systems<br />

The purge flow rate is selected by placing the appropriate orifice plate in the SAU. The purge<br />

flow rates given in Table 2 are based on standard setting of the flow sensor of 2.5mbar, 1” WC,<br />

250Pa. For LC systems the purge flow rate is set by the selection of the RLV and is not user<br />

adjustable.<br />

Continuous Flow Rate with<br />

2.5 mbarg, 1” WC, 250 Pa<br />

flow sensor set point<br />

N litre/minute SCFM<br />

A 10 0.4<br />

B 25 0.9<br />

C 40 1.4<br />

D 65 2.3<br />

E 90 3.2<br />

F 135 4.8<br />

G 180 6.4<br />

Orifice Plate<br />

Number<br />

NO ORIFICE 225 8.0<br />

Table 2 <strong>Purge</strong> Flow Rates<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 9 of 22


Action on Loss of Pressurization<br />

The action on loss of pressurization is the responsibility of the user.<br />

The action on loss of pressurization can be set to ALARMS ONLY (AO), or ALARM AND<br />

AUTOMATIC DISCONNECT OF POWER (A&T).<br />

a) Leakage Compensation<br />

The action on loss of pressurization is set by moving the<br />

jumper tube (see Figure 10 Action on Loss of<br />

Pressurization Jumper Tube). The standard setting is<br />

Alarm and Trip where the link is from C to A&T, with a<br />

plug in AO. Changing to Alarm Only (AO) is user<br />

adjustable by moving the link from C to AO, and plugging<br />

A&T.<br />

Figure 10 Action on loss of pressurization jumper tube<br />

b) Continuous Flow<br />

The standard CF system is built set to Alarm and Trip. Alarm Only can be installed when order<br />

specified or supplied as a retrofit kit later. See options.<br />

The selection for action on loss of pressurization depends on the area of operation and the<br />

following guidelines should be followed.<br />

The user must make use of this alarm facility in accordance with the local code of practice for<br />

"action on pressure or flow failure". Most codes include the following recommendations:<br />

Zone 1 Installations:<br />

Alarm and automatic disconnect of power.<br />

Exception: If the equipment inside the PE is suitable for use in Zone 2, the power trip may be<br />

performed manually, (no automatic power trip), if the pressure or flow failure persists for an<br />

unacceptable time.<br />

Zone 2 Installations:<br />

Alarm Only on pressure or flow failure with power being removed manually by turning off the air<br />

supply to the <strong>Mini</strong><strong>Purge</strong> � system if the failure persists for an unacceptable time.<br />

Class I Division 1 Installations:<br />

Alarm and Automatic Trip of Power. Note: NFPA 496 states power to the circuits shall be<br />

permitted to be continued for a short period if immediate loss of power would result in a more<br />

hazardous condition and if both audible and visual alarms are provided at a constantly attended<br />

location.<br />

Class I Division 2 Installations:<br />

Where automatic timing is preferred, Alarm Only on pressure or flow failure with power being<br />

removed manually by turning off the air supply to the <strong>Mini</strong><strong>Purge</strong> � system if the failure persists<br />

for an unacceptable time.<br />

4.9 Internal Gas Release<br />

If the PE contains an internal source of release of flammable gas or vapour, the procedures for<br />

assessment of the release as given in NFPA 496 or IEC / EN 60079-2 should be used. <strong>Expo</strong> is<br />

pleased to provide assistance or consultancy and advice on such matters.<br />

The user must verify that the specifications of the <strong>Expo</strong> system e.g. pressure, continuous flow<br />

(dilution) rate and type of protective gas are correct for the specific application.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 10 of 22


4.10 Multiple Enclosures<br />

More than one PE can be protected by a single system. Where PEs are connected and purged<br />

in "series" e.g. "Daisy Chained", the RLV and when using a CF system, the SAU25 should be<br />

fitted on the last enclosure with the <strong>Purge</strong> Inlet connected to the first enclosure. The bore and<br />

length of the pipe or conduit used to interconnect the enclosures is critical and will determine<br />

the maximum pressure experienced by the first enclosure in the series. Advice on sizing can be<br />

obtained from the <strong>Expo</strong> sales office but in general terms when using RLV25 or SAU25, the pipe<br />

bore size should not be less than 25mm (1”).<br />

A common fault of installing small bore pipe leads to over pressurizing of all but the last<br />

enclosure.<br />

PEs should not be connected in parallel.<br />

5. Commissioning<br />

Start by check that the system has been installed in<br />

accordance with this manual.<br />

Disconnect the supply pipe from the inlet to the <strong>Mini</strong><strong>Purge</strong> �<br />

system and blow it through for at least 10 seconds per meter<br />

(3ft) of length to remove any debris or condensation.<br />

Connect a temporary pressure gauge or water manometer to<br />

the PE or <strong>Mini</strong><strong>Purge</strong> � system pressure test point (Remove the<br />

red plug on the low pressure sensor and connect 4mm OD<br />

nylon tube).<br />

Figure 11. PE or <strong>Mini</strong><strong>Purge</strong> � system pressure test point<br />

Unless a supply shut-off valve has been specially fitted inside the <strong>Mini</strong><strong>Purge</strong> � system, it may be<br />

advisable to install an external shutoff valve with the same, or larger, thread size as the<br />

<strong>Mini</strong><strong>Purge</strong> � CU inlet fitting upstream of the connection.<br />

5.1 Continuous Flow (CF) Systems<br />

Open the Flow Control Valve (FCV) until the alarm/pressurized indicator just turns from red to<br />

green. Clockwise will reduce the flow and anti-clockwise will increase the airflow.<br />

If the FCV is opened fully and the indicator has still not turned green, check the air supply<br />

pressure at the inlet to the control unit while flow is taking place. It must be above the<br />

minimum 4 bar/ 60 psig/ 400kPa specified.<br />

Figure 12. Flow Control Valve (FCV)<br />

Check that the internal logic gauge reads 2bar /30 psig/200kPa.<br />

The purge timer will start as soon as the ‘alarm/pressurized’<br />

indicator turns from red (alarm) to green (pressurized). Check that<br />

the time delay between the indicator turning green and the<br />

application of power to the PE is not less than the minimum time<br />

required to purge the PE. When the purge time has been<br />

completed, the ‘purge complete’ indicator will turn from red to<br />

green.<br />

After the power has been turned on by the CU, the air flow will<br />

continue at the same rate to provide dilution as required.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 11 of 22


5.2 Leakage Compensation Systems (LC)<br />

Figure 13 Leakage Compensation Valve<br />

Open the Leakage Compensation Valve (LCV) fully, turn anti-clockwise.<br />

Clockwise will reduce the flow and anti-clockwise will increase the airflow.<br />

Open the supply regulator SLOWLY and allow the PE pressure to rise until<br />

the RLV opens. Check that the RLV opens at or below the figure specified<br />

in the documentation.<br />

Note tolerance of � 2 mbarg / 0.8” WC / 200Pa<br />

Repeat the test several times.<br />

Open the supply regulator to between 4 and 8 barg / 60 and 115 psi / 400<br />

and 800 kPa and the purging flow will start.<br />

Check that the internal logic gauge reads 2 bar /30 psi / 200 kPa<br />

At this time the "alarm/pressurized” indicator should be green and the "purging” indicator should<br />

be yellow. If the yellow indicator remains black the flow through the RLV is below the minimum<br />

for which the flow sensor has been calibrated. Check the air supply pressure at the inlet to<br />

the control unit while purging is taking place. It must be above the minimum specified.<br />

The purge timer will start as soon as the "purging" indicator turns yellow. Check that the time<br />

delay between the “purging” indicator turning yellow and the application of power to the PE is<br />

not less than the minimum time required purging the PE. Times in excess of the minimum are<br />

permitted and a tolerance of +20% is normally acceptable. If the time is too short it must be<br />

increased accordingly.<br />

After the power has been applied via the CU, the purging valve will close and the air flow into<br />

the enclosure will be controlled by the LCV. The initial setting of fully open will normally be too<br />

high. It should now be adjusted to set the PE pressure and leakage. There are three possible<br />

situations:<br />

Air continues to come out through the RLV Spark Arrestor after power has been applied in<br />

considerable quantity. The LCV is much too far open and the air flow is holding the RLV<br />

open continuously.<br />

Close the LCV slowly. The PE pressure will start to fall as the flow decreases but eventually<br />

the RLV will close and the enclosure pressure rise again. At this point the RLV may start to<br />

open intermittently as the PE pressure rises to the point where it exceeds the RLV opening<br />

pressure. When the RLV opens the pressure will fall quickly to the point where the RLV recloses<br />

and the enclosure pressure starts to rise again. This is entirely normal for this type of<br />

RLV.<br />

If the RLV is opening intermittently the LCV is slightly too far open. When the RLV opens<br />

the enclosure pressure falls quickly to the point where the RLV re-closes and the enclosure<br />

pressure starts to rise again. This is entirely normal for this type of RLV and shows that it is<br />

working correctly.<br />

Continue then to close the LCV until the cycling stops and the enclosure pressure starts to<br />

fall. Carefully adjust the LCV until the PE pressure is approximately 50% of the RLV<br />

opening pressure and stable. This pressure may be around 5 mbarg / 2” WC / 500 Pa and<br />

will be the "normal working pressure".<br />

We recommend that the setting of the minimum pressure sensor be checked at this time. Note<br />

the position of the LCV knob. (A pencil mark placed on the knob at "12 O'clock” can be used).<br />

Slowly lower the PE pressure by closing the LCV further, counting the number of turns from the<br />

"normal working pressure" position. Note the pressure at which the "alarm/pressurized"<br />

indicator turns from green to red and check that it is not lower than the figure given in the<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 12 of 22


documentation. Check also the "alarm" electrical contacts. As soon as the "alarm/pressurized"<br />

indicator turns red, the system will start to re-purge. If Alarm and Trip function is selected the<br />

enclosure power will be switched off.<br />

While it is re-purging return the LCV to its "normal working pressure" position so that, at the end<br />

of purging, the enclosure pressure should immediately settle down at the correct "normal"<br />

pressure.<br />

If, at the end of purging, the PE pressure falls below the minimum pressure sensor setting<br />

and the LCV is fully open, the system will start to purge again. This is indicative of<br />

excessive leakage from the enclosure. In this case, check the enclosure for leakage, and<br />

reduce or eliminate the leaks. This time, at the end of purging, the enclosure should stay<br />

pressurized and the RLV action is as in a) or b) above. Proceed as described above.<br />

5.3 Normal operation<br />

Turn the air supply on or off to start or stop the system. After this the pressurizing and purging<br />

sequence is entirely automatic<br />

6. Maintenance of the System<br />

The maintenance recommended for the system consists of the following items, supplemented<br />

by any additional local requirements imposed by the local Code of Practice. <strong>Expo</strong> recommends<br />

that the commissioning tests be repeated at least every six months.<br />

In addition the following checks are also recommended at that time:<br />

Check the RLV and all Spark Arrestors. Remove all debris & corrosion, or replace with a<br />

spare.<br />

Check the condition of the air supply filter element. Clean or replace it as necessary.<br />

At least every two years check the following additional items:<br />

Apparatus is suitable for the Hazardous Location<br />

There are no unauthorised modifications<br />

The air supply must be to the correct quality, refer to section Air Quality<br />

The interlocks and alarms function correctly<br />

Approval labels are legible and undamaged<br />

Adequate spares are carried<br />

The action on pressure failure is correct<br />

Pressure sensor calibration<br />

If it is decided that the minimum pressure /purge flow sensor needs recalibrating it must be<br />

returned to <strong>Expo</strong> for this service.<br />

Filter cleaning<br />

If the filter element needs cleaning the filter bowl can be unscrewed and removed. The filter<br />

element also unscrews and can then be cleaned in soapy water. Do not use solvents on any<br />

part of the filter assembly.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 13 of 22


7. Fault Finding<br />

If the system does not behave in the manner described above there is a fault. Some of the<br />

more likely faults are dealt with below. If a cure cannot be affected by following the procedure<br />

shown below please call <strong>Expo</strong> (24 hour answering) or your supplier for further assistance.<br />

The system has been designed for ease of fault finding and the many of the components fitted<br />

are plug-in or manifold mounted. Check components by substitution only after establishing that<br />

such action is necessary. If the system is less than 12 months old, parts under warranty should<br />

be returned to <strong>Expo</strong> for investigation, with a full report of the fault and the system serial number.<br />

As with any pneumatic system the greatest enemies are water, oil and dirt in the air supply. For<br />

this reason the air system must always incorporate a dust and water filter. This can be part of<br />

the <strong>Expo</strong> system or can be provided by others. However dirt can enter from other sources and<br />

it is vital therefore that the procedures described in Section 2 is carried out before using the<br />

system for the first time, or following any disconnection of the pipe-work. Failure to perform this<br />

work may cause damage that will not be covered under warranty.<br />

Before making the following checks verify that both the main air supply pressure to the purge<br />

system & the regulated pressure to the logic are as specified on the system specification sheet.<br />

Different flow charts for faulting have been provided for both the CF and LC options.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 14 of 22


Fault Finding (CF)<br />

Pressurized/Purging indicator<br />

will not turn green during<br />

start up<br />

Is the air supply<br />

pressure<br />

incorrect?<br />

No<br />

Is the supply<br />

pipe to the air<br />

inlet as least<br />

12mm I.D?<br />

Yes<br />

Is there<br />

excessive<br />

leakage from<br />

the PE?<br />

No<br />

Is the PE<br />

strong enough?<br />

Yes<br />

Is the Pressure /<br />

Flow Sensor out<br />

of calibration or<br />

faulty?<br />

No<br />

Call <strong>Expo</strong><br />

Yes<br />

Yes<br />

No<br />

Yes<br />

No<br />

Check the air<br />

supply pressure<br />

at the inlet to the<br />

<strong>Mini</strong><strong>Purge</strong> is<br />

stable between<br />

4 - 8 Barg /<br />

60 - 115 psi<br />

Replace pipe<br />

work<br />

Any significant<br />

leakage must be<br />

corrected. Check<br />

for leaks down<br />

the cables or<br />

conduit. Ensure<br />

leakage does not<br />

exceed 60 Nl/min<br />

(25 cfm)<br />

The standard<br />

requires that the<br />

PE is tested to<br />

1.5 times the<br />

Relief Valve<br />

opening pressure<br />

e.g. 15 mbarg for<br />

many systems.<br />

Has this been<br />

done?<br />

The basic operation of the Pressure Sensor<br />

can be checked by unscrewing the 60mm<br />

diameter diaphragm housing and, by using a<br />

rubber pad, e.g. an eraser, block the 12mm<br />

threaded hole in the top of the valve module.<br />

The valve should operate and the indicator<br />

turn green. If this is correct, the sensor<br />

diaphragm needs recalibrating or replacing.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 15 of 22


System fails to switch power<br />

on after the purge time has<br />

elapsed.<br />

Is Power<br />

available?<br />

Yes<br />

Is Power<br />

isolator closed?<br />

Yes<br />

Are the fuses or<br />

circuit breaker?<br />

OK?<br />

Yes<br />

Has the purge<br />

time completed<br />

its course?<br />

Yes<br />

For PO option only<br />

Is there pressure at the<br />

power switch output<br />

bulkhead and at the<br />

power switch? Is the<br />

power switch OK?<br />

Yes<br />

For PO option only<br />

Is the tube to the<br />

power switch air<br />

tight?<br />

Yes<br />

Is the <strong>Purge</strong><br />

time correct?<br />

Yes<br />

Call <strong>Expo</strong><br />

No<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 16 of 22<br />

No<br />

No<br />

No<br />

No<br />

No<br />

No<br />

Check the small<br />

indicator button<br />

on the timer<br />

valve. When the<br />

valve has timed<br />

out, it should<br />

return out when<br />

depressed.<br />

Check if the<br />

external Power<br />

Switch contacts<br />

close at 1.4 Barg<br />

Ensure fitting nuts<br />

are tightened and<br />

that the tube is<br />

not damaged.<br />

Check and repair<br />

as necessary.<br />

Note the timer setting. Reset the timer to the<br />

minimum available purging period and check<br />

the operation on that purge time.<br />

Ensure that the purge time is returned to<br />

its original setting and checked before<br />

putting the system back into service.


Relief Valve opens<br />

continuously or<br />

intermittently.<br />

Is the Pressurized<br />

Enclosure<br />

pressure too<br />

high?<br />

No<br />

Is there debris on<br />

the RLV disk<br />

allowing air to<br />

leak from the<br />

valve?<br />

No<br />

Call <strong>Expo</strong><br />

The Flow Control Valve<br />

(FCV) is too far open.<br />

Adjust the FCV<br />

clockwise to reduce the<br />

PE pressure<br />

Remove the RLV cover<br />

and clean the valve<br />

disk. If it is necessary to<br />

remove the disk and<br />

spring from the RLV,<br />

draw a line around it<br />

with a pencil to allow<br />

accurate replacement<br />

before removal,<br />

otherwise the opening<br />

pressure may be<br />

affected.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 17 of 22<br />

Yes<br />

Yes


Fault Finding (LC)<br />

System purges correctly<br />

but the alarm comes on<br />

at the end of purge time<br />

and the purging cycle is<br />

repeated.<br />

Yes<br />

Is the actual PE<br />

pressure below<br />

the setting of the<br />

<strong>Mini</strong>mum<br />

Pressure Sensor?<br />

No<br />

Is the Leakage<br />

Compensation<br />

Valve setting too<br />

low causing the<br />

<strong>Mini</strong><strong>Purge</strong> to<br />

auto-repurge?<br />

No<br />

Call <strong>Expo</strong><br />

Check the PE pressure<br />

with a manometer or<br />

gauge.<br />

Increase the PE<br />

pressure by turning the<br />

Leakage Compensation<br />

Valve anti-clockwise.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 18 of 22<br />

Yes<br />

Yes


Purging indicator will not<br />

turn "Yellow" during<br />

Purging.<br />

Is the air supply<br />

pressure<br />

incorrect?<br />

No<br />

Is the supply<br />

pipe to the air<br />

inlet as least<br />

12mm I.D?<br />

Yes<br />

Is there<br />

excessive<br />

leakage from<br />

the PE?<br />

No<br />

Is the PE strong<br />

enough?<br />

Yes<br />

Is the tube<br />

between the RLV<br />

tapping and flow<br />

sensor air tight?<br />

Yes<br />

Is the <strong>Purge</strong><br />

Flow Sensor out<br />

of calibration or<br />

faulty?<br />

No<br />

Call <strong>Expo</strong><br />

Yes<br />

Check the air<br />

supply pressure<br />

at the inlet to the<br />

<strong>Mini</strong><strong>Purge</strong> is<br />

stable between<br />

4 - 8 Barg /<br />

60 - 115 psi<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 19 of 22<br />

Yes<br />

No<br />

Yes<br />

No<br />

No<br />

Replace pipe<br />

work<br />

Any significant<br />

leakage must be<br />

corrected. Check<br />

for leaks down<br />

the cables or<br />

conduit. Ensure<br />

leakage does not<br />

exceed 60<br />

Nl/min (25 cfm)<br />

The standard<br />

requires that the<br />

PE is tested to<br />

1.5 times the<br />

Relief Valve<br />

opening<br />

pressure e.g. 15<br />

mbarg for many<br />

systems. Has<br />

this been done?<br />

Ensure fitting nuts<br />

are tightened and<br />

that the tube is<br />

not damaged.<br />

Check and repair<br />

as necessary.<br />

The basic operation of the <strong>Purge</strong> Flow<br />

Sensor can be checked by unscrewing the<br />

60mm diameter diaphragm housing and, by<br />

using a rubber pad, e.g. an eraser, block<br />

the 12mm threaded hole in the top of the<br />

valve module. The valve should operate<br />

and the indicator turn amber. If this is<br />

correct, the sensor diaphragm needs<br />

recalibrating or replacing.


System fails to switch power<br />

on after the purge time has<br />

elapsed.<br />

Is Power<br />

available?<br />

Yes<br />

Is Power<br />

isolator closed?<br />

Yes<br />

Are the fuses or<br />

circuit breaker?<br />

OK?<br />

Yes<br />

Has the purge<br />

time completed<br />

its course?<br />

Yes<br />

For PO option only<br />

Is there pressure at the<br />

power switch output<br />

bulkhead and at the<br />

power switch? Is the<br />

power switch OK?<br />

Yes<br />

For PO option only<br />

Is the tube to the<br />

power switch air<br />

tight?<br />

Yes<br />

Is the <strong>Purge</strong><br />

time correct?<br />

Yes<br />

Call <strong>Expo</strong><br />

No<br />

No<br />

No<br />

No<br />

No<br />

No<br />

Check the small<br />

indicator button<br />

on the timer<br />

valve. When the<br />

valve has timed<br />

out, it should<br />

return out when<br />

depressed.<br />

Check if the<br />

external Power<br />

Switch contacts<br />

close at 1.4 Barg<br />

Ensure fitting nuts<br />

are tightened and<br />

that the tube is not<br />

damaged. Check<br />

and repair as<br />

necessary.<br />

Note the timer setting. Reset the timer to the<br />

minimum available purging period and check<br />

the operation on that purge time.<br />

Ensure that the purge time is returned to<br />

its original setting and checked before<br />

putting the system back into service.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 20 of 22<br />

No


Relief Valve opens<br />

continuously or<br />

intermittently.<br />

Is the Pressurized<br />

Enclosure<br />

pressure too<br />

high?<br />

No<br />

Is there debris on<br />

the RLV disk<br />

allowing air to<br />

leak from the<br />

valve?<br />

No<br />

Call <strong>Expo</strong><br />

The Leakage<br />

Compensation Valve<br />

(LCV) is too far open.<br />

Adjust the LCV<br />

clockwise to reduce the<br />

PE pressure<br />

Remove the RLV cover<br />

and clean the valve<br />

disk. If it is necessary to<br />

remove the disk and<br />

spring from the RLV,<br />

draw a line around it<br />

with a pencil to allow<br />

accurate replacement<br />

before removal,<br />

otherwise the opening<br />

pressure may be<br />

affected.<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 21 of 22<br />

Yes<br />

Yes


8. Approval Documents<br />

System Approval Authority Certificate Number<br />

<strong>Mini</strong><strong>Purge</strong> � IECEx SIR 07.0027X<br />

Sira 01ATEX 1295X<br />

INMETRO/TUV TÜV 12.1462X<br />

FM 1X8A4.AE<br />

UL E190061<br />

For PA Option Only Approval Authority Certificate Number<br />

Ex e junction box IECEx IECEx ITS10.0003X<br />

ATEX ITS 10 ATEX 37092X<br />

TUV TÜV 12.1463<br />

Ex d switches IECEx PTB IECEx PTB07.0045X<br />

PTB 00 ATEX 1093 X<br />

Bartec 01-2511-7C0001<br />

9. Glossary<br />

Acronym Description<br />

A&T Alarm and Trip<br />

AO Alarm Only<br />

CF Continuous Flow<br />

CU Control Unit<br />

FCV Flow Control Valve<br />

FM Factory Mutual<br />

IS Intrinsically Safe<br />

LC Leakage Compensation<br />

LCV Leakage Compensation Valve<br />

MIU <strong>Mini</strong><strong>Purge</strong> � Interface Unit<br />

PA Ex d Power and Alarm Switch Wired to Ex e terminal box<br />

PE Pressurized Enclosure<br />

PO Pneumatic Output<br />

RLV Relief Valve<br />

SAU Spark Arrestor Unit<br />

UL Underwriter Laboratories<br />

<strong>ML</strong> <strong>442</strong> Issue 5C SP5115 09/11/12 ©<br />

Page 22 of 22


The contents of this drawing / document are Copyright © <strong>Expo</strong> <strong>Technologies</strong> Limited. They are to be treated as confidential<br />

and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent<br />

from <strong>Expo</strong> <strong>Technologies</strong> Limited, neither are they to be used in any way against our interests.<br />

UNSPECIFIED NO DEC PLACE ±0.5<br />

TOLERANCES 1 DEC PLACE ±0.2<br />

2 DEC PLACE ±0.1<br />

FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH<br />

DIMENSIONS IN mm<br />

DO NOT SCALE<br />

3rd ANGLE<br />

PROJECTION<br />

PRESSURIZED INDICATOR<br />

Pressurized Enclosure door closed<br />

Red = Pressure Low<br />

"Pressurized" signal absent i.e. "Alarm" ON<br />

Turn Pressurizing air or inert gas on<br />

Enclosure door opened, or excessive leakage<br />

Pressurizing air or inert gas turned off<br />

Air enters the PE<br />

Enclosure pressure falls below the minimum<br />

No<br />

Is the PE pressure above the minimum?<br />

Low Pressure sensor turns off<br />

PRESSURIZED INDICATOR<br />

Action taken on pressure failure<br />

Red = Pressure Low<br />

depends upon the user. Actions<br />

include:- Alarm and/or Trip<br />

Alarm and delayed trip Power turned off automatically without delay "Pressurized" signal absent i.e. "Alarm" ON<br />

Yes<br />

PRESSURIZED INDICATOR<br />

Low Pressure sensor turns on<br />

Green = Pressure OK<br />

Relief Valve opens <strong>Purge</strong> flow starts "Pressurized" signal to remote alarm switch<br />

No<br />

<strong>Purge</strong> Outlet flow above the minimum?<br />

Yes<br />

<strong>Purge</strong> Flow Sensor turns on<br />

<strong>Purge</strong> timer resets<br />

"Purging" Indicator<br />

Amber = <strong>Purge</strong> flow OK<br />

Black = <strong>Purge</strong> flow too low<br />

<strong>Purge</strong> timer starts automatically<br />

No<br />

Outlet flow still above the minimum?<br />

Key to functions<br />

Yes<br />

<strong>Purge</strong> timer times out<br />

<strong>Manual</strong> operation by the user<br />

<strong>Purge</strong> valve closes; Power Sw. signal ON<br />

Automatic operation by the system<br />

"<strong>Purge</strong> Complete" signal to electrical Power Switch<br />

<strong>Purge</strong> flow ceases; Relief Valve closes<br />

Optional operation (User decision)<br />

Purging Indicator turns Black as<br />

<strong>Purge</strong> flow falls below minimum<br />

Leakage Compensation starts<br />

THIS DRAWING IS REFERENCED TO<br />

EXPO CETIFICATION DRAWING EP99-2-3<br />

Power on - Normal operation<br />

REV:<br />

01<br />

1:1<br />

SCALE<br />

SURREY KT7 0RH<br />

UNITED KINGDOM<br />

<strong>Expo</strong> <strong>Technologies</strong> Limited<br />

MATERIAL<br />

23/06/2010<br />

DRAWN DATE:<br />

REV. MOD NUMBER APPROVED DATE APPROVED<br />

Controlled<br />

DRAWING No.<br />

TITLE<br />

DRAWING STATUS:<br />

XBR-7TD0-040<br />

1<br />

MINIPURGE X LC SEQUENCE DIAGRAM<br />

FINISH<br />

CUSTOMER:<br />

JOB No:<br />

SHEET No. OF 1<br />

APP'D CHK'D DR'WN<br />

JPdB PSC BRD<br />

01 DRAWN 23/06/2010 JPdB


The contents of this drawing / document are Copyright © <strong>Expo</strong> <strong>Technologies</strong> Limited. They are to be treated as confidential<br />

and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent<br />

from <strong>Expo</strong> <strong>Technologies</strong> Limited, neither are they to be used in any way against our interests.<br />

UNSPECIFIED NO DEC PLACE ±0.5<br />

TOLERANCES 1 DEC PLACE ±0.2<br />

2 DEC PLACE ±0.1<br />

FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH<br />

DIMENSIONS IN mm<br />

3rd ANGLE<br />

PROJECTION<br />

DO NOT SCALE<br />

Enclosure door opened, or excessive leakage<br />

Pressurizing air or inert gas turned off<br />

PRESSURIZED INDICATOR<br />

Red = Pressure Low<br />

Pressurized Enclosure door closed<br />

Enclosure pressure or Flow<br />

fall below the minimum<br />

"Pressurized/Flow" signal absent i.e. "Alarm" ON<br />

Turn Pressurizing air or inert gas on<br />

Pressurized/Flow Indicator<br />

Red = Pressure/Flow Low<br />

Low Pressure/Flow sensor turns off<br />

Air enters the PE<br />

"Pressurized/Flow" signal absent i.e. "Alarm" ON<br />

Power turned off automatically<br />

with/without delay<br />

Enclosure pressure and the purge outlet<br />

flow above the minimum specified?<br />

No<br />

Action taken on Pressure/Flow<br />

failure depends upon the user.<br />

Actions include:- Alarm and/or<br />

Trip Alarm and delayed trip<br />

Yes<br />

PRESSURIZED INDICATOR<br />

Green = Pressure/Flow OK<br />

Low Pressure sensor turns on<br />

<strong>Purge</strong> timer resets<br />

"Pressurized/Flow" signal to remote alarm switch<br />

<strong>Purge</strong> timer starts automatically<br />

No<br />

<strong>Purge</strong> Outlet flow above the minimum?<br />

Yes<br />

<strong>Purge</strong> timer times out<br />

Power On Indicator turns<br />

Green at "<strong>Purge</strong> Complete"<br />

Power Sw. signal ON<br />

Possible "Action on Pressure/Flow<br />

Failure" (user decision)<br />

"<strong>Purge</strong> Complete" signal to electrical Power Switch<br />

Power on<br />

Key to functions<br />

Continuous Flow/ Dilution Flow starts<br />

<strong>Manual</strong> operation by the user<br />

<strong>Purge</strong> flow ceases; Relief Valve closes<br />

No<br />

Automatic operation by the system<br />

Outlet flow still above the minimum?<br />

Yes<br />

Optional operation (User decision)<br />

Power on - Normal operation<br />

THIS DRAWING IS REFERENCED TO<br />

EXPO CERTIFICATION DRAWING EP99-2-4<br />

REV:<br />

1:1 01<br />

SCALE<br />

SURREY KT7 0RH<br />

UNITED KINGDOM<br />

<strong>Expo</strong> <strong>Technologies</strong> Limited<br />

MATERIAL<br />

23/06/2010<br />

DRAWN DATE:<br />

REV. MOD NUMBER APPROVED DATE APPROVED<br />

XBR-7TD0-041<br />

Controlled<br />

TITLE<br />

DRAWING No.<br />

APP'D CHK'D DR'WN FINISH<br />

MINIPURGE X CF SEQUENCE DIAGRAM<br />

JPdB PSC BRD<br />

JOB No:<br />

CUSTOMER:<br />

SHEET No. 1 OF 1<br />

DRAWING STATUS:<br />

01 DRAWN 23/06/2010 JPdB


1)<br />

2)<br />

3)<br />

133 [5 1 4 "]<br />

<strong>Mini</strong><strong>Purge</strong><br />

CONFIGURATION<br />

NOTES:<br />

USE DIRECT MOUNTING WHEREVER<br />

POSSIBLE, WALL MOUNTING<br />

BRACKETS AND PIPING KITS FOR<br />

SIDE MOUNTING ARE OPTIONAL.<br />

MINIPURGE MUST BE MOUNTED IN<br />

THE POSTIONS SHOWN.<br />

PURGE AIR TO VENT INTO TOP OF<br />

ENCLOSURE AND EXIT THROUGH<br />

RELIEF VALVE /SPARK ARRESTOR<br />

AT THE BOTTOM OF THE<br />

ENCLOSURE.<br />

D.P. LO<br />

6mm OR M5 (10-32 UNF)<br />

FITTING SUPPLIED<br />

33 [1 5<br />

"]<br />

5<br />

16<br />

29 [1<br />

32 "]<br />

PURGE OUTLET<br />

DO NOT OBSTRUCT<br />

LC OPTION ONLY.<br />

FLOW MONITORING<br />

PIPE REQUIRED<br />

RLV 25 RELIEF VALVE<br />

44 [1 23<br />

32 "]<br />

FOR LC<br />

SYSTEMS<br />

ONLY<br />

GASKET<br />

HOUSING<br />

PANEL<br />

MOUNT<br />

(OPTIONAL)<br />

RLV25 RELIEF VALVE<br />

WEIGHT = 0.5 kg (1.1 lb)<br />

M5 FIXINGS SUPPLIED<br />

Ø6 (Ø1/4") HOLES REQUIRED<br />

IN ENCLOSURE.<br />

HOLE Ø25(1") REQUIRED<br />

IN ENCLOSURE<br />

44 [1 23<br />

32 "]<br />

62 [2 15<br />

32 "]<br />

CUTOUT DETAILS VIEWED<br />

FROM INSIDE ENCLOSURE<br />

46 [1 13<br />

16 "]<br />

ALARM<br />

(RED)<br />

ALARM ALARME<br />

(ROT) (ROUGE)<br />

PRESSURIZED<br />

PURGING<br />

(GREEN)<br />

(YELLOW)<br />

PRESSURISE DRUCK OK EN BALAYAGE VORSPÜLUNG<br />

(VERT) (GRÜN) (JAUNE) (GELB)<br />

EN50 016:1977 (BS 5501 pt 3)<br />

EEx p II SCS Certificate Ex 94C1052U<br />

BS EN50016:1995 (2nd edition)<br />

[EEx p] II Sira Certificate Ex99E1002U<br />

SAU25 SPARK ARRESTOR<br />

WEIGHT = 0.2 kg (0.44 lb)<br />

D.P. LO<br />

6mm OR M5 (10-32 UNF)<br />

FITTING SUPPLIED<br />

M25 X 1.5P THREAD<br />

Ø26mm (1") CLEAREANCE<br />

HOLE REQUIRED IN<br />

ENCLOSURE<br />

35 [1 3 8 "]<br />

55 [2 5<br />

"]<br />

32<br />

25 [31<br />

32 "]<br />

DIRECT MOUNT (PREFERRED OPTION)<br />

SIDE<br />

MOUNT<br />

PIPING KIT<br />

(OPTIONAL)<br />

CF OPTION<br />

SAU 25 SPARK<br />

ARRESTOR<br />

(CF OPTION ONLY)<br />

ORIFICE PLATE<br />

AND CIRCLIP<br />

SEE NOTE<br />

GASKET<br />

SPARK<br />

ARRESTOR<br />

BODY<br />

NOTE:-<br />

SYSTEMS SUPPLIED WITHOUT ENCLOSURES ARE<br />

SUPPLIED WITH A RANGE OF 8 ORIFICE PLATES TO SUIT<br />

FLOW RATES BETWEEN 10-225 NL/MIN (0.4-8 SCFM)<br />

XBR-7TD0-003 ISSUE 4<br />

Sub <strong>Mini</strong><strong>Purge</strong> Systems<br />

CONFIGURATION


The contents of this drawing / document are Copyright © <strong>Expo</strong> <strong>Technologies</strong> Limited. They are to be treated as confidential and are returnable<br />

upon request. They are not to be copied or communicated in part or in whole without written consent from <strong>Expo</strong> <strong>Technologies</strong> Limited, neither<br />

are they to be used in any way against our interests.<br />

UNSPECIFIED NO DEC PLACE ±0.5<br />

TOLERANCES 1 DEC PLACE ±0.2<br />

2 DEC PLACE ±0.1<br />

FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH<br />

DIMENSIONS IN mm<br />

DO NOT SCALE<br />

3rd ANGLE<br />

PROJECTION<br />

35 [1.30"] APPROX.<br />

MOUNTING BAR PITCH = 180 [7.09"]<br />

150 [5.91"]<br />

PURGE<br />

INDICATOR 2<br />

ALARM<br />

INDICATOR 1<br />

MOUNTING BAR<br />

(SPECIAL OPTION ONLY)<br />

129 [5.08"]<br />

INDICATORS<br />

PURGE<br />

COMPLETE<br />

PURGING<br />

PRESSURIZED<br />

ALARM<br />

MOUNTING BAR PITCH = 210 [8.27"]<br />

<strong>Mini</strong><strong>Purge</strong><br />

1 2<br />

BLACK<br />

YELLOW<br />

GREEN<br />

RED<br />

LEAKAGE<br />

COMPENSATION<br />

(LC)<br />

155 [6.10"]<br />

PA. OPTION<br />

CUSTOMER TO<br />

SITE AND DRILL<br />

INPUT GLAND<br />

HOLE<br />

180 [7.09"]<br />

GREEN<br />

RED<br />

GREEN<br />

RED<br />

CONTINUOUS<br />

FLOW (CF)<br />

www.expoworldwide.com<br />

BLACK<br />

YELLOW<br />

GREEN<br />

RED<br />

CONTINUOUS<br />

FLOW AFTER<br />

HIGH PURGE<br />

(CFHP)<br />

102 [4.02"]<br />

8 [0.31"]<br />

APPROX.<br />

REMOVABLE COVER<br />

45 [1.77"]<br />

PO. OPTION<br />

PURGE OUTLET 1/2" NPTF<br />

D.P. HI / ENCLOSURE PRESSURE 1/8" NPTF<br />

(LC OPTION ONLY)<br />

35 [1.30"]<br />

APPROX.<br />

HOLE Ø7.5 [Ø0.30"]<br />

FOR M6 OR<br />

1/4" FIXING<br />

POWER INTERLOCK<br />

SIGNAL<br />

1/8" NPTF<br />

D.P. LO / RLV OR SAU CONNECTION 1/8" NPTF<br />

HOLE SUITABLE FOR GLAND M20 OR 1/2" NPT<br />

AIR SUPPLY 4 - MAX 8 barg [60-115 psi]<br />

1/2" NPTF<br />

[1.38"]<br />

35<br />

65 [2.56"]<br />

37<br />

[1.46"]<br />

PASSIVE ALARM<br />

/ PRESSURIZED<br />

SIGNAL<br />

1/8" NPTF<br />

90 [3.54"]<br />

75 [2.95"]<br />

5 [0.20"]<br />

96 [3.78"]<br />

IS. OPTION<br />

HOLE SUITABLE<br />

FOR GLAND M20 OR<br />

1/2" NPT<br />

NOTES<br />

MINIPURGE MUST BE MOUNTED WITH PURGE OUTLET FITTING IN<br />

65 [2.56"]<br />

8 [0.31"] APPROX.<br />

1.<br />

120 [4.72"]<br />

VERTICAL PLANE POINTING DOWN.<br />

[1.61"]<br />

41<br />

155 [6.10"]<br />

APPROXIMATE WEIGHT: 5.5 kg [12.1 POUNDS].<br />

2.<br />

EQUIVALENT IMPERIAL DIMENSIONS SHOWN IN BRACKETS.<br />

3.<br />

185 [7.28"]<br />

REFER TO DRG XSD-7TD0-001 FOR MOUNTING DETAILS.<br />

240 [9.45"]<br />

SCALE<br />

SURREY KT7 0RH<br />

UNITED KINGDOM<br />

<strong>Expo</strong> <strong>Technologies</strong> Limited<br />

MATERIAL<br />

STAINLESS STEEL<br />

1<br />

DRAWN<br />

DRAWING No.<br />

TITLE<br />

FINISH<br />

1 3<br />

CUSTOMER:<br />

JOB No:<br />

NROB<br />

5<br />

4657<br />

2/4/09<br />

JPdB<br />

4<br />

4385<br />

21/12/07<br />

JPdB<br />

3<br />

4353<br />

13/09/07<br />

SHEET No. OF<br />

MJF JPdB<br />

NON CERTIFIED<br />

ISSUE:<br />

MOD. No:<br />

DATE:<br />

APPROVED:<br />

DRAWING STATUS:


The contents of this drawing / document are Copyright © <strong>Expo</strong> <strong>Technologies</strong> Limited. They are to be treated as confidential and are returnable<br />

upon request. They are not to be copied or communicated in part or in whole without written consent from <strong>Expo</strong> <strong>Technologies</strong> Limited, neither<br />

are they to be used in any way against our interests.<br />

NO DEC PLACE ±0.5<br />

1 DEC PLACE ±0.2<br />

2 DEC PLACE ±0.1<br />

UNSPECIFIED<br />

TOLERANCES<br />

DIMENSIONS IN mm<br />

DO NOT SCALE<br />

3rd ANGLE<br />

PROJECTION<br />

FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH<br />

LC LEAKAGE COMPENSATION SHOWN (ITEMS IN DOTTED REMOVED FOR CF)<br />

TO RESERVOIRS<br />

8<br />

9<br />

76<br />

2 18 13 3 7<br />

TIMER<br />

PINCH<br />

VALVES<br />

1<br />

PURGE TIME SELECTOR<br />

DOOR INTERNAL<br />

15<br />

16<br />

17<br />

33 35<br />

26<br />

34<br />

22<br />

PUSH-IN PLUG<br />

ENCLOSURE<br />

PRESSURE<br />

TEST POINT<br />

26<br />

14<br />

19<br />

AO C A&T AO C A&T<br />

ALARM ONLY<br />

ALARM AND TRIP<br />

PLUG 4mm<br />

26<br />

MINIMUM PRESSURE SENSOR<br />

14<br />

GAUGE, LOGIC AIR SUPPLY<br />

1<br />

"ACTION ON ALARM" OPTION PIPE<br />

33<br />

MAIN AIR SUPPLY FILTER, MANUAL DRAIN<br />

15<br />

LOGIC AIR SUPPLY REGULATOR<br />

2<br />

ALARM ONLY PUSH-IN FITTING<br />

34<br />

PURGE COMPLETE "OR" GATE<br />

16<br />

IN LINE RESTRICTOR<br />

3<br />

ALARM AND TRIP PUSH-IN FITTING<br />

35<br />

LEAKAGE COMPENSATION VALVE<br />

17<br />

BLACK COLLAR (PLUGGED)<br />

7<br />

PURGE TIME SELECTOR<br />

76<br />

TIMER VALVE<br />

18<br />

INDICATOR, "ALARM/PRESSURIZED"<br />

8<br />

PURGE BOOST VALVE<br />

19<br />

INDICATOR, "PURGING"<br />

9<br />

PURGE COMPLETE VALVE (BELOW ITEM 17)<br />

22<br />

PURGE FLOW SENSOR<br />

13<br />

SCALE<br />

SURREY KT7 0RH<br />

UNITED KINGDOM<br />

<strong>Expo</strong> <strong>Technologies</strong> Limited<br />

MATERIAL<br />

DRAWING No.<br />

TITLE<br />

FINISH<br />

5<br />

4657<br />

2/4/09<br />

JPdB<br />

4<br />

4385<br />

21/12/07<br />

JPdB<br />

2 OF 3<br />

CUSTOMER:<br />

JOB No:<br />

SHEET No.<br />

1 3<br />

DRAWN 4353<br />

13/09/07<br />

MJF JPdB<br />

NON CERTIFIED<br />

ISSUE:<br />

MOD. No:<br />

DATE:<br />

APPROVED:<br />

DRAWING STATUS:


The contents of this drawing / document are Copyright © <strong>Expo</strong> <strong>Technologies</strong> Limited. They are to be treated as confidential and are returnable<br />

upon request. They are not to be copied or communicated in part or in whole without written consent from <strong>Expo</strong> <strong>Technologies</strong> Limited, neither<br />

are they to be used in any way against our interests.<br />

NO DEC PLACE ±0.5<br />

1 DEC PLACE ±0.2<br />

2 DEC PLACE ±0.1<br />

UNSPECIFIED<br />

TOLERANCES<br />

DIMENSIONS IN mm<br />

DO NOT SCALE<br />

3rd ANGLE<br />

PROJECTION<br />

FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH<br />

PA OPTION PO OPTION<br />

IS OPTION<br />

FLOW<br />

FLOW<br />

FLOW<br />

PA BOX<br />

MIN<br />

MIN<br />

MIN<br />

CLEAR 4mm PIPE TO PASSIVE<br />

ALARM/PRESSURIZED SIGNAL<br />

1/8" NPTF CONNECTOR<br />

Ex d SWITCH WIRED TO ALARM<br />

TERMINALS IN PA BOX<br />

TERMINALS FOR CONNECTING I.S.<br />

CIRCUITS VIA M20 OR 1/2" NPT CABLE<br />

ENTRY ON LHS OR BOTTOM<br />

BLUE 4mm PIPE TO POWER<br />

INTERLOCK 1/8" NPTF CONNECTOR<br />

Ex d SWITCH WIRED TO POWER<br />

TERMINALS IN PA BOX<br />

NOTE:<br />

LC VERSION SHOWN. (ITEMS IN DOTTED REMOVED FOR CF)<br />

SCALE<br />

SURREY KT7 0RH<br />

UNITED KINGDOM<br />

<strong>Expo</strong> <strong>Technologies</strong> Limited<br />

MATERIAL<br />

DRAWING No.<br />

TITLE<br />

FINISH<br />

5<br />

4657<br />

2/4/09<br />

JPdB<br />

4<br />

4385<br />

21/12/07<br />

JPdB<br />

3 OF 3<br />

CUSTOMER:<br />

JOB No:<br />

SHEET No.<br />

1 3<br />

DRAWN 4353<br />

13/09/07<br />

MJF JPdB<br />

NON CERTIFIED<br />

ISSUE:<br />

MOD. No:<br />

DATE:<br />

APPROVED:<br />

DRAWING STATUS:


IECEx Certificate<br />

of Conformity<br />

INTERNATIONAL ELECTROTECHNICAL COMMISSION<br />

IEC Certification Scheme for Explosive Atmospheres<br />

for rules and details of the IECEx Scheme visit www.iecex.com<br />

Certificate history:<br />

Issue No. 4 (2011-12-9)<br />

Issue No. 3 (2011-3-9)<br />

Issue No. 2 (2011-1-12)<br />

Issue No. 1 (2009-3-16)<br />

Issue No. 0 (2007-9-20)<br />

Certificate No.: IECEx SIR 07.0027X issue No.:4<br />

Status: Current<br />

Date of Issue: 2011-12-09 Page 1 of 4<br />

EXPO <strong>Technologies</strong> Ltd<br />

Summer Road<br />

Thames Ditton<br />

Surrey KT7 ORH<br />

United Kingdom<br />

Applicant:<br />

Electrical Apparatus: <strong>Mini</strong><strong>Purge</strong> <strong>Purge</strong> Controller<br />

Optional accessory:<br />

Type of Protection: Pressurised<br />

Marking: Standard versions: (Ta –20°C to +55°C)<br />

Ex [px] IIC T6 Gb<br />

Ex [py] IIC T6 Gb<br />

Ex [p] IIIC T85°C Db or<br />

Ex [pz Gc ] IIC T6 Gb<br />

Ex [p Dc] IIIC T85°C Db<br />

Standard /ET versions: (Ta –20°C to +55°C)<br />

Ex [px] ia IIC T6 Gb<br />

Ex [p] ia IIIC T95°C Db<br />

Low temp. versions: (Ta –50°C to +55°C)<br />

Ex[px]dem IICT3orT4Gb<br />

Ex [p] IIIC T200°C or T135°C Db<br />

Low temp. /ET versions: (Ta –50°C to +55°C)<br />

Ex [px] dem ia IIC T3 or T4 Gb<br />

Ex [p] ia IIIC T200°C or T135°C Db<br />

C Ellaby<br />

Approved for issue on behalf of the IECEx<br />

Certification Body:<br />

Position: Deputy Certification Manager<br />

Signature:<br />

(for printed version)<br />

Date:<br />

1. This certificate and schedule may only be reproduced in full.<br />

2. This certificate is not transferable and remains the property of the issuing body.<br />

3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.<br />

Certificate issued by:<br />

SIRA Certification Service<br />

Rake Lane<br />

Eccleston<br />

Chester<br />

CH4 9JN<br />

United Kingdom


CERTIFICATION<br />

CERTIFICATION<br />

SCHEDULE<br />

1 EC TYPE-EXAMINATION CERTIFICATE<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

2 Equipment intended for use in Potentially Explosive Atmospheres Directive 94/9/EC<br />

13 DESCRIPTION OF EQUIPMENT<br />

The <strong>Purge</strong> Controllers are pneumatically operated devices, which are intended to provide a given flow rate of<br />

purging gas for a predetermined time to unspecified Ex p protected electrical equipment. The <strong>Mini</strong><strong>Purge</strong><br />

Control Units provide one of the following four methods of purge operation.<br />

3 Certificate Number: Sira 01ATEX1295X Issue: 7<br />

4 Equipment: <strong>Purge</strong> Controllers: Sub-<strong>Mini</strong><strong>Purge</strong>, <strong>Mini</strong><strong>Purge</strong>, Super-<strong>Mini</strong><strong>Purge</strong>,<br />

Super-<strong>Mini</strong><strong>Purge</strong> 1800/3500/7000/7000X<br />

5 Applicant: EXPO <strong>Technologies</strong> Limited<br />

LC-Leakage compensation only after initial high purge<br />

CF-Continuous flow (same flow rate during and after purging)<br />

CF2-Two flow CF system with initial high purge rate only at one orifice<br />

CFHP-Continuous (lower) flow after initial high purge<br />

The <strong>Mini</strong><strong>Purge</strong> control unit may be supplied within a heated enclosure to permit the use of the system within<br />

an ambient temperature down to –50 o C.<br />

The <strong>Mini</strong><strong>Purge</strong> option pD is for use in combustible dust<br />

6 Address: Summer Road, Thames Ditton, Surrey KT7 ORH, UK<br />

7 This equipment and any acceptable variation thereto is specified in the schedule to this certificate and<br />

the documents therein referred to.<br />

8 Sira Certification Service, notified body number 0518 in accordance with Article 9 of Directive 94/9/EC of 23<br />

March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety<br />

Requirements relating to the design and construction of equipment intended for use in potentially explosive<br />

atmospheres given in Annex II to the Directive.<br />

The examination and test results are recorded in the confidential reports listed in Section 14.2.<br />

Relief Valve - The <strong>Mini</strong><strong>Purge</strong> controller is supplied with an optional overpressure relief valve,whichistobe<br />

fitted to the Ex p protected apparatus to prevent an internal overpressure above the maximum overpressure<br />

rating of the apparatus. There are 14 models of relief valve; the designation of each relief valve refers to its<br />

nominal bore in mm, as follows:<br />

9 Compliance with the Essential Health and Safety Requirements, with the exception of those listed in the<br />

schedule to this certificate, has been assured by compliance with the following documents:<br />

IEC 60079-0:2011 EN 60079-2:2007 EN 61241-4: 2006<br />

RLV3, RLV6, RLV9, RLV12, RLV19, RLV25, RLV26, RLV52, RLV36, RLV75, RLV104, RLV125, RLV150 and<br />

RLV200.<br />

10 If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to special<br />

conditions for safe use specified in the schedule to this certificate.<br />

The outlet of each relief valve is fitted with a spark arrestor, of which there are four optional types:<br />

� Metal foam � Multi-layer stainless steel mesh<br />

� Tortuous path with at least 4 x 90�or 2 x 180� bends � Knitted mesh<br />

11 This EC type-examination certificate relates only to the design and construction of the specified equipment. If<br />

applicable, further requirements of this Directive apply to the manufacture and supply of this equipment.<br />

12 The marking of the equipment shall include the following:<br />

Outlet Orifice - Three types of orifice are used:<br />

� Threaded Orifices e.g. ¼� NPT or 2� BSP with a built in spark arrester. These are selected to maintain a<br />

desired back pressure within the Ex p protected apparatus when used with the Continuous Flow options.<br />

Thedesignationofeachoutletorificeindicatesthenominalinletdiameter. Thedesignationsareas<br />

follows: SA3, SA6, SA9, SA12, SA19, SA25, SA32, SA38 and SA50.<br />

� Plain holes in the Relief Valve disk, sizedaccordingtotheflow rate required.<br />

� Replaceable orifice type SAU**.<br />

Standard versions Low temperature versions<br />

II 2(2) GD II 2(2) GD<br />

Ex [px] IIC T6 Gb Ex [px] dem IIC T3 or T4 Gb<br />

Ex [py] IIC T6 Gb Ex [p] IIIC T200°C or T135°C Db<br />

Ex [p] IIIC T85°C Db (Ta –50°C to +55°C)<br />

(Ta –20°C to +55°C)<br />

High Pressure Sensor for CF Systems (HP code) - If the pressure in the pressurized enclosure<br />

rises above the setting of the High Pressure sensor, the controller resets cutting the power to the<br />

enclosure. On detecting the overpressure an optional facility is available for the generation of an alarm<br />

or indicator. On systems with a High Pressure sensor, the relief valve may be omitted.<br />

II 2(3) GD<br />

Ex [pz Gc ] IIC T6 Gb<br />

Ex [p Dc] IIIC T85°C Db<br />

(Ta –20°C to +55°C)<br />

Standard /ET versions Low temperature /ET versions<br />

High Pressure Sensor for LC Systems (HP code) - If the pressure in the pressurized enclosure<br />

rises above the setting of the High Pressure sensor, the purge gas flow is isolated from the pressurised<br />

enclosure. The valve isolates both the leakage compensation and the purge streams. On detecting the<br />

overpressure, an optional facility isavailableforthegenerationofanalarm or indicator. On systems<br />

with a High Pressure sensor, the relief valve may be omitted.<br />

II 2(2) GD<br />

II 2(2) GD<br />

Ex [px] ia IIC T6 Gb Ex [px] dem ia IIC T3 or T4 Gb<br />

Ex [p] ia IIIC T95°C Db Ex [p] ia IIIC T200°C or T135°C Db<br />

(Ta –20 o Cto+55 o C) (Ta –50°C to +55°C)<br />

Pneumatically Operated Outlet Valve - The pneumatically operated outlet valve is used to<br />

positively open or close the outlet of the purged enclosure by means of a spring return pneumatic<br />

cylinder. Systems fitted with the Pneumatically Operated Outlet Valve will carry the option OV.<br />

Project Number 25983 C Ellaby<br />

Deputy Certification Manager<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

Page 1 of 7<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 2 of 7<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Form 9400 Issue 1<br />

Form 9400 Issue1


CERTIFICATION<br />

CERTIFICATION<br />

SCHEDULE<br />

SCHEDULE<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

Variation 1 This variation introduced the following changes:<br />

i. The purge controller to be fitted inside an additional, heated, stainless steel enclosure that allows<br />

it to be used down to -50 o C.<br />

The heater (500 W maximum) is manufactured by Intertec-Hess GmbH and coded Ex d m IIC T3<br />

(max) under PTB 02ATEX1041X. If the outer enclosure is reduced in size the power of the heater<br />

may be reduced in proportion to the reduction in surface area. Other alternative heaters may be<br />

used as a replacement if they are suitably certified, carry the same or greater ambient<br />

temperature range, occupy the same or smaller physical space, have the same certification code<br />

and have the same or more restrictive Temperature Class.<br />

The enclosure is made from 1.5mm or 2.5 mm thick stainless or mild steel painted and the lid is<br />

made from 1.5 mm thick stainless steel, lined with 38 mm thick insulation, or other materials with<br />

equivalent insulating properties. The purge inlet, purge outlet and pressure sensing lines are<br />

similarly insulated. The door may optionally be hinged with quick release catches, these will be<br />

fitted with a padlock. An enclosure breather tube is fitted to help prevent condensation. A plastic<br />

clear viewing window may optionally be fitted to the door.<br />

RTDs are fitted to the air inlet pipe-work and inside the purge controller enclosure.<br />

An Ex e terminal box is provided within the main enclosure for connection of the heater leads. This<br />

polyester box is manufactured by Bartec and coded Ex e II T6 under BAS 98ATEX3008X. Other<br />

alternative ATEX terminal boxes may be used as a replacement if they are suitably certified, carry<br />

the same or greater ambient temperature range, occupy the same or smaller physical space, have<br />

the same certification code and have the same Temperature Class.<br />

Model Number Designation for ATEX approved <strong>Mini</strong><strong>Purge</strong> systems<br />

a <strong>Size</strong> or Capacity<br />

1 Sub-<strong>Mini</strong><strong>Purge</strong><br />

Model Number:<br />

2 <strong>Mini</strong><strong>Purge</strong><br />

1 X LC cs DS SS AA MO FM OA TW<br />

3 Super-<strong>Mini</strong><strong>Purge</strong><br />

4 Super-<strong>Mini</strong><strong>Purge</strong> 1800<br />

Key:<br />

5 Super-<strong>Mini</strong><strong>Purge</strong> 3500<br />

a b cc mm Example option codes<br />

6 Super-<strong>Mini</strong><strong>Purge</strong> 7000<br />

7 Super-<strong>Mini</strong><strong>Purge</strong> xxxx<br />

b Pressurization Type<br />

X X Pressurization<br />

Y Y Pressurization<br />

Z Z Pressurization<br />

cc Action after initial purging<br />

LC Leakage Compensation only after initial High <strong>Purge</strong><br />

CF Continuous Flow (same flow rate during and after purging)<br />

CF2 Two Flow CF system with initial High <strong>Purge</strong> rate but only one orifice<br />

CFHP Continuous (lower) Flow after initial High <strong>Purge</strong><br />

DP Dust Protection (pressurization only)<br />

mm Material of the Control Unit Enclosure<br />

al Aluminium alloy<br />

cs Mild steel, painted<br />

ss Stainless steel<br />

bp Back Plate only<br />

co Chassis only<br />

pm Panel mounting<br />

nm Non-Metallic<br />

Option codes (Added only if used)<br />

AA Active Alarm output fitted.<br />

AC Alarm cancellation circuit.<br />

AO "Alarm Only" Action on Pressure or Flow Failure.<br />

AS Alarm "Action on Pressure or Flow failure", Selector valve.<br />

CS Containment System Monitor.<br />

DS Door switch Power Interlock fitted.<br />

DT Delayed Trip after Pressure or Flow failure.<br />

DXXX Special design for specific flow rates<br />

ET Electronic Timer<br />

FM Flow Meter(s) fitted.<br />

HP System LC or CF with High Pressure Sensor<br />

IS Internal Switches suitable for Ex i circuits.<br />

MO <strong>Manual</strong> Override fitted.<br />

MT Mechanical Timer.<br />

OA On/Off switch controlling Protective gas and logic supply.<br />

OB On/Off switch controlling logic supply only.<br />

OC On/Off switch controlling Protective gas supply only.<br />

OS Outlet (Orifice) Selector valve.<br />

OV Outlet valve, pneumatically operated.<br />

PA "Ex" switch(es) built-in, with/without "Ex" junction box.<br />

PC PE Pressure Control Leakage Compensation Valve (CLAPS System.)<br />

PO Pneumatic Output signals for Power and Alarm control.<br />

SP Secondary Pressurization supply options.<br />

SS Separate Supply for Protective gas and Logic air.<br />

TW Twin (or more) outputs for two or more separate pressurized enclosures purged in parallel<br />

Any suitably ATEX, Category 2 approved cable glandmaybeused,ifitcanbeusedwiththe<br />

ambient temperature range.<br />

ii. A change of the Applicant’s name on the certificate and the substitution of the new name for the<br />

old name on the approved label affixed to the purge controllers:<br />

Old Name: New name:<br />

<strong>Expo</strong> Telektron Safety System Limited <strong>Expo</strong> <strong>Technologies</strong> Limited<br />

Variation 2 This variation introduced the following change:<br />

i. To permit the pressurisation of enclosures for the exclusion of combustible dusts in accordance<br />

with IEC61241-4:2001 and modification of the marking to include one of the following:<br />

[Ex pD] II T200°C 21 (Ta = -20°C to +55°C) - (used with the low temperature versions)<br />

[Ex pD] II T85°C 21 (Ta = -20°C to +55°C) - (used with the standard temperature versions)<br />

The ATEX coding is modified to: II 2(2) G D<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Sira Certification Service<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 4 of 7<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 3 of 7<br />

Form 9400 Issue1<br />

Form 9400 Issue1


CERTIFICATION<br />

CERTIFICATION<br />

SCHEDULE<br />

SCHEDULE<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

Issue Date Report no. Comment<br />

4 7 June 2007 R51L15966B This Issue covers the following changes:<br />

� All previously issued certification was rationalised<br />

into a single certificate, Issue 4, Issues 0 to 3<br />

referenced above are only intended to reflect the<br />

history of the previous certification and have not<br />

been issued as documents in this format.<br />

� The introduction of Variation 3.<br />

5 18 February 2009 R51L19695A The introduction of Variation 4.<br />

6 22 December 2010 R23665A/00 This Issue covers the following changes:<br />

� This certificate history was modified to recognise<br />

that that Variation 2 was re-issued, subsequent<br />

Variations have therefore been re-numbered.<br />

� The introduction of Variation 5.<br />

7 07 December 2011 R25983A/00 The introduction of Variation 6.<br />

Variation 3 This variation introduced the following changes:<br />

i. Following appropriate re-assessment to demonstrate compliance with the requirements of the EN<br />

60079 series of standards, the documents originally listed in section 9, EN 50014:1997<br />

(amendments A1 to A2) and EN 50016:1995, were replaced by EN 60079-0:2006, EN 60079-1:2004,<br />

EN 61241-0:2006 and EN 61241-1:2006, the markings in section 12 were updated accordingly.<br />

ii. The removal of special conditions for safe use that were not specifically associated with the<br />

equipment covered by this certificate.<br />

Variation 4 - This variation introduced the following changes:<br />

i. To permit the inclusion of the following coding for the Low Temperature <strong>Mini</strong><strong>Purge</strong> Enclosure:<br />

Ex [p] dem IIC T4<br />

Ex pD II 21 T135°C<br />

(Ta –50 o Cto+55 o C)<br />

Variation 5 - This variation introduced the following changes:<br />

15 SPECIAL CONDITIONS FOR SAFE USE (denoted by X after the certificate number)<br />

15.1 When using the AO, AS and DT options, the recommendations for the additional requirements of Ex p<br />

apparatus contained within EN 60079-14 shall be applied.<br />

i. The introduction of the /ET version, an alternative to the pneumatic or mechanical timer system,<br />

this incorporates an Electronic Timer Module ETM-IS**-*** in the <strong>Mini</strong> <strong>Purge</strong>, the certification<br />

includes ‘ia’ marking when the ETM is fitted.<br />

ii. The dust marking was changed to be consistent with the marking for gases and vapours.<br />

iii. The introduction of a high pressure sensor for the LC option.<br />

15.2 The installer/user shall ensure that the <strong>Mini</strong><strong>Purge</strong> Control Unit is installed in accordance with the<br />

equipment certificate that covers the combination of the pressurised enclosure(s) and <strong>Mini</strong><strong>Purge</strong><br />

Control Unit.<br />

Variation 6 - This variation introduced the following changes:<br />

15.3 The values of the safety parameters shall be set in accordance with the equipment certificate that<br />

covers the combination of the pressurised enclosure(s) and <strong>Mini</strong><strong>Purge</strong> Control Unit.<br />

15.4 This <strong>Mini</strong><strong>Purge</strong> Control Unit shall be incorporated into equipment and the appropriate Conformity<br />

Assessment Procedures applied to the combination as defined by Directive 94/9/EC. This certificate<br />

does not cover the combination.<br />

i. Following appropriate re-assessment to demonstrate compliance with the requirements of the<br />

latest EN 60079 series of standards, the documents previously listed in section 9, EN 60079-0:<br />

2006 and EN 60079-2: 2004 were replaced by those currently listed (EN 61241-0: 2006 was<br />

removed as this is incorporated into the current version of 60079-0), the markings in section 12<br />

were updated accordingly and a new condition of certification was added.<br />

14 DESCRIPTIVE DOCUMENTS<br />

15.5 The purge controller, low temperature version, shall be protected by a safety related system that<br />

ensures that it cannot be energised if the temperature of the air inlet or purge controller falls below -<br />

20 o C. This system shall utilise the RTDs that are fitted to the purge controller to provide the<br />

appropriate level of system integrity, i.e. a level of operational safety of Cat 3 according to EN 954-1 for<br />

ATEX Category 2 (Zone 1) applications; note that these RTDs have not been assessed as a safety<br />

related device in accordance with EHSR 1.5 of Directive 94/9/EC.<br />

14.1 Drawings<br />

Refer to Certificate Annexe.<br />

14.2 Associated Sira Reports and Certificate History<br />

16 ESSENTIAL HEALTH AND SAFETY REQUIREMENTS (EHSRs)<br />

The relevant EHSRs that are not addressed by the standards listed in this certificate have been<br />

identified and individually assessed reports listed in Section 14.2.<br />

Issue Date Report no. Comment<br />

0 3 July 2002 R53A7169A The release of prime certificate.<br />

1 29 March 2004 R53V11342A The introduction of Variation 1.<br />

2 30 September 2004 R51A11080A The introduction of Variation 2.<br />

3 19 September 2006 R51A15629A The re-issue of Variation 2 to include the changes<br />

described in report number R51A15629A.<br />

17 CONDITIONS OF CERTIFICATION<br />

17.1 The use of this certificate is subject to the Regulations Applicable to Holders of Sira Certificates.<br />

17.2 Holders of Type Examination Certificates are required to comply with the production control<br />

requirements defined in Article 8 of directive 94/9/EC.<br />

17.3 The switches incorporated in the PA option shall be suitably certified for Category 2.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 6 of 7<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 5 of 7<br />

Form 9400 Issue1<br />

Form 9400 Issue1


Certificate Annexe<br />

Certificate Number: Sira 01ATEX1295X<br />

CERTIFICATION<br />

Equipment: <strong>Purge</strong> Controllers<br />

Sub-<strong>Mini</strong><strong>Purge</strong>, <strong>Mini</strong><strong>Purge</strong>, Super-<strong>Mini</strong><strong>Purge</strong>,<br />

Super-<strong>Mini</strong><strong>Purge</strong> 1800/3500/7000/7000X<br />

CERTIFICATION<br />

Applicant: EXPO <strong>Technologies</strong> Limited<br />

SCHEDULE<br />

Issue 0 (The drawings associated with this issue were replaced by those listed in Issue 4)<br />

EC TYPE-EXAMINATION CERTIFICATE Sira 01ATEX1295X<br />

Issue 7<br />

Number Sheet Rev. Date Description<br />

SD7281 1 to 4 3 02 Jul 02 <strong>Mini</strong><strong>Purge</strong> ATEX Certification Labelling<br />

SD7282 1 to 2 2 21 May 01 <strong>Mini</strong><strong>Purge</strong> ATEX Certification Type Numbering Scheme<br />

EP/99-2-17 1 of 1 1 21 Sep 00 <strong>Mini</strong><strong>Purge</strong>, Continuous Flow with /HP Sensor –Schematic diagram<br />

EP99-7-7 1 of 1 1 21 Sep 00 RLV, outlet orifice<br />

EP99-7-9 1 of 1 1 21 Sep 00 Outlet Valve Control Circuit Diagram<br />

17.4 The following routine tests shall be performed by the manufacturer:<br />

Verification of <strong>Mini</strong>mum Overpressure Cut Off<br />

An overpressure loss shall be simulated whilst the <strong>Mini</strong><strong>Purge</strong> Control Unit is cycling, it shall be verified<br />

that the controller provides the appropriate output and resets.<br />

Issue 1 (The drawings associated with this issue were replaced by those listed in Issue 4)<br />

Verification of <strong>Purge</strong> Failure Protection<br />

Number Sheet Rev. Date Description<br />

SD7448 1 of 1 3 22 March 04 Low Temperature Housing - General Arrangement<br />

A purge failure shall be simulated whilst the <strong>Mini</strong><strong>Purge</strong> Control Unit is cycling, it shall be verified that<br />

the controller provides the appropriate output and resets.<br />

Issue 2 (The drawings associated with this issue were replaced by those listed in Issue 4)<br />

Verification of Air Supply Failure Protection<br />

Number Sheet Rev. Date Description<br />

SD7281* 1 to 5 4 17 Dec 03 Certification label<br />

SD7449 1 of 1 1 18 Dec 03 Low temperature housing wiring certification drawing.<br />

* Modified by Sira 30 September 2004<br />

An air supply failure shall be simulated whilst the <strong>Mini</strong><strong>Purge</strong> Control Unit is cycling, it shall be verified<br />

that the controller provides the appropriate output and resets.<br />

Issue 3 (The drawings associated with this issue were replaced by those listed in Issue 4)<br />

Verification of Purging Overpressure protection<br />

Where the HP is specified an overpressure shall be simulated whilst the <strong>Mini</strong><strong>Purge</strong> Control Unit is<br />

cycling, it shall be verified that the controller provides the appropriate output and resets.<br />

Number Sheet Rev. Date Description<br />

SD7281 1 to 5 5 30 Aug 06 Certification label<br />

Issue 4<br />

Number Sheet Rev. Date Description<br />

EP99-3-1 1 of 1 02 15 Mar 07 <strong>Mini</strong>purge Control Unit – General Assembly<br />

EP99-2-1 1 of 1 03 09 Jul 07 Schematic - Type x Leakage Compensation<br />

EP99-2-3 1 of 1 02 15 Mar 07 Sequence Diagram - Type x Leakage Compensation<br />

EP99-2-2 1 of 1 02 15 Mar 07 Schematic - Type x Continuous Flow<br />

EP99-2-7 1 of 1 02 15 Mar 07 Schematic – Separate Supply and Mechanical Timer<br />

EP99-2-8 1 of 1 02 15 Mar 07 Schematic – Delay Before Trip and On/Off<br />

EP99-2-9 1 of 1 02 15 Mar 07 Schematic – Twin Output and <strong>Manual</strong> Override<br />

EP99-2-10 1 of 1 03 15 Mar 07 Schematic – Pressure Control Leakage Compensation<br />

EP99-2-11 1 of 1 03 15 Mar 07 Internal “IS” Switches<br />

EP99-2-12 1 of 1 02 15 Mar 07 Schematic – Containment System and Secondary pressurisation<br />

EP99-2-14 1 of 1 02 15 Mar 07 Schematic – Continuous Flow with 2 Flow Rates<br />

EP99-2-17 1 of 1 02 15 Mar 07 Schematic – Continuous Flow with High Pressure<br />

EP99-2-16 1 of 1 02 15 Mar 07 Schematic – Outlet Valve Control<br />

SD7533 1 of 1 01 15 Mar 07 Schematic – Dust Protection<br />

SD7535 1 of 1 01 15 Mar 07 Spark Arrestor<br />

SD7536 1 of 1 01 18 Apr 07 Differential Flow Monitor<br />

SD7538 1 of 1 01 27 Mar 07 Continuous Flow Outlet Orifice<br />

SD7449 1 of 1 02 15 Mar 07 Wiring Diagram – Low temperature<br />

SD7500 1 of 1 01 25 Apr 07 Outlet Orifice Closing Device<br />

SD7448 1 of 1 04 15 Mar 07 Low Temperature Housing<br />

SD7281 1 to 2 06 20 Feb 07 Certification Label Details<br />

SD7282 1 to 2 03 20 Feb 07 <strong>Mini</strong><strong>Purge</strong> Data Sheet<br />

17.5 The products covered by this certificate incorporate previously certified devices, it is therefore the<br />

responsibility of the manufacturer to continually monitor the status of the certification associated with<br />

these devices, and the manufacturer shall inform Sira of any modifications of the devices that may<br />

impinge upon the explosion safety design of the products.<br />

17.6 The certification code that is appropriate to <strong>Purge</strong> Controllers low temperature version shall appear in<br />

the product marking applied to outer stainless steel enclosure.<br />

17.7 The <strong>Purge</strong> Controllers: Sub-<strong>Mini</strong><strong>Purge</strong>, <strong>Mini</strong><strong>Purge</strong>, Super-<strong>Mini</strong><strong>Purge</strong>, Super-<strong>Mini</strong><strong>Purge</strong><br />

1800/3500/7000/7000X shall not be marked as suitable for use in explosive dust atmospheres when a<br />

non-metallic or painted housing is used.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 1 of 2<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 7 of 7<br />

Form 9400 Issue 1<br />

Form 9400 Issue1


Certificate Annexe<br />

Certificate Number: Sira 01ATEX1295X<br />

CERTIFICATION<br />

Equipment: <strong>Purge</strong> Controllers<br />

Sub-<strong>Mini</strong><strong>Purge</strong>, <strong>Mini</strong><strong>Purge</strong>, Super-<strong>Mini</strong><strong>Purge</strong>,<br />

Super-<strong>Mini</strong><strong>Purge</strong> 1800/3500/7000/7000X<br />

Applicant: EXPO <strong>Technologies</strong> Limited<br />

Number Sheet Rev. Date Description<br />

SD7537 1 to 3 01 20 Feb 07 Fault Evaluation<br />

EP99-7-9 1 of 2 02 15 Mar 07 Outlet Valve Circuit N/O<br />

EP99-7-9 2 of 2 01 15 Mar 07 Outlet Control Valve N/C<br />

SD7531 1 of 1 02 09 Jul 07 Schematic – Type Z or Y leakage compensation<br />

SD7532 1 of 1 01 15 Mar 07 Schematic Type Z or Y Continuous Flow<br />

EP99-2-4 1 of 1 02 15 Mar 07 Sequence Diagram – Type X Continuous Flow<br />

EP99-2-5 1 of 1 02 15 Mar 07 Schematic – Alarm only and Alarm Action Selector<br />

EP99-2-6 1 of 1 02 15 Mar 07 Schematic – Door Switch Active Alarm and Alarm Cancel<br />

SD7555 1 to 4 01 05 Jul 07 RLV Configurations<br />

SD7556 1 of 2 01 09 Jul 07 Alternative Z&Y LC System<br />

SD7556 2 of 2 01 09 Jul 07 Alternative Z&Y LC System<br />

Issue 5<br />

Number Sheets Rev. Date (Sira stamp) Description<br />

SD7281 1 to 2 7 12 Feb 09 <strong>Mini</strong>purge ATEX/IECEx Certification Label<br />

SD7448 1 of 1 05 12 Feb 09 <strong>Mini</strong>purge Low temperature Housing<br />

Issue 6<br />

Number Sheets Rev. Date (Sira stamp) Description<br />

SD7281 1 to 2 8 23 Dec 10 <strong>Mini</strong>purge ATEX/IECEx Certification Label<br />

SD7282 1 to 2 4 21 Dec 10 <strong>Mini</strong><strong>Purge</strong> Data Sheet<br />

SD7913 1 of 1 2 21 Dec 10 <strong>Mini</strong><strong>Purge</strong> electronic timer<br />

SD7914 1 of 1 2 21 Dec 10 <strong>Mini</strong><strong>Purge</strong> HP sensor<br />

Issue 7<br />

Number Sheets Rev. Date (Sira stamp) Description<br />

SD7448 1 of 1 6 23 Nov 11 <strong>Mini</strong>purge Low Temperature Housing<br />

SD7282 1 & 2 5 23 Nov 11 <strong>Mini</strong>purge Data Sheets<br />

SD7281 1 to 3 9 23 Nov 11 <strong>Mini</strong>purge ATEX/IECEx Certification Label<br />

SD7533 1 of 1 2 23 Nov 11 <strong>Mini</strong>purge Dust Protection Schematic<br />

Sira Certification Service<br />

Rake Lane, Eccleston, Chester, CH4 9JN, England<br />

This certificate and its schedules may only be<br />

reproduced in its entirety and without change.<br />

Tel: +44 (0) 1244 670900<br />

Fax: +44 (0) 1244 681330<br />

Email: info@siracertification.com<br />

Web: www.siracertification.com<br />

Page 2 of 2<br />

Form 9400 Issue 1


®<br />

File E190061 Vol 1 Issued 1999-07-23<br />

Revised 2003-05-08<br />

®<br />

FOLLOW-UP SERVICE PROCEDURE<br />

(TYPE R)<br />

PURGING AND PRESSURIZING CONTROLS AND<br />

ACCESSORIES FOR USE IN HAZARDOUS LOCATIONS<br />

(RFPW,RFPW7)<br />

Manufacturer: EXPO TECHNOLOGIES LIMITED<br />

(466459-001) SUMMER RD<br />

THAMES DITTON<br />

SURREY<br />

KT7 0RH ENGLAND UNITED KINGDOM<br />

Applicant: SAME AS MANUFACTURER<br />

(466459-001)<br />

Classified Company: SAME AS MANUFACTURER<br />

(466459-001)<br />

This Procedure authorizes the above Manufacturer to use the marking specified by<br />

Underwriters Laboratories Inc. only on products covered by this Procedure,<br />

in accordance with the applicable Follow-Up Service Agreement.<br />

333 Pfingsten Road<br />

Northbrook, Illinois 60062-2096<br />

United States Country Code(1)<br />

(847) 272-8800<br />

FAX No. (847) 272-8129<br />

http://www.ul.com<br />

The prescribed Mark or Marking shall be used only at the above manufacturing location<br />

on such products which comply with this Procedure and any other applicable<br />

requirements.<br />

The Procedure contains information for the use of the above named Manufacturer and<br />

representatives of Underwriters Laboratories Inc. and is not to be used for any other<br />

purpose. It is lent to the Manufacturer with the understanding that it is not to<br />

be copied, either wholly or in part, and that it will be returned to Underwriters<br />

Laboratories Inc. upon request.<br />

This PROCEDURE, and any subsequent revisions, is the property of UNDERWRITERS<br />

LABORATORIES INC. and is not transferable.<br />

A<br />

UNDERWRITERS LABORATORIES INC.<br />

A.W. Schaefer<br />

Vice President and General Manager<br />

US and Canadian Operations<br />

A not-for-profit organization<br />

dedicated to public safety and<br />

committed to quality service


<strong>Mini</strong><strong>Purge</strong> Interface Unit MIU/e<br />

User Instruction <strong>Manual</strong><br />

Manufacturer: <strong>Expo</strong> <strong>Technologies</strong> Ltd, Unit 2 The Summit, Sunbury-on-Thames. Uk<br />

Model Type & Rating: MIU/e1 MIU/e2 MIU/e1/MO<br />

400V / 7A 400V / 7A 400 V / 6A<br />

Certificates:<br />

Hazardous Area Marking<br />

Code:<br />

APPLICATION SUITABILITY<br />

The <strong>Mini</strong><strong>Purge</strong> Interface Units – MIU/e are certified for use in Hazardous Areas where the Hazardous Area is nonmining<br />

(i.e. above ground) and the hazard is caused by flammable gasses or vapours.<br />

The systems may be used in ATEX/IECEx Gas Zones 1 & 2, Gas Groups IIA, IIB & IIC and in Dust Zones 21 & 22,<br />

Dust Groups IIIA, IIIB & IIIC.<br />

The following materials are used in the construction of MIU/e: Stainless Steel, Steel, Brass, Copper, Polyamide,<br />

Silicone. If substances that will adversely affect any of these materials are present in the surrounding environment,<br />

please consult <strong>Expo</strong> <strong>Technologies</strong> for further guidance. This equipment is designed for use under normal industrial<br />

conditions of ambient temperature, humidity and vibration. Please consult <strong>Expo</strong> <strong>Technologies</strong> before installing this<br />

equipment in conditions that may cause stresses beyond normal industrial conditions.<br />

WARNING - Only install, commission, inspect, maintain or fault find when safe to do so.<br />

INSTALLATION<br />

The MIU/e shall be installed in accordance with relevant standards, such as EN 60079-14 and any local codes of<br />

practice that are in force. Cable glands or other cable entry devices shall be appropriately certified and suitable for<br />

the cable and the conditions of use and be installed in accordance with the manufacturer’s instructions.<br />

The MIU/e shall be connected to the <strong>Purge</strong> and Pressurization system in accordance with the instructions given in<br />

the handbook supplied with the pressurization system.<br />

The external earth connection of the MIU/e shall be connected to earth using minimum 4mm 2 conductor.<br />

TERMINALS<br />

MIU/e may be fitted with a combination of:<br />

WDU2.5 terminals certified to KEMA 98ATEX1683U & IECEx ULD05.0008U<br />

SAK2.5 terminals certified to KEMA 98ATEX1798U & IECEx KEM06.0014U<br />

WPE2.5 Earth terminals certified to KEMA 98ATEX1683U & IECEx ULD05.0008U<br />

For all type of terminals:<br />

Tightening torque range: 0.4 to 0.8 Nm (WDU & WPE) & 0.4 to 0.6 Nm (SAK)<br />

Conductor cross section maximum 2.5 mm 2 , minimum 1.5 mm 2<br />

Type of connection is screwed - Solid copper conductors to be used.<br />

Stripping length shall be 10 mm.<br />

Only one conductor is allowed at each side of a terminal. Multiple conductors shall be crimped together before<br />

screwed into the terminal.<br />

Maximum number of terminals:<br />

For Model MIU/e1 – Up to 18 current carrying terminals<br />

For Model MIU/e2 – Up to 33 current carrying terminals<br />

For Model MIU/e1/MO – Up to 13 current carrying terminals<br />

IECEx ITS10.0003X ITS 10ATEX37092X TUV 12.1463<br />

Ex e IIC T5 Gb<br />

Ex tb IIIC T100°C Db IP66<br />

Tamb -20°C to +55°C<br />

II 2 G D<br />

Ex e IIC T5 Gb<br />

Ex tb IIIC T100°C Db IP66<br />

Tamb -20°C to +55°C<br />

Ex e IIC T5 Gb<br />

Ex tb IIIC T100º Db IP66<br />

Tamb -20°C to +55°C<br />

COMMISSIONING<br />

The installation of the cable glands, electrical and earth connections shall be inspected for correct installation<br />

before the unit is put into service. The lid shall be correctly fitted.<br />

MAINTENANCE<br />

The condition of enclosure and associated cable glands shall be inspected for damage every six months. The<br />

terminals shall be inspected for tightness and gaskets inspected for damage.<br />

FAULT FINDING<br />

When wiring or signal fault occurs, check each terminated wire, terminals for tightness and gaskets for damage.<br />

External faults such as broken switches within the Control Unit may also require investigation.<br />

<strong>ML</strong>358 v5 Page 1 of 1 06-Nov-12


EC-Declaration of<br />

Conformity<br />

S:\Files\QA\CERTS\C-OF-C\<strong>Mini</strong>purge CE SC004 Issue4.doc<br />

With<br />

European<br />

Directives<br />

<strong>Expo</strong> <strong>Technologies</strong> Ltd<br />

Summer Road<br />

Thames Ditton KT7 0RH UK<br />

<strong>Expo</strong> <strong>Technologies</strong> Ltd<br />

declares that<br />

<strong>Purge</strong> Controllers Type “<strong>Mini</strong><strong>Purge</strong>” certified under<br />

EC Type Examination Certificate SIRA 01ATEX1295X<br />

are manufactured in conformity with the following<br />

European Directives and standards:<br />

Electromagnetic Compatibility Directive 2004/108/EG<br />

<strong>Mini</strong><strong>Purge</strong> Systems with a /PO suffix in the type number are non-electrical and are outside<br />

the scope of the EMC Directive.<br />

<strong>Mini</strong><strong>Purge</strong> Systems with suffices /PA or /IS incorporate one or more volt-free (“dry”)<br />

contacts which work in circuits specified by others. In normal operation these circuits are<br />

“benign” and no CE mark is appropriate.<br />

<strong>Mini</strong><strong>Purge</strong> Systems with Electronic Timer (Option /ET) are designed to conform to the<br />

EMC Directive, in compliance with EN 61000-6-4:2007 and EN 61000-6-2:2005 (Intertek<br />

Report EM10048000).<br />

Low Voltage Directive 2006/95/EC<br />

<strong>Mini</strong><strong>Purge</strong> systems are intended to be used in Hazardous Areas (Explosive Atmospheres)<br />

and are therefore excluded from the Low Voltage Directive.<br />

ATEX Directive 94/9/EC<br />

<strong>Mini</strong><strong>Purge</strong> systems are designed to conform to the ATEX Directive, in compliance with:<br />

EN 60079-0 : 2009 EN 60079-2 : 2007<br />

EN 61241-0 : 2006 EN 61241-4 : 2006<br />

Pressure Equipment Directive 97/23/EC<br />

Signed Date 27/01/2011<br />

Managing Director Confidential Assessment file reference SC004


<strong>Expo</strong> <strong>Technologies</strong> Ltd., Tel + 44 (0) 20 8398 8011<br />

Unit 2, The Summit, Fax + 44 (0) 20 8398 8014<br />

Hanworth Road, E-mail: sales@expoworldwide.com<br />

Sunbury-On-Thames,<br />

TW16 5DB<br />

<strong>Expo</strong> <strong>Technologies</strong> Inc., Tel: +1 888-NFPA-496<br />

9140 Ravenna Road Unit #3, Tel: +1 (440) 247 5314<br />

Twinsburg Fax: +1 (330) 487 0611<br />

OH 44087 E-mail: sales.na@expoworldwide.com<br />

USA<br />

www.expoworldwide.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!