14.2.6.2 <strong>Outdoor</strong> Air Temperature Control<br />

� The maximum current value is regulated when the outdoor air temperature rise above 57.2°F in order to avoid<br />

compressor overloading.<br />

� The compressor will be stopped to avoid compressor overloading.<br />

14.2.6.3 Overload Protection Control<br />

� The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown<br />

below.<br />

� If the heat exchanger temperature exceeds 60°C, compressor will stop.<br />

14.2.6.4 Low Temperature Compressor Oil Return Control<br />

� In heating operation, if the outdoor temperature falls below 14°F when compressor starts, the compressor<br />

frequency will be regulated up to 600 seconds.<br />

14.2.6.5 Cold Draught Prevention Control<br />

� When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced or<br />

stop.<br />

� Horizontal vane angle may be adjusted in Auto vane setting.<br />

14.2.6.6 Deice Operation<br />

� When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor<br />

and outdoor fan motor stop and operation LED blinks. Horizontal vane is closed during auto vane setting.<br />