16.4.18 F11 (<strong>Indoor</strong> Pipe Temperature Sensor Abnormality)<br />
Malfunction Decision Conditions<br />
� When cooling operation, when indoor pipe temperature or indoor heat exchanger temperature sensor is above<br />
113°F.<br />
Malfunction Caused<br />
� Faulty connector connection.<br />
� Faulty indoor pipe temperature sensor.<br />
� Faulty indoor main PCB.<br />
Troubleshooting<br />
65