25.02.2013 Views

technical data

technical data

technical data

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

����������������������������������<br />

��������������������������������������<br />

1.Technical background<br />

When installing VRV outdoor units collectively on the rooftop, the suction temperature increases due to the heat emanated from other outdoor units (air short circuit).<br />

As a result, in cooling system, the COP is lowered because of decreased equipment capacity and increased power consumption. In some cases, outdoor units stop<br />

operations due to abnormally high pressure. When installing these units, choose the most suitable layout for on-site space conditions from the installation options below,<br />

while taking walkway space and ventilation into consideration.<br />

* For other installation patterns, determine the appropriate installation method based on the space conditions, referring to the installation examples below.<br />

For the space in front of the units, please ensure there is enough space for refrigerant piping work. The required installation space shown in the illustrations is based on the<br />

cooling operation at 35°C of outside temperature. When the design outside temperature exceeds 35°C, make the inlet space larger than spaces shown in the illustrations.<br />

2. Installation examples (up to 24 units)<br />

Here shows basic collective installation examples of 16 HP units when 1600mm-high walls surround outdoor units, which is as high as outdoor units. Please be sure that<br />

the distances from each wall and between outdoor units are larger than the figures shown in illustration diagrams.<br />

���������������������������<br />

Determination of the Installation Location<br />

SELECTION OF LOCATION<br />

This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.<br />

If installed as a household appliance it could cause electromagnetic interference.<br />

The VRV outdoor units should be installed in a location that meets the following requirements:<br />

1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.<br />

2. The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available.<br />

(Refer to below figure and choose one of both possibilities.)<br />

3. There is no danger of fire due to leakage of inflammable gas.<br />

4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in case of a blocked drain pipe).<br />

5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length. (See “Example of connection”.)<br />

6. Select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturb anyone.<br />

7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction.<br />

Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.<br />

����������<br />

�������������������������<br />

��������<br />

���<br />

�������<br />

���<br />

���� ���<br />

���<br />

������<br />

���������<br />

�������<br />

�������<br />

�������<br />

�������<br />

��<br />

��<br />

�����������������������������������<br />

���<br />

��� ���<br />

��<br />

�������<br />

�������<br />

�������������������<br />

����������������������������������� ����������������������������<br />

9 Outdoor Unit Layout Guide<br />

���<br />

���<br />

��� ����<br />

��<br />

�������<br />

�������<br />

��<br />

���� ����<br />

����<br />

�������<br />

�������<br />

Fresh air<br />

Fresh air

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!