Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Technical Documentation Pressure Independent Characterized ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Belimo Project: 1100 Peachtree, Atlanta, Georgia<br />
<strong>Technical</strong> <strong>Documentation</strong><br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves <br />
(PICCV) Patented<br />
Effective December 2007
Control Valve Product Range<br />
2<br />
Electronic <strong>Pressure</strong> <strong>Independent</strong><br />
<strong>Characterized</strong> Control Valves <br />
U.S. Patent<br />
PICCV Two-way<br />
1/2” to 2”<br />
PICCV<br />
Service: Chilled/Hot Water,<br />
60% glycol<br />
Flow Rate: 0.5-100 GPM<br />
Material: Brass Body<br />
Brass/Stainless Trim<br />
Control: Floating<br />
Multi-Function Technology ®<br />
Spring Return or<br />
Non-Spring Return<br />
Typical Application<br />
Air Handling Units: – Heating Coils<br />
– Cooling Coils<br />
Unit Ventilators<br />
VAV Box Re-heat Coils<br />
Heat Pumps<br />
Electronic<br />
<strong>Characterized</strong> Control Valves <br />
U.S. Patent<br />
CCV<br />
B2… Series Two-way<br />
B3… Series Three-way<br />
Mixing/Diverting<br />
B6… Series Two-way Flanged<br />
1/2” to 3”<br />
Service: Chilled/Hot Water,<br />
60% glycol<br />
Cv Range: 0.3-240<br />
Material: Stainless Trim or<br />
Brass Trim<br />
Control: On/Off, Floating, 2-10 VDC<br />
Multi-Function Technology ®<br />
Spring Return or<br />
Non-Spring Return<br />
Typical Application<br />
Air Handling Units: – Heating Coils<br />
– Cooling Coils<br />
Fan Coil Units: – Heating Coils<br />
– Cooling Coils<br />
Unit Ventilators<br />
VAV Box Re-heat Coils<br />
Bypass Loops<br />
Electronic Zone Valves<br />
ZONE2…N Series Two-way NPT<br />
ZONE2…S Series Two-way Sweat<br />
ZONE3…N Series Three-way<br />
Diverting NPT<br />
ZONE3…S Series Three-way<br />
Diverting Sweat<br />
1/2” to 1”<br />
Service: Chilled/Hot Water,<br />
50% glycol<br />
C v Range: 1.0 - 8.0<br />
Material: Brass Body<br />
Control: On/Off<br />
Spring Return<br />
Typical Application<br />
Fan Coil Units: – Heating Coils<br />
– Cooling Coils<br />
Baseboard Radiation<br />
For detailed information and submittal data, see <strong>Technical</strong> <strong>Documentation</strong> at www.belimo.com or on CD-ROM.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Electronic Globe Valves<br />
G2…(S) Two-way Screwed<br />
Series Bronze or Stainless Trim<br />
G6…C (S) Two-way Flanged ANSI 125<br />
Series Bronze or Stainless Trim<br />
G6…(S) Two-way Flanged ANSI 125<br />
Series Bronze or Stainless Trim<br />
G6…(S)-250 Two-way Flanged ANSI 250<br />
Series Bronze or Stainless Trim<br />
G3…(D) Three-way Screwed<br />
Series Bronze Trim<br />
G7…D (S) Three-way Flanged<br />
Series ANSI 125 Bronze or<br />
Stainless Trim<br />
G7…D (S)-250 Three-way Flanged<br />
Series ANSI 250 Bronze or<br />
Stainless Trim<br />
Three-way Valves available in Mixing or Diverting<br />
1/2” to 6”<br />
Service: Chilled/Hot Water,<br />
60% Glycol, Steam<br />
Cv Range: 0.4-344 (Two-way)<br />
2.2-340 (Three-way Mix.)<br />
4.4-248 (Three-way Div.)<br />
Material: Stainless Steel Stem,<br />
Bronze Trim or<br />
Stainless Trim<br />
Control: On/Off, Floating, 2-10 VDC<br />
Multi-Function Technology ®<br />
Spring Return or<br />
Non-Spring Return<br />
Typical Application<br />
Air Handling Units: – Heating Coils<br />
– Cooling Coils<br />
Fan Coil Units: – Heating Coils<br />
– Cooling Coils<br />
Unit Ventilators<br />
VAV Box Re-heat Coils<br />
Bypass Loops<br />
Electronic Butterfly Valves<br />
F6… Series Two-way<br />
(HS,HSU)<br />
F7… Series Three-way<br />
(HS,HSU) Mixing/Diverting<br />
F6… SHP Two-way ANSI 150/300<br />
Series<br />
F7… SHP Three-way ANSI 150/300<br />
Series Mixing/Diverting<br />
Typical Application<br />
Chiller and Cooling Tower Isolation<br />
Change-over Systems<br />
Large Air Handler Coil Control<br />
Bypass Control Applications<br />
Control Valve Product Range<br />
B2… Two-way Screwed<br />
VS Series Stainless Steel Trim<br />
B3… Three-way Mixing/<br />
VS Series Diverting Screwed<br />
Stainless Steel Trim<br />
B2… Two-way Screwed<br />
VSS Series Stainless Steel Body<br />
and Trim<br />
B6… Two-way Flanged<br />
VS Series Stainless Steel Trim<br />
2” to 30” 1/2” to 10”<br />
Service: Chilled/Hot Water,<br />
50% Glycol<br />
Cv Range: 115-73,426<br />
Material: Stainless Shaft<br />
Stainless Disc<br />
Cast Iron, Full Lug Body<br />
EPDM Liner<br />
Control: On/Off, Floating,<br />
2-10 VDC<br />
On/Off, Floating<br />
2-10 VDC,<br />
1-5 VDC, 4-20mA<br />
(NEMA 4 Actuator)<br />
Multi-Function Technology ®<br />
Spring Return or<br />
Non-Spring Return<br />
For detailed information and submittal data, see <strong>Technical</strong> <strong>Documentation</strong><br />
at www.belimo.com or on CD-ROM.<br />
Electronic Ball Valves – VS Series<br />
Service: Chilled/Hot Water,<br />
50% Glycol, Steam<br />
Cv Range: 1 to 12,400<br />
Material: Bronze or Stainless Body<br />
Stainless Steel Trim<br />
RPTFE Seats<br />
Control: On/Off, Floating,<br />
2-10 VDC<br />
On/Off, Floating<br />
2-10 VDC,<br />
1-5 VDC, 4-20mA<br />
(NEMA 4 Actuator)<br />
Multi-Function Technology ®<br />
Spring Return or<br />
Non-Spring Return<br />
Typical Application<br />
Unit Ventilators<br />
Humidifiers<br />
Heating and Cooling Coils<br />
Call Customer Service to discuss<br />
your application.<br />
3
Valve/Actuator Selection At A Glance<br />
Base product nomenclature<br />
PICCV-15-003-PT + LRX24-MFT<br />
4<br />
VALVE ACTUATOR<br />
PICCV 15-003 –PT LRX24 - MFT<br />
VALVE SIZES<br />
Valve Designation Sizes<br />
PICCV 15 1/2”<br />
TYPE OF VALVE<br />
20 3/4”<br />
25 1”<br />
32 1-1/4”<br />
40 1-1/2”<br />
50 2”<br />
PRESSURE INDEPENDENT<br />
CHARACTERIZED CONTROL<br />
VALVE (PICCV)<br />
PICCV 2-way Chrome Plated<br />
Brass Ball & Brass Stem<br />
GPM Ex:<br />
003 = 3.0 GPM<br />
Description<br />
Non-Spring<br />
Return Actuator<br />
Spring<br />
Return Actuator<br />
–PT with P/T ports to measure<br />
delta P to verify the flow rate<br />
without P/T ports<br />
LR…<br />
AR…<br />
TF<br />
LF…<br />
AF…<br />
24 VAC/DC<br />
Power*<br />
Rotary<br />
Rotary<br />
DESIGNATOR DESCRIPTION<br />
–MFT Multi-Function<br />
Technology ® (MFT)<br />
2 – 10 VDC Control<br />
or Selectable<br />
(See MFT chart<br />
opposite)<br />
-3 Floating control<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Specify upon ordering<br />
P-10019+NO+AHU<br />
ORDERING EXAMPLE<br />
Valve/Actuator Selection At A Glance<br />
MFT CONFIGURATION SET-UP TAGGING<br />
1<br />
2<br />
P-10019 NO AHU<br />
Choose the desired valve/actuator combination<br />
based on valve ratings and actuator control<br />
parameters from the following pages. PICCV-15-003-PT + LRX24-MFT ●<br />
Specify Configuration (important)<br />
SET UP*<br />
Non-Spring Models<br />
NO = Normally Open<br />
NC = Normally Closed<br />
Spring Return Models<br />
NO/FO = Normally Open/Fail Open<br />
NO/FC = Normally Open/Fail Closed<br />
NC/FO = Normally Closed/Fail Open<br />
NC/FC = Normally Closed/Fail Closed<br />
*Refers to valve port inlet to outlet,<br />
per flow arrow designation<br />
Valve set up required<br />
prior to ordering.<br />
TAGGING<br />
Valves may be tagged per<br />
customer specification<br />
Example:<br />
AHU<br />
FCU-2<br />
Multi-Function Technology<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-10118 2-6 VDC 100 2-10 VDC No Charge<br />
P-10119 6-10 VDC 100 2-10 VDC No Charge<br />
P-10137 2-5 VDC 100 2-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
• Multi-Function Technology: P-10019 (2-10 VDC input / 2-10 VDC feedback) ●<br />
• Set-up: NO (Normally Open) ●<br />
• Tagging: AHU ●<br />
PICCV-15-003-PT+LRX24-MFT+P-10019+NO+AHU Total List Price ●<br />
5
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />
Features and Benefits<br />
6<br />
● Characterizing disc –<br />
made of Tefzel ®<br />
known<br />
for excellent strength<br />
and chemical resistance<br />
● Thermal isolating adapter<br />
between flange and actuator<br />
● Easy direct coupling<br />
of actuator with a<br />
single screw<br />
● Forged brass valve<br />
body – no pin-hole<br />
leaks<br />
Disadvantages of Today’s Systems<br />
● Regulator<br />
Assembly<br />
● Time consuming balancing effort<br />
● Rebalancing required when adding to system or remodeling<br />
● Poor valve authority at average or low load<br />
● Balancing procedure dictates quality<br />
● Potential spreading of control problems can occur when one<br />
or more loops are instable, due to interactive nature of circuits<br />
● Low ∆T reduces efficiency of chillers, condensing boilers, or<br />
coils<br />
● Starving of terminals in less favored spaces results in long<br />
start-up time<br />
Features<br />
● Automatic dynamic system balancing<br />
● Field adjustable flow rate<br />
● 5 – 50 PSI differential pressure operating range (gradual<br />
flow will increase from 0-5 PSI)<br />
● 0.5 – 100 GPM (1/2” – 2”)<br />
● 5 year warranty<br />
*Teflon ® is a registered product of Dupont<br />
● Vent holes reduce<br />
condensation build-up<br />
● Non-corroding<br />
chrome-plated brass<br />
Advantages of the PICCV<br />
● Actuator can be mounted in four<br />
different positions<br />
● Perpendicular mounting flange<br />
and square drive head eliminate<br />
lateral forces on the stem<br />
● Blow-out proof stem with<br />
thrust-bearing Teflon ® disc and<br />
double O-ring design for long<br />
service life*<br />
● Teflon ® seats with O-rings<br />
provide constant seating<br />
force against the ball and<br />
reduce torque requirement*<br />
● Easy selection, no Cv calculation required<br />
● Hydronic balancing is simplified, as the circuits are not<br />
interactive<br />
● Flexible commissioning<br />
● One piece installation saves 50% of labor costs, installation<br />
space, and investment for for balancing valve<br />
● Reduces pumping costs<br />
● Maintains ∆T for higher efficiency of chillers and condensing<br />
boilers<br />
● Visualizes flow in a BMS system and provides accurate<br />
flow for each degree of opening<br />
● Prevents overflow or underflow for fast start-up<br />
Options<br />
Patented<br />
● P/T ports for flow or temperature measurement<br />
● Belimo PC-Tool for commissioning<br />
● Customized Flows<br />
● Certified Factory Calibrated Flows<br />
● Weather shields<br />
● Auxiliary switches<br />
● Metric threads<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
The Best Way to Control Flow<br />
Maintain design flow independent of<br />
pressure variations<br />
The PICCV is a two-way valve that will<br />
supply a specific flow for each degree<br />
of ball opening regardless of pressure<br />
variations in a system.<br />
Flow accuracy ≤ ± 5% (5 to 50 PSI)<br />
(absolute)<br />
Variation due to ≤ ± 5% (5 to 50 PSI)<br />
manufacturing<br />
tolerances<br />
Hysteresis ≤ 1%<br />
(absolute)<br />
Operation<br />
PICCV consists of a differential pressure<br />
regulator in series with a control valve.<br />
The amount of flow that passes through the<br />
valve is controlled by the use of a pressure<br />
regulator that moves according to the<br />
change in pressure above and below it.<br />
All pressure changes are absorbed by<br />
the pressure regulator allowing the<br />
differential pressure to be held constant<br />
over the control valve section thereby<br />
giving the same flow.<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve TM (PICCV)<br />
Flow Rate (GPM)<br />
14<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
Water<br />
enters<br />
valve –<br />
pressure<br />
is P1 (high)<br />
Water passes<br />
through regulator,<br />
disc, and ball –<br />
pressure drops<br />
PICCV Performance<br />
Operating Differential Range of 5 – 50 PSI<br />
0 5 10 15 20 25 30 35 40 45 50<br />
Differential <strong>Pressure</strong> PSI<br />
Regulator<br />
Section<br />
Control Valve<br />
Section<br />
Low pressure pulls regulator<br />
down against the spring force<br />
hence reducing the regulator<br />
opening, reducing the flow.<br />
100%<br />
90%<br />
80%<br />
70%<br />
60%<br />
50%<br />
40%<br />
Water exits<br />
valve –<br />
pressure<br />
is P2 (low)<br />
Ports sense pressure drop<br />
and transfer it through this<br />
channel below regulator<br />
% Ball Opening<br />
7
P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />
with MFT, Non-Spring Return Actuator<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />
Differential <strong>Pressure</strong><br />
Across Valve Range (ΔP): 5 to 50 psid<br />
Maximum Flow Setting:<br />
Manual Field Adjustable – LRB24-3 Actuators<br />
PC Tool Field Adjustable – MFT Actuators<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />
Valve Non-Spring Return Actuator<br />
Model Valve Floating Proportional/MFT<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off<br />
Valve GPM sec Inches mm psi LRB24-3† LRX24-MFT<br />
PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
Electrical 3 ft cable 3 ft cable<br />
Connection 1/2” conduit fitting 1/2” conduit fitting<br />
When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 14).<br />
† Note: FlowSetR only available on (-3) actuator.<br />
Refer to page 53 for customized flows and certified factory calibration flows.<br />
Options (add to list price) LRB24-3-S<br />
Built-in aux. switch (-S) ❑ Pg 12<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
8<br />
LRB24-3<br />
LRX24-MFT<br />
LRB…<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />
Differential <strong>Pressure</strong><br />
Across Valve Range (ΔP): 5 to 50 psid<br />
Maximum Flow Setting:<br />
PC Tool Field Adjustable – MFT Actuators<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />
Valve Spring Return Actuator<br />
Model Valve Proportional/MFT<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off<br />
Valve GPM sec Inches mm psi TF24-MFT US LF24-MFT US<br />
PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 19<br />
PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 19<br />
PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 19<br />
PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 19<br />
PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 19<br />
Electrical 3 ft cable 3 ft cable<br />
Connection 1/2” conduit fitting 1/2” conduit fitting<br />
When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 18).<br />
Refer to page 53 for customized flows and certified factory calibration flows.<br />
Options (add to list price) LF24-MFT-S US<br />
Built-in aux. switch (-S) ❑ Pg 19<br />
P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with MFT, Spring Return Actuator<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends<br />
TF24-MFT US<br />
TF…<br />
LF24-MFT US<br />
LF…<br />
9
P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />
with MFT, Non-Spring Return Actuator<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T ports, NPT Female Ends<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />
Differential <strong>Pressure</strong><br />
Across Valve Range (∆P): 5 to 50 psid<br />
Maximum Flow Setting:<br />
Manual Field Adjustable – LRB24-3 Actuators<br />
PC Tool Field Adjustable – MFT Actuators<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T ports<br />
Valve Non-Spring Return Actuator<br />
Model Valve Floating Proportional/MFT<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off LRB24-3 † LRX24-MFT<br />
Valve GPM sec Inches mm psi ARX24-MFT<br />
PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />
PICCV-32-018-PT 18 1.14 1-1/4” 32 200 ❑ Pg 23<br />
PICCV-32-020-PT 20 1.26 1-1/4” 32 200 ❑ Pg 23<br />
PICCV-32-022-PT 22 1.39 1-1/4” 32 200 ❑ Pg 23<br />
PICCV-32-024-PT 24 1.51 1-1/4” 32 200 ❑ Pg 23<br />
PICCV-32-026-PT 26 1.64 1-1/4” 32 200 ❑ Pg 23<br />
PICCV-40-026-PT 26 1.64 1-1/2” 40 200 ❑ Pg 23<br />
PICCV-40-028-PT 28 1.77 1-1/2” 40 200 ❑ Pg 23<br />
PICCV-40-030-PT 30 1.89 1-1/2” 40 200 ❑ Pg 23<br />
PICCV-40-033-PT 33 2.08 1-1/2” 40 200 ❑ Pg 23<br />
PICCV-50-033-PT 33 2.08 2” 50 200 ❑ Pg 23<br />
PICCV-50-036-PT 36 2.27 2” 50 200 ❑ Pg 23<br />
PICCV-50-040-PT 40 2.52 2” 50 200 ❑ Pg 23<br />
PICCV-50-044-PT 44 2.78 2” 50 200 ❑ Pg 31<br />
PICCV-50-048-PT 48 3.03 2” 50 200 ❑ Pg 31<br />
PICCV-50-052-PT 52 3.28 2” 50 200 ❑ Pg 31<br />
PICCV-50-056-PT 56 3.53 2” 50 200 ❑ Pg 31<br />
PICCV-50-060-PT 60 3.79 2” 50 200 ❑ Pg 31<br />
PICCV-50-065-PT 65 4.10 2” 50 200 ❑ Pg 31<br />
PICCV-50-070-PT 70 4.42 2” 50 200 ❑ Pg 31<br />
PICCV-50-075-PT 75 4.73 2” 50 200 ❑ Pg 31<br />
PICCV-50-080-PT 80 5.05 2” 50 200 ❑ Pg 31<br />
PICCV-50-090-PT 90 5.68 2” 50 200 ❑ Pg 31<br />
PICCV-50-100-PT 100 6.31 2” 50 200 ❑ Pg 31<br />
Electrical 3 ft cable 3 ft cable<br />
Connection 1/2” conduit fitting 1/2” conduit fitting<br />
When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 14).<br />
† Note: FlowSetR only available on (-3) actuator.<br />
Refer to page 53 for customized flows and certified factory calibration flows.<br />
Options (add to list price) LRB24-3-S<br />
Built-in aux. switch (-S) ❑ Pg 12<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
10<br />
LRB24-3<br />
ARX24-MFT LRX24-MFT<br />
®<br />
ARX…<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® P2<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range:<br />
Differential <strong>Pressure</strong><br />
-22°F to 122°F [-30°C to 50°C]<br />
Across Valve Range (∆P):<br />
Maximum Flow Setting:<br />
5 to 50 psid<br />
PC Tool Field Adjustable – MFT Actuators<br />
Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />
with MFT, Spring Return Actuator<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T ports, NPT Female Ends<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T ports<br />
Valve Spring Return Actuator<br />
Model Valve Proportional/MFT<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off TF24-MFT US LF24-MFT US<br />
Valve GPM sec Inches mm psi AF24-MFT US<br />
PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />
PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 19<br />
PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 19<br />
PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 19<br />
PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 19<br />
PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 19<br />
PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 19<br />
PICCV-32-018-PT 18 1.14 1-1/4” 32 200 ❑ Pg 27<br />
PICCV-32-020-PT 20 1.26 1-1/4” 32 200 ❑ Pg 27<br />
PICCV-32-022-PT 22 1.39 1-1/4” 32 200 ❑ Pg 27<br />
PICCV-32-024-PT 24 1.51 1-1/4” 32 200 ❑ Pg 27<br />
PICCV-32-026-PT 26 1.64 1-1/4” 32 200 ❑ Pg 27<br />
PICCV-40-026-PT 26 1.64 1-1/2” 40 200 ❑ Pg 27<br />
PICCV-40-028-PT 28 1.77 1-1/2” 40 200 ❑ Pg 27<br />
PICCV-40-030-PT 30 1.89 1-1/2” 40 200 ❑ Pg 27<br />
PICCV-40-033-PT 33 2.08 1-1/2” 40 200 ❑ Pg 27<br />
PICCV-50-033-PT 33 2.08 2” 50 200 ❑ Pg 27<br />
PICCV-50-036-PT 36 2.27 2” 50 200 ❑ Pg 27<br />
PICCV-50-040-PT 40 2.52 2” 50 200 ❑ Pg 27<br />
PICCV-50-044-PT 44 2.78 2” 50 200 ❑ Pg 33<br />
PICCV-50-048-PT 48 3.03 2” 50 200 ❑ Pg 33<br />
PICCV-50-052-PT 52 3.28 2” 50 200 ❑ Pg 33<br />
PICCV-50-056-PT 56 3.53 2” 50 200 ❑ Pg 33<br />
PICCV-50-060-PT 60 3.79 2” 50 200 ❑ Pg 33<br />
PICCV-50-065-PT 65 4.10 2” 50 200 ❑ Pg 33<br />
PICCV-50-070-PT 70 4.42 2” 50 200 ❑ Pg 33<br />
PICCV-50-075-PT 75 4.73 2” 50 200 ❑ Pg 33<br />
PICCV-50-080-PT 80 5.05 2” 50 200 ❑ Pg 33<br />
PICCV-50-090-PT 90 5.68 2” 50 200 ❑ Pg 33<br />
PICCV-50-100-PT 100 6.31 2” 50 200 ❑ Pg 33<br />
Electrical 3 ft cable 3 ft cable<br />
Connection 1/2” conduit fitting 1/2” conduit fitting<br />
When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 18).<br />
Refer to page 53 for customized flows and certified factory calibration flows.<br />
Options (add to list price) LF24-MFT-S US AF24-MFT-S US<br />
Built-in aux. switch (-S) ❑ Pg 19 ❑ Pg 27 & 33<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
TF24-MFT US<br />
LF24-MFT US<br />
AF24-MFT US<br />
AF…<br />
11
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with Floating, Non-Spring Return Actuator, P/T Ports (Optional)<br />
Valve Specifications<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1/2”, 3/4”, 1”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-P/T)<br />
Body pressure rating 600 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />
1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />
3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />
5 GPM [.32 l/s]<br />
Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />
8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />
10 GPM [0.63 l/s]<br />
Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />
16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
operating range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 1/2” = 2.52 lbs<br />
3/4” = 3.05 lbs<br />
1” = 4.98 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
12<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
Actuator Specifications<br />
❏ LRB24-3… on/off-floating<br />
Power Supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power Consumption 1.5 W (0.2 W)<br />
Transformer Sizing 3 VA (Class 2 power source)<br />
Electrical Connection 3 ft, 18 GA plenum rated cable<br />
3 ft, 18 GA appliance rated cable (-S)<br />
1/2” conduit connector<br />
Overload Protection electronic throughout 0 to 95° rotation<br />
Control on/off, floating point<br />
Input Impedance 600Ω<br />
Direction of Rotation reversible with switch<br />
Position Indication handle<br />
Manual Override external push button and handle<br />
Running Time 95 seconds, constant independent of load<br />
Humidity 5 to 95% RH non condensing<br />
(EN 60730-1)<br />
Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />
Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />
Housing NEMA 2/IP54<br />
Housing Material UL94-5VA<br />
Agency Listings cULus acc. to UL60730-1A/-2-14,<br />
CAN/CSA E60730-1, CSA C22.2<br />
No. 24-93, CE acc. to 89/336/EEC and<br />
(-S Models) 2006/95/EC†<br />
Noise Level
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Valve Specifications<br />
®<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1/2”, 3/4”, 1”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-P/T)<br />
Body pressure rating 600 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />
1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />
3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />
5 GPM [.32 l/s]<br />
Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />
8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />
10 GPM [0.63 l/s]<br />
Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />
16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
operating range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 1/2” = 2.52 lbs<br />
3/4” = 3.05 lbs<br />
1” = 4.98 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ LRX24-MFT<br />
Power Supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power Consumption 2 W (1.2 W)<br />
Transformer Sizing 3.5 VA (Class 2 power source)<br />
Electrical Connection 18 GA plenum rated cable<br />
1/2” conduit connector<br />
❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />
Overload Protection electronic throughout 0 to 95° rotation<br />
Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />
Variable (VDC, PWM, Floating Point,<br />
On/Off)<br />
Input Impedance 100kΩ (0.1 mA), 500Ω<br />
1500Ω (PWM, Floating Point, On/Off)<br />
Feedback Output U 2 to 10 Vdc, 0.5mA max<br />
VDC Variable<br />
Torque 45 in-lb [5 Nm]<br />
Direction of Rotation reversible with switch<br />
Position Indication reflective visual indicator (snap-on)<br />
Manual Override external push button<br />
Running Time Motor* 100 sec constant<br />
Humidity 5 to 95% RH non condensing<br />
(EN 60730-1)<br />
Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />
Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />
Housing NEMA 2/IP54<br />
Housing Material UL94-5VA<br />
Agency Listings cULus acc. to UL60730-1A/-2-14,<br />
CAN/CSA E60730-1, CSA C22.2<br />
No. 24-93, CE acc. to 89/336/EEC†<br />
Noise Level
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />
1/2”, 0.5 – 5 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />
GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />
1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />
table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 2 GPM flow rate.<br />
Solution: Order the PICCV-15-002<br />
Example 2: The application requires a 3.5 GPM flow rate.<br />
Solution: Order the PICCV-15-005 and re-program to the<br />
below setting for 3.5 GPM. As a standard, the<br />
PICCV is available in flows of 4 GPM and 3 GPM.<br />
If you desire 3.5 GPM and have a Normally<br />
Closed (NC) valve, simply reprogram the maximum<br />
setting to 71%, and minimum setting<br />
of 0% as indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 74% 0% NEW<br />
PICCV-15-001(-PT) + LRX24-MFT ♦ 1 0.06 94% 0% NEW<br />
PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 48% 0%<br />
PICCV-15-001(-PT) + LRX24-MFT †♦ 1 0.06 73% 0%<br />
PICCV-15-1.50(-PT) + LRX24-MFT 1.5 0.09 57% 0%<br />
PICCV-15-002(-PT) + LRX24-MFT 2 0.13 64% 0%<br />
2.5 0.16 66% 0%<br />
PICCV-15-003(-PT) + LRX24-MFT 3 0.19 69% 0%<br />
3.5 0.22 71% 0%<br />
PICCV-15-004(-PT) + LRX24-MFT 4 0.25 76% 0%<br />
4.5 0.28 79% 0%<br />
PICCV-15-005(-PT) + LRX24-MFT 5 0.32 82% 0%<br />
5.5 0.35 87% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 100% 33% NEW<br />
PICCV-15-001(-PT) + LRX24-MFT ♦ 1 0.06 100% 12% NEW<br />
PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 100% 55%<br />
PICCV-15-001(-PT) + LRX24-MFT †♦ 1 0.06 100% 37%<br />
PICCV-15-1.50(-PT) + LRX24-MFT 1.5 0.09 100% 43%<br />
PICCV-15-002(-PT) + LRX24-MFT 2 0.13 100% 40%<br />
2.5 0.16 100% 37%<br />
PICCV-15-003(-PT) + LRX24-MFT 3 0.19 100% 35%<br />
3.5 0.22 100% 32%<br />
PICCV-15-004(-PT) + LRX24-MFT 4 0.25 100% 28%<br />
4.5 0.28 100% 25%<br />
PICCV-15-005(-PT) + LRX24-MFT 5 0.32 100% 20%<br />
5.5 0.35 100% 18%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
† Note: 1/2” valve has 2 disc sizes (.5 to 1 GPM) (1.5 to 5.5 GPM)<br />
♦ For replacement or re-programming, please contact <strong>Technical</strong> Support 800-543-9038.<br />
Multi-Function<br />
Technology<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
14<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 3 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-15-003 + LRX24-MFT + P-10019.<br />
Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />
valve bodies to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered Multi-<br />
Function Technology®. The PICCV-15-001 offers nominal flow<br />
rates that are adjustable from 0.5 to 1.0 GPM. The PICCV-15-005<br />
offers nominal flow rates that are adjustable from 1.5 to 5.5 GPM<br />
range. Please follow MFT guideline settings when configuring the<br />
PICCV MFT actuators in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® <strong>Pressure</strong><br />
Selecting the Proper Flow Rate:<br />
The PICCV-20-010 (-PT) can be ordered in 6 GPM to 10 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 6 GPM flow rate.<br />
Solution: Order the PICCV-20-006<br />
Example 2: The application requires a 8.5 GPM flow rate.<br />
Solution: Order the PICCV-20-010 and re-program to the<br />
below setting for 8.5 GPM. As a standard, the<br />
PICCV is available in flows of 8 GPM and 9 GPM.<br />
If you desire 8.5 GPM and have a Normally Closed<br />
(NC) valve, simply reprogram the maximum setting<br />
to 82%, and minimum setting of 0% as indicated<br />
on the chart below.<br />
<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
3/4”, 6 – 10 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LRX24-MFT 6 0.38 74% 0%<br />
6.5 0.41 75% 0%<br />
PICCV-20-007(-PT) + LRX24-MFT 7 0.44 77% 0%<br />
7.5 0.47 79% 0%<br />
PICCV-20-008(-PT) + LRX24-MFT 8 0.50 80% 0%<br />
8.5 0.54 82% 0%<br />
PICCV-20-009(-PT) + LRX24-MFT 9 0.57 83% 0%<br />
9.5 0.60 85% 0%<br />
PICCV-20-010(-PT) + LRX24-MFT 10 0.63 90% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LRX24-MFT 6 0.38 100% 31%<br />
6.5 0.41 100% 28%<br />
PICCV-20-007(-PT) + LRX24-MFT 7 0.44 100% 27%<br />
7.5 0.47 100% 25%<br />
PICCV-20-008(-PT) + LRX24-MFT 8 0.50 100% 24%<br />
8.5 0.54 100% 22%<br />
PICCV-20-009(-PT) + LRX24-MFT 9 0.57 100% 19%<br />
9.5 0.60 100% 18%<br />
PICCV-20-010(-PT) + LRX24-MFT 10 0.63 100% 13%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
Multi-Function<br />
Technology<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 6 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-20-006 + LRX24-MFT + P-10019.<br />
Engineering Note: The 3/4” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology®. The PICCV-20-010 offers nominal<br />
flow rates that are adjustable from 6 to 10 GPM. Please follow<br />
MFT guideline settings when configuring the PICCV MFT actuators<br />
in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
15
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />
1”, 12 – 18 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV can be ordered in 2 ways. The PICCV-25-016<br />
can be reprogrammed to offer flows from 11 GPM – 16 GPM.<br />
Example 1: The application requires a 14 GPM flow rate.<br />
Solution: Order the PICCV-25-014<br />
Example 2: The application requires a 15 GPM flow rate.<br />
Solution: Order the PICCV-25-016 and re-program to the<br />
below setting for 15 GPM. As a standard, the<br />
PICCV is available in flows of 14 GPM and 16<br />
GPM. If you desire 15 GPM and have a Normally<br />
Closed (NC) valve, simply reprogram the maximum<br />
setting to 83%, and minimum setting of 0% as<br />
indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
11 0.69 73% 0%<br />
PICCV-25-012(-PT) + LRX24-MFT 12 0.76 75% 0%<br />
13 0.82 77% 0%<br />
PICCV-25-014(-PT) + LRX24-MFT 14 0.88 80% 0%<br />
15 0.95 83% 0%<br />
PICCV-25-016(-PT) + LRX24-MFT† 16 1.01 100% 0%<br />
PICCV-25-018 (-PT)+ LRX24-MFT 17 1.07 78% 0%<br />
18 1.14 81% 0%<br />
19 1.20 92% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
11 0.69 100% 26%<br />
PICCV-25-012(-PT) + LRX24-MFT 12 0.76 100% 24%<br />
13 0.82 100% 20%<br />
PICCV-25-014(-PT) + LRX24-MFT 14 0.88 100% 16%<br />
15 0.95 100% 9%<br />
PICCV-25-016(-PT) + LRX24-MFT† 16 1.01 100% 0%<br />
PICCV-25-018(-PT) + LRX24-MFT 17 1.07 100% 22%<br />
18 1.14 100% 15%<br />
19 1.20 100% 11%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
† 1” valve has 2 disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
Multi-Function<br />
Technology<br />
16<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 14 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-25-014 + LRX24-MFT+ P-10019.<br />
Engineering Note: The 1” PICCV utilizes two uniquely engineered<br />
valve bodies to achieve the listed flow rate offerings. Variable<br />
GPMs are further realized using Belimo’s registered Multi-Function<br />
Technology®. The PICCV-25-016 offers nominal flow rates that<br />
are adjustable from 11 to 16 GPM. The PICCV-25-018 offers nominal<br />
flow rates that are adjustable from 17 to 19 GPM range.<br />
Please follow MFT guideline settings when configuring the PICCV<br />
MFT actuators in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® <strong>Pressure</strong><br />
<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
Actuator Specifications<br />
TF24-MFT US<br />
Power supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power consumption running: 2.5 W; holding: 1 W<br />
Transformer sizing 4 VA (class 2 power source)<br />
Electrical connection TF24-MFT US 3 ft, 18 GA plenum rated cable<br />
1/2” conduit connector<br />
Overload protection electronic throughout 0° to 95° rotation<br />
Operating range Y 2 to 10 VDC<br />
4 to 20 mA<br />
(w/500Ω, 1/4 W resistor) ZG-R01<br />
Input impedance 100kΩ for 2 to 10 VDC (0.1 mA)<br />
500Ω for 4 to 20 mA<br />
Feedback output U<br />
1500Ω for PWM, Floating point and<br />
On-Off control<br />
2 to 10 VDC, 0.5 mA max<br />
Torque min 18 in-lb (2 Nm)<br />
Direction of rotation spring: reversible with cw/ccw mounting<br />
motor: reversible with built-in switch<br />
Mech. angle of rotation max 95°, adjust with mechanical stop<br />
Running time motor* 100 sec constant<br />
Running time spring
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
1/2”, 0.5 – 5 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />
GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />
1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />
table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 2 GPM flow rate.<br />
Solution: Order the PICCV-15-002<br />
Example 2: The application requires a 3.5 GPM flow rate.<br />
Solution: Order the PICCV-15-005 and re-program to the<br />
below setting for 3.5 GPM. As a standard, the<br />
PICCV is available in flows of 4 GPM and 3 GPM.<br />
If you desire 3.5 GPM and have a Normally<br />
Closed, Fail Open (NC, FO) valve, simply reprogram<br />
the maximum setting to 75%, and minimum<br />
setting of 0% as indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on W<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT)+ TF24-MFT US 0.5 0.03 FO 80%, FC 73% FO, FC 0%<br />
PICCV-15-001(-PT) + TF24-MFT US† 1 0.06 FO 94%, FC 90% FO, FC 0%<br />
PICCV-15-1.50(-PT)+ TF24-MFT US 1.5 0.09 FO 62%, FC 58% FO, FC 0%<br />
PICCV-15-002(-PT) + TF24-MFT US 2 0.13 FO 66%, FC 62% FO, FC 0%<br />
2.5 0.16 FO 69%, FC 65% FO, FC 0%<br />
PICCV-15-003(-PT) + TF24-MFT US 3 0.19 FO 72%, FC 69% FO, FC 0%<br />
3.5 0.22 FO 75%, FC 71% FO, FC 0%<br />
PICCV-15-004(-PT) + TF24-MFT US 4 0.25 FO 77%, FC 73% FO, FC 0%<br />
4.5 0.25 FO 81%, FC 77% FO, FC 0%<br />
PICCV-15-005(-PT) + TF24-MFT US 5 0.32 FO 85%, FC 81% FO, FC 0%<br />
5.5 0.35 FO 89%, FC 85% FO, FC 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT)+ TF24-MFT US 0.5 0.03 FO, FC 100% FO 29%, FC 34%<br />
PICCV-15-001(-PT) + TF24-MFT US† 1 0.06 FO, FC 100% FO 13%, FC 15%<br />
PICCV-15-1.50(-PT)+ TF24-MFT US 1.5 0.09 FO, FC 100% FO 43%, FC 47%<br />
PICCV-15-002(-PT) + TF24-MFT US 2 0.13 FO, FC 100% FO 39%, FC 43%<br />
2.5 0.16 FO, FC 100% FO 36%, FC 41%<br />
PICCV-15-003(-PT) + TF24-MFT US 3 0.19 FO, FC 100% FO 34%, FC 38%<br />
3.5 0.22 FO, FC 100% FO 31%, FC 36%<br />
PICCV-15-004(-PT) + TF24-MFT US 4 0.25 FO, FC 100% FO 28%, FC 33%<br />
4.5 0.25 FO, FC 100% FO 25%, FC 29%<br />
PICCV-15-005(-PT) + TF24-MFT US 5 0.32 FO, FC 100% FO 20%, FC 25%<br />
5.5 0.35 FO, FC 100% FO 17%, FC 22%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
† Note: 1/2” valve has 2 disc sizes (.5 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
Multi-Function<br />
Technology<br />
18<br />
Please note that the settings are different for Normally Closed,<br />
Fail Open or Fail Closed (NC, FO or FC) and Normally Open, Fail<br />
Open or Fail Closed (NO, FO or FC) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 3 GPM flow rate is required, spring return actuator,<br />
2-10 VDC signal.<br />
Solution: PICCV-15-003 + TF24-MFT US + P-10019.<br />
Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />
valve bodies to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered Multi-<br />
Function Technology®. The PICCV-15-001 offers nominal flow rates<br />
that are adjustable from 0.5 to 1.0 GPM. The PICCV-15-005 offers<br />
nominal flow rates that are adjustable from 1.5 to 5.5 GPM range.<br />
Please follow MFT guideline settings when configuring the PICCV<br />
MFT actuators in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: TF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Valve Specifications<br />
® <strong>Pressure</strong><br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1/2”, 3/4”, 1”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-PT)<br />
Body pressure rating 600 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />
1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />
3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />
5 GPM [.32 l/s]<br />
Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />
8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />
10 GPM [0.63 l/s]<br />
Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />
16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
operating range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 1/2” = 2.52 lbs, 3/4” = 3.05 lbs<br />
1” = 4.98 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ LF24-MFT US<br />
Control MFT<br />
Control signal Y 2 to 10 VDC (Default)<br />
Power supply 24 VAC ± 20% 50/60 Hz, 24 VDC ± 10%<br />
Power consumption 2.5 W running, 1 W holding<br />
Transformer sizing 5 VA (Class 2 power source)<br />
Electrical connection 3 ft, 18 GA, plenum rated cable,<br />
1/2” conduit<br />
Overload protection electronic throughout 0 to 95° rotation<br />
Operating range 2 to 10 VDC, 4 to 20 mA<br />
(w/500 Ω, 1/4 W resistor) ZG-R01<br />
Input impedance 100kΩ for 2 to 10 VDC (0.1 mA)<br />
500Ω for 4 to 20 mA, 1500Ω for PWM,<br />
Floating point and On-Off control<br />
Feedback output U 2 to 10 VDC, 0.5 mA max<br />
Direction of rotation spring return reversible with CW/CCW<br />
mounting. Control direction selected by<br />
switch: CW=CW with decrease in signal<br />
CCW=CCW with a decrease in signal<br />
Running time motor* 100 sec constant<br />
Running time spring
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
1/2”, 0.5 – 5 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />
GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />
1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />
table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 2 GPM flow rate.<br />
Solution: Order the PICCV-15-002<br />
Example 2: The application requires a 3.5 GPM flow rate.<br />
Solution: Order the PICCV-15-005 and re-program to the<br />
below setting for 3.5 GPM. As a standard, the<br />
PICCV is available in flows of 4 GPM and 3 GPM.<br />
If you desire 3.5 GPM and have a Normally Closed<br />
(NC) valve, simply reprogram the maximum setting<br />
to 71%, and minimum setting of 0% as indicated<br />
on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 FO 72%, FC 68%° FO, FC 0%° NEW<br />
PICCV-15-001(-PT) + LF24-MFT US♦ 1 0.06 FO 91%, FC 88%° FO, FC 0%° NEW<br />
PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 48% 0%<br />
PICCV-15-001(-PT) + LF24-MFT US†♦ 1 0.06 73% 0%<br />
PICCV-15-1.50(-PT) + LF24-MFT US♦ 1.5 0.09 57% 0%<br />
PICCV-15-002-PT + LF24-MFT US 2 0.13 64% 0%<br />
2.5 0.16 66% 0%<br />
PICCV-15-003(-PT) + LF24-MFT US 3 0.19 69% 0%<br />
3.5 0.22 71% 0%<br />
PICCV-15-004(-PT) + LF24-MFT US 4 0.25 76% 0%<br />
4.5 0.28 79% 0%<br />
PICCV-15-005(-PT) + LF24-MFT US 5 0.32 82% 0%<br />
5.5 0.35 87% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 FO, FC 100%° FO 30%, FC 33%° NEW<br />
PICCV-15-001(-PT) + LF24-MFT US♦ 1 0.06 FO, FC 100%° FO 11%, FC 15%° NEW<br />
PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 100% 55%<br />
PICCV-15-001(-PT) + LF24-MFT US†♦ 1 0.06 100% 37%<br />
PICCV-15-1.50(-PT) + LF24-MFT US 1.5 0.09 100% 43%<br />
PICCV-15-002(-PT) + LF24-MFT US 2 0.13 100% 40%<br />
2.5 0.16 100% 37%<br />
PICCV-15-003(-PT) + LF24-MFT US 3 0.19 100% 35%<br />
3.5 0.22 100% 32%<br />
PICCV-15-004(-PT) + LF24-MFT US 4 0.25 100% 28%<br />
4.5 0.28 100% 25%<br />
PICCV-15-005(-PT) + LF24-MFT US 5 0.32 100% 20%<br />
5.5 0.35 100% 18%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set. °FO = Fail Open, FC = Fail Closed<br />
† Note: 1/2” valve has 2 disc sizes (.5 to 1 GPM) (1.5 to 5.5 GPM)<br />
♦For replacement or re-programming, please contact <strong>Technical</strong> Support 800-543-9038.<br />
Multi-Function<br />
Technology<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 3 GPM flow rate is required, spring return actuator,<br />
2-10 VDC signal.<br />
Solution: PICCV-15-003 + LF24-MFT US + P-10019.<br />
Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />
valve bodies to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered Multi-<br />
Function Technology®. The PICCV-15-001 offers nominal flow rates<br />
that are adjustable from 0.5 to 1.3 GPM. The PICCV-15-005 offers<br />
nominal flow rates that are adjustable from 1.5 to 5.5 GPM range.<br />
Please follow MFT guideline settings when configuring the PICCV<br />
MFT actuators in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
20<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Selecting the Proper Flow Rate:<br />
The PICCV-20-010 (-PT) can be ordered in 6 GPM to 10 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 6 GPM flow rate.<br />
Solution: Order the PICCV-20-006<br />
Example 2: The application requires a 8.5 GPM flow rate.<br />
Solution: Order the PICCV-20-010 and re-program to the<br />
below setting for 8.5 GPM. As a standard, the<br />
PICCV is available in flows of 8 GPM and 9 GPM.<br />
If you desire 8.5 GPM and have a Normally Closed<br />
(NC) valve, simply reprogram the maximum setting<br />
to 82% and minimum setting of 0% as indicated on<br />
the chart below.<br />
Multi-Function<br />
Technology<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 6 GPM flow rate is required, spring return actuator,<br />
2-10 VDC signal.<br />
Solution: PICCV-20-006 + LF24-MFT US + P-10019.<br />
Engineering Note: The 3/4” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology®. The PICCV-20-010 offers nominal<br />
flow rates that are adjustable from 6 to 10 GPM. Please follow<br />
MFT guideline settings when configuring the PICCV MFT actuators<br />
in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
3/4”, 6 – 10 GPM<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LF24-MFT US 6 0.38 74% 0%<br />
6.5 0.41 75% 0%<br />
PICCV-20-007(-PT) + LF24-MFT US 7 0.44 77% 0%<br />
7.5 0.47 79% 0%<br />
PICCV-20-008(-PT) + LF24-MFT US 8 0.50 80% 0%<br />
8.5 0.54 82% 0%<br />
PICCV-20-009(-PT) + LF24-MFT US 9 0.57 83% 0%<br />
9.5 0.60 85% 0%<br />
PICCV-20-010(-PT) + LF24-MFT US 10 0.63 90% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustments**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-20-006(-PT) + LF24-MFT US 6 0.38 100% 31%<br />
6.5 0.41 100% 28%<br />
PICCV-20-007(-PT) + LF24-MFT US 7 0.44 100% 27%<br />
7.5 0.47 100% 25%<br />
PICCV-20-008(-PT) + LF24-MFT US 8 0.50 100% 24%<br />
8.5 0.54 100% 22%<br />
PICCV-20-009(-PT) + LF24-MFT US 9 0.57 100% 19%<br />
9.5 0.60 100% 18%<br />
PICCV-20-010(-PT) + LF24-MFT US 10 0.63 100% 13%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
21
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with MFT, Spring Return Actuator, P/T Ports (Optional)<br />
1”, 12 – 18 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-25-016 (-PT) can be ordered in 11 GPM to 16 GPM<br />
flow increments, as stated in the table below.<br />
The PICCV-25-018 (-PT) can be ordered in 17 GPM to 19 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 14 GPM flow rate.<br />
Solution: Order the PICCV-25-014<br />
Example 2: The application requires a 15 GPM flow rate.<br />
Solution: Order the PICCV-25-016 and re-program to the<br />
below setting for 15 GPM. As a standard, the PICCV<br />
is available in flows of 14 GPM and 16 GPM. If you<br />
desire 15 GPM and have a Normally Closed (NC)<br />
valve, simply reprogram the maximum setting to<br />
83%, and minimum setting of 0% as indicated on<br />
the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
11 0.69 73% 0%<br />
PICCV-25-012(-PT) + LF24-MFT US 12 0.76 75% 0%<br />
13 0.82 77% 0%<br />
PICCV-25-014(-PT) + LF24-MFT US 14 0.88 80% 0%<br />
15 0.95 83% 0%<br />
PICCV-25-016(-PT) + LF24-MFT US† 16 1.01 100% 0%<br />
PICCV-25-018(-PT) + LF24-MFT US 17 1.07 78% 0%<br />
18 1.14 81% 0%<br />
19 1.20 92% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
11 0.69 100% 26%<br />
PICCV-25-012(-PT) + LF24-MFT US 12 0.76 100% 24%<br />
13 0.82 100% 20%<br />
PICCV-25-014(-PT) + LF24-MFT US 14 0.88 100% 16%<br />
15 0.95 100% 9%<br />
PICCV-25-016(-PT) + LF24-MFT US† 16 1.01 100% 0%<br />
PICCV-25-018(-PT) + LF24-MFT US 17 1.07 100% 22%<br />
18 1.14 100% 15%<br />
19 1.20 100% 11%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
† 1” valve has 2 disc sizes (11 to 16 GPM) (17 to 19 GPM)<br />
Multi-Function<br />
Technology<br />
22<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 14 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-25-014 + LF24-MFT US + P-10019.<br />
Engineering Note: The 1” PICCV utilizes two uniquely engineered<br />
valve bodies to achieve the listed flow rate offerings. Variable<br />
GPMs are further realized using Belimo’s registered Multi-Function<br />
Technology®. The PICCV-25-016 offers nominal flow rates that<br />
are adjustable from 11 to 16 GPM. The PICCV-25-018 offers nominal<br />
flow rates that are adjustable from 17 to 19 GPM range.<br />
Please follow MFT guideline settings when configuring the PICCV<br />
MFT actuators in the field.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Valve Specifications<br />
®<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1-1/4”, 1-1/2”, 2”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />
<strong>Pressure</strong> rating 400 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1-1/4” 18 GPM [1.14 l/s], 20 GPM [1.26 l/s],<br />
22 GPM [1.33 l/s], 24 GPM [1.51 l/s],<br />
26 GPM [1.64 l/s]<br />
Flow rate – 1-1/2” 26 GPM [1.64 l/s], 28 GPM [1.77 l/s],<br />
30 GPM [1.89 l/s], 33 GPM [2.08 l/s]<br />
Flow rate – 2” 33 GPM [2.08 l/s], 36 GPM [2.27 l/s],<br />
40 GPM [2.52 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 1-1/4” = 8.31 lbs<br />
1-1/2” = 7.70 lbs<br />
2” = 9.38 lbs<br />
*Consult page 51 and 52 for flow verification data.<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Non-Spring Return Actuator<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils, and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ ARX24-MFT<br />
Power Supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power Consumption 4 W (1.25 W)<br />
Transformer Sizing 6 VA (Class 2 power source)<br />
Electrical Connection 18 GA plenum rated cable<br />
1/2” conduit connector<br />
❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />
Overload Protection electronic throughout 0 to 95° rotation<br />
Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />
Variable (VDC, PWM, Floating Point,<br />
On/Off)<br />
Input Impedance 100 kΩ (0.1 mA), 500Ω<br />
1500 Ω (PWM, Floating Point, On/Off)<br />
Feedback Output U 2 to 10 VDC, 0.5 mA max<br />
VDC Variable<br />
Direction of Rotation reversible with switch<br />
Position Indication handle<br />
Manual Override external push button and handle<br />
Running Time Motor* 100 sec constant<br />
Humidity 5 to 95% RH non condensing<br />
(EN 60730-1)<br />
Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />
Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />
Housing NEMA 2/IP54<br />
Housing Material UL94-5VA<br />
Agency Listings cULus acc. to UL60730-1A/-2-14,<br />
CAN/CSA E60730-1, CSA C22.2<br />
No. 24-93, CE acc. to 89/336/EEC†<br />
Noise Level
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Non-Spring Return Actuator<br />
1-1/4”, 18 – 26 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-32-026-PT can be ordered in 26 GPM to 33 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 22 GPM flow rate.<br />
Solution: Order the PICCV-32-022-PT<br />
Example 2: The application requires a 25 GPM flow rate.<br />
Solution: Order the PICCV-32-026-PT and re-program to<br />
the below setting for 25 GPM. As a standard, the<br />
PICCV is available in flows of 18, 20, 22, 24 and<br />
26 GPM. If you desire 25 GPM and have a<br />
Normally Closed (NC) valve, simply reprogram<br />
the maximum setting to 87%, and minimum setting<br />
of 0% as indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-32-018-PT + ARX24-MFT 18 1.14 78% 0%<br />
19 1.19 79% 0%<br />
PICCV-32-020-PT + ARX24-MFT 20 1.26 80% 0%<br />
21 1.32 82% 0%<br />
PICCV-32-022-PT + ARX24-MFT 22 1.33 83% 0%<br />
23 1.45 84% 0%<br />
PICCV-32-024-PT + ARX24-MFT 24 1.51 85% 0%<br />
25 1.58 87% 0%<br />
PICCV-32-026-PT + ARX24-MFT 26 1.64 92% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-32-018-PT + ARX24-MFT 18 1.14 100% 25%<br />
19 1.19 100% 24%<br />
PICCV-32-020-PT + ARX24-MFT 20 1.26 100% 23%<br />
21 1.32 100% 22%<br />
PICCV-32-022-PT + ARX24-MFT 22 1.33 100% 19%<br />
23 1.45 100% 18%<br />
PICCV-32-024-PT + ARX24-MFT 24 1.51 100% 17%<br />
25 1.58 100% 14%<br />
PICCV-32-026-PT + ARX24-MFT 26 1.64 100% 11%<br />
* Preprogrammed at factory<br />
** Customer reprogrammable using MFT PC tool / or can be factory set.<br />
Multi-Function<br />
Technology<br />
24<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 22 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-32-022-PT + ARX24-MFT + P-10019.<br />
Engineering Note: The 1-1/4” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . Please follow MFT guideline settings<br />
when configuring the PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-40-033-PT can be ordered in 26 GPM to 33 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 28 GPM flow rate.<br />
Solution: Order the PICCV-40-028-PT<br />
Example 2: The application requires a 31 GPM flow rate.<br />
Solution: Order the PICCV-40-033-PT and re-program to<br />
the below setting for 31 GPM. As a standard, the<br />
PICCV is available in flows of 26, 28, 30, and 33<br />
GPM. If you desire 31 GPM and have a Normally<br />
Closed (NC) valve, simply reprogram the maximum<br />
setting to 89%, and minimum setting of 0%<br />
as indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-40-026-PT + ARX24-MFT 26 1.64 81% 0%<br />
27 1.70 82% 0%<br />
PICCV-40-028-PT + ARX24-MFT 28 1.77 87% 0%<br />
29 1.83 88% 0%<br />
PICCV-40-030-PT + ARX24-MFT 30 1.89 90% 0%<br />
31 1.96 89% 0%<br />
32 2.02 93% 0%<br />
PICCV-40-033-PT + ARX24-MFT 33 2.08 99% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-40-026-PT + ARX24-MFT 26 1.64 100% 25%<br />
27 1.70 100% 24%<br />
PICCV-40-028-PT + ARX24-MFT 28 1.77 100% 22%<br />
29 1.83 100% 20%<br />
PICCV-40-030-PT + ARX24-MFT 30 1.89 100% 16%<br />
31 1.96 100% 12%<br />
32 2.02 100% 10%<br />
PICCV-40-033-PT + ARX24-MFT 33 2.08 100% 6%<br />
* Preprogrammed at factory<br />
** Customer reprogrammable using MFT PC tool / or can be factory set.<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Non-Spring Return Actuator<br />
1-1/2”, 26 – 33 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Multi-Function<br />
Technology<br />
®<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 26 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-40-026-PT + ARX24-MFT + P-10019.<br />
Engineering Note: The 1-1/2” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . Please follow MFT guideline settings<br />
when configuring the PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
25
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Non-Spring Return Actuator<br />
2”, 33 – 40 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-50-040-PT can be ordered in 33 GPM to 40 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 33 GPM flow rate.<br />
Solution: Order the PICCV-50-033-PT<br />
Example 2: The application requires a 34 GPM flow rate.<br />
Solution: Order the PICCV-50-040-PT and re-program to the<br />
below setting for 34 GPM. As a standard, the<br />
PICCV is available in flows of 33 GPM and 36 GPM.<br />
If you desire 34 GPM and have a Normally Closed<br />
(NC) valve, simply re-program the maximum setting<br />
to 79%, and a minimum setting of 0% as indicated<br />
on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-033-PT + ARX24-MFT 33 2.08 78% 0%<br />
34 2.14 79% 0%<br />
35 2.21 80% 0%<br />
PICCV-50-036-PT + ARX24-MFT 36 2.27 81% 0%<br />
37 2.33 82% 0%<br />
38 2.40 84% 0%<br />
39 2.46 85% 0%<br />
PICCV-50-040-PT + ARX24-MFT 40 2.52 100% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-033-PT + ARX24-MFT 33 2.08 100% 23%<br />
34 2.14 100% 22%<br />
35 2.21 100% 20%<br />
PICCV-50-036-PT + ARX24-MFT 36 2.27 100% 19%<br />
37 2.33 100% 18%<br />
38 2.40 100% 17%<br />
39 2.46 100% 16%<br />
PICCV-50-040-PT + ARX24-MFT 40 2.52 100% 15%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
Multi-Function<br />
Technology<br />
26<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal:<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 33 GPM, flow rate is required, non-spring<br />
return actuator, 2-10 VDC signal.<br />
Solution: PICCV-50-033-PT + ARX24-MFT + P-10019<br />
Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ®. The PICCV-50-040-PT offers<br />
nominal flow rates that are adjustable from 33 to 40 GPM.<br />
Please follow MFT guideline settings when configuring the<br />
PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Valve Specifications<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1-1/4”, 1-1/2”, 2”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />
<strong>Pressure</strong> rating 400 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1-1/4” 18 GPM [1.14 l/s], 20 GPM [1.26 l/s],<br />
22 GPM [1.33 l/s], 24 GPM [1.51 l/s],<br />
26 GPM [1.64 l/s]<br />
Flow rate – 1-1/2” 26 GPM [1.64 l/s], 28 GPM [1.77 l/s],<br />
30 GPM [1.89 l/s], 33 GPM [2.08 l/s]<br />
Flow rate – 2” 33 GPM [2.08 l/s], 36 GPM [2.27 l/s],<br />
40 GPM [2.52 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body Weight of valve body<br />
1-1/4” = 8.31 lbs, 1-1/2” = 7.70 lbs<br />
2” = 9.38 lbs<br />
*Consult page 51 and 52 for flow verification data.<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Spring Return Actuator<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils, and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ AF24-MFT US<br />
Control MFT<br />
Control signal: 2 to 10 VDC,<br />
(4 to 20 mA with 500Ω resistor)<br />
Power supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power consumption: 6 W running,<br />
2.5 W holding<br />
Transformer sizing: 10 VA, class 2 power<br />
Electrical connection: 3 ft, 18 GA appl. cable, 1/2” conduit fit.<br />
Electrical protection: Aux. switches double insulated<br />
Overload protection: electronic throughout rotation<br />
Input impedance: 100 KΩ for 2 to 10 VDC (0.1 mA)<br />
500Ω for 4 to 20 mA<br />
750Ω for PWM<br />
1500Ω for on/off and floating point<br />
Feedback output: 2 to 10 VDC, 0.5 mA max<br />
Angle of rotation: 95°<br />
Direction of rotation: selected by switch:<br />
CW=CW with decrease signal<br />
CCW=CCW with decrease signal<br />
Spring return direction: CW/CCW mounting<br />
Position indication: visual indicator<br />
Manual override: hex crank<br />
Running time motor:* 100 sec constant<br />
Ambient temperature: -22° F to 122° F [-30° C to 50° C]<br />
Housing: NEMA 2 / IP54<br />
Agency listings: UL 873, CSA C22.2<br />
No. 24 certified, CE<br />
Noise level: max. 45 dB(A)<br />
AF24-MFT-S US<br />
Auxiliary switch 2 x SPDT 5° fixed/25° to 85°,<br />
7A (2.5A) @ 250 VAC<br />
Weight of actuator 6.28 lbs [2.85 Kg]<br />
*PICCV/AF24-MFT US must remain at 100 sec constant run time<br />
27
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Spring Return Actuator<br />
1-1/4”, 18 – 26 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-32-026-PT can be ordered in 18 GPM to 26 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 22 GPM flow rate.<br />
Solution: Order the PICCV-32-022-PT<br />
Example 2: The application requires a 25 GPM flow rate.<br />
Solution: Order the PICCV-32-026-PT and re-program to<br />
the below setting for 25 GPM. As a standard, the<br />
PICCV is available in flows of 18, 20, 22, 24 and<br />
26 GPM. If you desire 25 GPM and have a<br />
Normally Closed (NC) valve, simply reprogram<br />
the maximum setting to 87%, and minimum setting<br />
of 0% as indicated on the chart below.<br />
28<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 22 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-32-022-PT + AF24-MFT US + P-10019.<br />
Engineering Note: The 1-1/4” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . Please follow MFT guideline settings<br />
when configuring the PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-32-018-PT + AF24-MFT US 18 1.14 78% 0%<br />
19 1.19 79% 0%<br />
PICCV-32-020-PT + AF24-MFT US 20 1.26 80% 0%<br />
21 1.32 82% 0%<br />
PICCV-32-022-PT + AF24-MFT US 22 1.33 83% 0%<br />
23 1.45 84% 0%<br />
PICCV-32-024-PT + AF24-MFT US 24 1.51 85% 0%<br />
25 1.58 87% 0%<br />
PICCV-32-026-PT + AF24-MFT US 26 1.64 92% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-32-018-PT + AF24-MFT US 18 1.14 100% 25%<br />
19 1.19 100% 24%<br />
PICCV-32-020-PT + AF24-MFT US 20 1.26 100% 23%<br />
21 1.32 100% 22%<br />
PICCV-32-022-PT + AF24-MFT US 22 1.33 100% 19%<br />
23 1.45 100% 18%<br />
PICCV-32-024-PT + AF24-MFT US 24 1.51 100% 17%<br />
25 1.58 100% 14%<br />
PICCV-32-026-PT + AF24-MFT US 26 1.64 100% 11%<br />
* Preprogrammed at factory<br />
** Customer reprogrammable using MFT PC tool / or can be factory set.<br />
Multi-Function<br />
Technology<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Selecting the Proper Flow Rate:<br />
The PICCV-40-033-PT can be ordered in 26 GPM to 33 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 28 GPM flow rate.<br />
Solution: Order the PICCV-40-028-PT<br />
Example 2: The application requires a 31 GPM flow rate.<br />
Solution: Order the PICCV-40-033-PT and re-program to<br />
the below setting for 31 GPM. As a standard, the<br />
PICCV is available in flows of 26, 28, 30, and 33<br />
GPM. If you desire 31 GPM and have a Normally<br />
Closed (NC) valve, simply reprogram the maximum<br />
setting to 89%, and minimum setting of 0%<br />
as indicated on the chart below.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-40-026-PT + AF24-MFT US 26 1.64 81% 0%<br />
27 1.70 82% 0%<br />
PICCV-40-028-PT + AF24-MFT US 28 1.77 87% 0%<br />
29 1.83 88% 0%<br />
PICCV-40-030-PT + AF24-MFT US 30 1.89 90% 0%<br />
31 1.96 89% 0%<br />
32 2.02 93% 0%<br />
PICCV-40-033-PT + AF24-MFT US 33 2.08 99% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-40-026-PT + AF24-MFT US 26 1.64 100% 25%<br />
27 1.70 100% 24%<br />
PICCV-40-028-PT + AF24-MFT US 28 1.77 100% 22%<br />
29 1.83 100% 20%<br />
PICCV-40-030-PT + AF24-MFT US 30 1.89 100% 16%<br />
31 1.96 100% 12%<br />
32 2.02 100% 10%<br />
PICCV-40-033-PT + AF24-MFT US 33 2.08 100% 6%<br />
* Preprogrammed at factory<br />
** Customer reprogrammable using MFT PC tool / or can be factory set.<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Spring Return Actuator<br />
1-1/2”, 26 – 33 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Multi-Function<br />
Technology<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering, please<br />
specify NO or NC operation.<br />
Selecting the Proper Control Signal<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 26 GPM flow rate is required, non-spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-40-026-PT + AF24-MFT US + P-10019.<br />
Engineering Note: The 1-1/2” PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . Please follow MFT guideline settings<br />
when configuring the PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
29
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />
P/T Ports and MFT, Spring Return Actuator<br />
2”, 33 – 40 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-50-040-PT can be ordered in 33 GPM to 40 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 33 GPM flow rate.<br />
Solution: Order the PICCV-50-033-PT<br />
Example 2: The application requires a 34 GPM flow rate.<br />
Solution: Order the PICCV-50-040-PT and re-program to<br />
the below setting for 34 GPM. As a standard, the<br />
PICCV is available in flows of 33 GPM and 36<br />
GPM. If you desire 34 GPM and have a Normally<br />
Closed (NC) valve, simply re-program the maximum<br />
setting to 79%, and a minimum setting of<br />
0% as indicated on the chart below.<br />
30<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
Selecting the Proper Control Signal:<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 33 GPM, flow rate is required, non-spring<br />
return actuator, 2-10 VDC signal.<br />
Solution: PICCV-50-033-PT + AF24-MFT US + P-10019<br />
Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ®. The PICCV-50-040-PT offers<br />
nominal flow rates that are adjustable from 33 to 40 GPM.<br />
Please follow MFT guideline settings when configuring the<br />
PICCV MFT actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-033-PT + AF24-MFT US 33 2.08 78% 0%<br />
34 2.14 79% 0%<br />
35 2.21 80% 0%<br />
PICCV-50-036-PT + AF24-MFT US 36 2.27 81% 0%<br />
37 2.33 82% 0%<br />
38 2.40 84% 0%<br />
39 2.46 85% 0%<br />
PICCV-50-040-PT + AF24-MFT US 40 2.52 100% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default* Flow Adjustable**<br />
Flow rate Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-033-PT + AF24-MFT US 33 2.08 100% 23%<br />
34 2.14 100% 22%<br />
35 2.21 100% 20%<br />
PICCV-50-036-PT + AF24-MFT US 36 2.27 100% 19%<br />
37 2.33 100% 18%<br />
38 2.40 100% 17%<br />
39 2.46 100% 16%<br />
PICCV-50-040-PT + AF24-MFT US 40 2.52 100% 15%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
Multi-Function<br />
Technology<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example:AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Valve Specifications<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 2” (44 GPM to 100 GPM)<br />
Type of end fitting female, NPT<br />
Materials:<br />
®<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seats fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* Qty (2) 1/4” brass/Nortel (Standard)<br />
Body pressure rating 400 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 2” 44 GPM [2.78 l/s], 48 GPM [3.03 l/s],<br />
52 GPM [3.28 l/s], 56 GPM [3.53 l/s],<br />
60 GPM [3.79 l/s], 65 GPM [4.10 l/s],<br />
70 GPM [4.42 l/s], 75 GPM [4.73 l/s],<br />
80 GPM [5.05 l/s], 90 GPM [5.68 l/s],<br />
100 GPM [6.31 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure 5 to 50 PSI<br />
range<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 29.1 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
*Consult page 51 and 52 for flow verification data.<br />
2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with P/T Ports and MFT, Non-Spring Return Actuator<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils, and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ ARX24-MFT<br />
Power Supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power Consumption 4 W (1.25 W)<br />
Transformer Sizing 6 VA (Class 2 power source)<br />
Electrical Connection 18 GA plenum rated cable<br />
1/2” conduit connector<br />
❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />
Overload Protection electronic throughout 0 to 95° rotation<br />
Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />
Variable (VDC, PWM, Floating Point,<br />
On/Off)<br />
Input Impedance 100 kΩ (0.1 mA), 500Ω<br />
1500 Ω (PWM, Floating Point, On/Off)<br />
Feedback Output U 2 to 10 VDC, 0.5 mA max<br />
VDC Variable<br />
Direction of Rotation reversible with switch<br />
Position Indication handle<br />
Manual Override external push button and handle<br />
Running time motor* 100 sec constant<br />
Humidity 5 to 95% RH non condensing<br />
(EN 60730-1)<br />
Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />
Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />
Housing NEMA 2/IP54<br />
Housing Material UL94-5VA<br />
Agency Listings cULus acc. to UL60730-1A/-2-14,<br />
CAN/CSA E60730-1, CSA C22.2<br />
No. 24-93, CE acc. to 89/336/EEC†<br />
Noise Level
2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with P/T Ports and MFT, Non-Spring Return Actuator<br />
2”, 44 – 100 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-50-080-PT can be ordered in 44 GPM to 80 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 50 GPM flow rate, and a<br />
Normally Closed valve.<br />
Solution: Order the PICCV-50-052-PT<br />
Example 2: The application requires a 56 GPM flow rate.<br />
Solution: Order the PICCV-50-080-PT and re-program to a<br />
maximum setting of 87%, and a minimum setting of<br />
0% as indicated on the chart below.<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
32<br />
Selecting the Proper Control Signal:<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 50 GPM, flow rate is required, non-spring<br />
return actuator, 2-10 VDC signal.<br />
Solution: PICCV-50-052-PT + ARX24-MFT + P-10019<br />
Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . The PICCV-50-080-PT offers nominal<br />
flow rates that are adjustable from 44 to 80 GPM. Please<br />
follow MFT guideline settings when configuring the PICCV MFT<br />
actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />
Default*<br />
Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-044-PT + ARX24-MFT 44 2.78 82% 0%<br />
PICCV-50-048-PT + ARX24-MFT 48 3.03 84% 0%<br />
PICCV-50-052-PT + ARX24-MFT 52 3.28 85% 0%<br />
PICCV-50-056-PT + ARX24-MFT 56 3.53 87% 0%<br />
PICCV-50-060-PT + ARX24-MFT 60 3.79 89% 0%<br />
PICCV-50-065-PT + ARX24-MFT 65 4.10 91% 0%<br />
PICCV-50-070-PT + ARX24-MFT 70 4.42 94% 0%<br />
PICCV-50-075-PT + ARX24-MFT 75 4.73 97% 0%<br />
PICCV-50-080-PT + ARX24-MFT 80 5.05 99% 0%<br />
PICCV-50-090-PT + ARX24-MFT 90 5.68 94% 0%<br />
PICCV-50-100-PT + ARX24-MFT 100 6.31 100% 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />
Default*<br />
Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-044-PT + ARX24-MFT 44 2.78 100% 28%<br />
PICCV-50-048-PT + ARX24-MFT 48 3.03 100% 26%<br />
PICCV-50-052-PT + ARX24-MFT 52 3.28 100% 24%<br />
PICCV-50-056-PT + ARX24-MFT 56 3.53 100% 22%<br />
PICCV-50-060-PT + ARX24-MFT 60 3.79 100% 20%<br />
PICCV-50-065-PT + ARX24-MFT 65 4.10 100% 17%<br />
PICCV-50-070-PT + ARX24-MFT 70 4.42 100% 13%<br />
PICCV-50-075-PT + ARX24-MFT 75 4.73 100% 10%<br />
PICCV-50-080-PT + ARX24-MFT 80 5.05 100% 1%<br />
PICCV-50-090-PT + ARX24-MFT 90 5.68 100% 11%<br />
PICCV-50-100-PT + ARX24-MFT 100 6.31 100% 0%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
†Note: 2” valves has 2 disc sizes (44 GPM to 80 GPM) (90 GPM to 100 GPM)<br />
Multi-Function<br />
Technology<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Valve Specifications<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 2” (44 GPM - 100 GPM)<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seats fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless steel<br />
Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />
Body pressure rating 400 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 2” 44 GPM [2.78 l/s], 48 GPM [3.03 l/s],<br />
52 GPM [3.28 l/s], 56 GPM [3.53 l/s],<br />
60 GPM [3.79 l/s], 65 GPM [4.10 l/s],<br />
70 GPM [4.42 l/s], 75 GPM [4.73 l/s],<br />
80 GPM [5.05 l/s], 90 GPM [5.68 l/s],<br />
100 GPM [6.31 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 29.1 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
*Consult page 51 and 52 for flow verification data.<br />
2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with P/T Ports and MFT, Spring Return Actuator<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />
used in air handling units on heating and cooling coils, and fan coil<br />
unit heating or cooling coils. Some other common applications<br />
include unit ventilators and VAV re-heat coils. This valve is suitable<br />
for use in a hydronic system with constant or variable flow.<br />
This valve is designed with MFT functionality which facilitates<br />
the use of various control input.<br />
Actuator Specifications<br />
❏ AF24-MFT US<br />
Control MFT<br />
Control signal: 2 to 10 VDC,<br />
(4 to 20 mA with 500Ω resistor)<br />
Power supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power consumption: 6 W running,<br />
2.5 W holding<br />
Transformer sizing: 10 VA, class 2 power<br />
Electrical connection: 3 ft, 18 GA appl. cable, 1/2” conduit fit.<br />
Electrical protection: Aux. switches double insulated<br />
Overload protection: electronic throughout rotation<br />
Input impedance: 100 KΩ for 2 to 10 VDC (0.1 mA)<br />
500Ω for 4 to 20 mA<br />
750Ω for PWM<br />
1500Ω for on/off and floating point<br />
Feedback output: 2 to 10 VDC, 0.5 mA max<br />
Angle of rotation: 95°<br />
Direction of rotation: selected by switch:<br />
CW=CW with decrease signal<br />
CCW=CCW with decrease signal<br />
Spring return direction: CW/CCW mounting<br />
Position indication: visual indicator<br />
Manual override: hex crank<br />
Auxiliary switches: 2 x SPDT. 5° fixed/25° to 85°(-S)<br />
Running time motor:* 100 sec constant<br />
Ambient temperature: -22° F to 122° F [-30° C to 50° C]<br />
Housing: NEMA 2 / IP54<br />
Agency listings: UL 873, CSA C22.2<br />
No. 24 certified, CE<br />
Noise level: max. 45 dB(A)<br />
AF24-MFT-S US<br />
Auxiliary switch 2 x SPDT 5° fixed/25° to 85°,<br />
7A (2.5A) @ 250 VAC<br />
Weight of actuator 6.28 lbs [2.85 Kg]<br />
*PICCV/AF24-MFT US must remain at 100 sec constant run time<br />
LISTED<br />
94D5<br />
TEMP. IND & UL ®<br />
REG. EQUIP.<br />
©<br />
MFT<br />
33
2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with P/T Ports and MFT, Spring Return Actuator<br />
2”, 44 – 100 GPM<br />
The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />
Selecting the Proper Flow Rate:<br />
The PICCV-50-080-PT can be ordered in 44 GPM to 80 GPM<br />
flow rate increments, as stated in the table below.<br />
If you wish to re-program to the values listed in the table below:<br />
Example 1: The application requires a 50 GPM flow rate, and a<br />
Normally Closed valve.<br />
Solution: Order the PICCV-50-052-PT<br />
Example 2: The application requires a 56 GPM flow rate.<br />
Solution: Order the PICCV-50-080-PT and re-program to a<br />
maximum setting of 81%, and a minimum setting of<br />
0% as indicated on the chart below.<br />
Please note that the settings are different for Normally Closed<br />
(NC) and Normally Open (NO) operation. When ordering,<br />
please specify NO or NC operation.<br />
34<br />
MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />
Default*<br />
Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-044-PT + AF24-MFT US 44 2.78 75% 0%<br />
PICCV-50-048-PT + AF24-MFT US 48 3.03 77% 0%<br />
PICCV-50-052-PT + AF24-MFT US 52 3.28 78% 0%<br />
PICCV-50-056-PT + AF24-MFT US 56 3.53 81% 0%<br />
PICCV-50-060-PT + AF24-MFT US 60 3.79 83% 0%<br />
PICCV-50-065-PT + AF24-MFT US 65 4.10 85% 0%<br />
PICCV-50-070-PT + AF24-MFT US 70 4.42 88% 0%<br />
PICCV-50-075-PT + AF24-MFT US 75 4.73 92% 0%<br />
PICCV-50-080-PT + AF24-MFT US 80 5.05 100% 0%<br />
PICCV-50-090-PT + AF24-MFT US 90 5.68 FO 93%, FC 89% FO, FC 0%<br />
PICCV-50-100-PT + AF24-MFT US 100 6.31 FO, FC 100% FO, FC 0%<br />
MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />
Default*<br />
Flow rate MFT angle of MFT angle of<br />
Product Range GPM l/s rotation max. setting rotation min. setting<br />
PICCV-50-044-PT + AF24-MFT US 44 2.78 100% 24%<br />
PICCV-50-048-PT + AF24-MFT US 48 3.03 100% 22%<br />
PICCV-50-052-PT + AF24-MFT US 52 3.28 100% 21%<br />
PICCV-50-056-PT + AF24-MFT US 56 3.53 100% 19%<br />
PICCV-50-060-PT + AF24-MFT US 60 3.79 100% 17%<br />
PICCV-50-065-PT + AF24-MFT US 65 4.10 100% 13%<br />
PICCV-50-070-PT + AF24-MFT US 70 4.42 100% 11%<br />
PICCV-50-075-PT + AF24-MFT US 75 4.73 100% 2%<br />
PICCV-50-080-PT + AF24-MFT US 80 5.05 100% 0%<br />
PICCV-50-090-PT + AF24-MFT US 90 5.68 FO, FC 100% FO 12%, FC 16%<br />
PICCV-50-100-PT + AF24-MFT US 100 6.31 FO, FC 100% FO, FC 0%<br />
*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />
†Note: 2” valves has 2 disc sizes (44 GPM to 80 GPM) (90 GPM to 100 GPM)<br />
Multi-Function<br />
Technology<br />
Selecting the Proper Control Signal:<br />
Select one of the MFT codes below for the signal required.<br />
Example: A 50 GPM, flow rate is required, spring return<br />
actuator, 2-10 VDC signal.<br />
Solution: PICCV-50-052-PT + AF24-MFT US + P-10019<br />
Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />
valve body to achieve the listed flow rate offerings.<br />
Variable GPMs are further realized using Belimo’s registered<br />
Multi-Function Technology ® . The PICCV-50-080-PT offers nominal<br />
flow rates that are adjustable from 44 to 80 GPM. Please<br />
follow MFT guideline settings when configuring the PICCV MFT<br />
actuators in the field.<br />
Note: Minimum and Maximum Settings differ for the<br />
ARX24-MFT and AF24-MFT US actuators.<br />
For complete technical information and list of configuration codes refer to<br />
Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />
Model Control Input Running Time Built-in Feedback List Price<br />
P-10019 2-10 VDC 100 2-10 VDC No Charge<br />
P-10028 0-10 VDC 100 0-10 VDC No Charge<br />
P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />
P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />
P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />
P-30003 Floating Point 100 2-10 VDC No Charge<br />
P-10019* On/Off 100 2-10 VDC No Charge<br />
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />
Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />
*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
PICCV-15-0.50 (-PT) Normally Closed<br />
0.50<br />
0.45<br />
0.40<br />
0.35<br />
0.30<br />
0.25<br />
0.20<br />
0.15<br />
0.10<br />
0.05<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-15-001 (-PT) Normally Closed<br />
1.00<br />
0.90<br />
0.80<br />
0.70<br />
0.60<br />
0.50<br />
0.40<br />
0.30<br />
0.20<br />
0.10<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-15-0.50 (-PT) to PICCV-15-001 (-PT) (.5 to 1 GPM)<br />
NEW ♦<br />
NEW ♦<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
♦ Please use “NEW” if the order was placed after July 24, 2007.<br />
PICCV-15-0.50 (-PT) Normally Open<br />
0.50<br />
0.45<br />
0.40<br />
0.35<br />
0.30<br />
0.25<br />
0.20<br />
0.15<br />
0.10<br />
0.05<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-15-001 (-PT) Normally Open<br />
1.00<br />
0.90<br />
0.80<br />
0.70<br />
0.60<br />
0.50<br />
0.40<br />
0.30<br />
0.20<br />
0.10<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
NEW ♦<br />
NEW ♦<br />
35
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-15-1.50 (-PT) to PICCV-15-003 (-PT) (1.5 to 3 GPM)<br />
36<br />
1.50<br />
1.25<br />
1.00<br />
0.75<br />
0.50<br />
0.25<br />
2.00<br />
1.75<br />
1.50<br />
1.25<br />
1.00<br />
0.75<br />
0.50<br />
0.25<br />
PICCV-15-002 (-PT) Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
PICCV-15-1.50 (-PT) Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback (Volts)<br />
PICCV-15-003 (-PT) Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
1.50<br />
1.25<br />
1.00<br />
0.75<br />
0.50<br />
0.25<br />
2.00<br />
1.75<br />
1.50<br />
1.25<br />
1.00<br />
0.75<br />
0.50<br />
0.25<br />
PICCV-15-002 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
PICCV-15-1.50 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback (Volts)<br />
PICCV-15-003 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
®<br />
PICCV-15-004 (-PT) Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-15-005 (-PT) Normally Closed<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-15-004 (-PT) to PICCV-15-005 (-PT) (4 to 5 GPM)<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
PICCV-15-004 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-15-005 (-PT) Normally Open<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
37
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-20-006 (-PT) to PICCV-20-008 (-PT) (6 to 8 GPM)<br />
38<br />
PICCV-20-006 (-PT) Normally Closed<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-20-007 (-PT) Normally Closed<br />
7.00<br />
6.50<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-20-008 (-PT) Normally Closed<br />
8.00<br />
7.50<br />
7.00<br />
6.50<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-20-006 (-PT) Normally Open<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-20-007 (-PT) Normally Open<br />
7.00<br />
6.50<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-20-008 (-PT) Normally Open<br />
8.00<br />
7.50<br />
7.00<br />
6.50<br />
6.00<br />
5.50<br />
5.00<br />
4.50<br />
4.00<br />
3.50<br />
3.00<br />
2.50<br />
2.00<br />
1.50<br />
1.00<br />
0.50<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
®<br />
PICCV-20-009 (-PT) Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
Feedback (Volts)<br />
PICCV-20-010 (-PT) Normally Closed<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-20-009 (-PT) to PICCV-20-010 (-PT) (9 to 10 GPM)<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
PICCV-20-009 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
Feedback (Volts)<br />
PICCV-20-010 (-PT) Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
39
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-25-012 (-PT) to PICCV-25-014 (-PT) (12 to 14 GPM)<br />
40<br />
PICCV-25-012 (-PT) Normally Closed<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-25-014 (-PT) Normally Closed<br />
14.00<br />
13.00<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-25-012 (-PT) Normally Open<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-25-014 (-PT) Normally Open<br />
14.00<br />
13.00<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® Feedback<br />
PICCV-25-016 (-PT) Normally Closed<br />
16.00<br />
15.00<br />
14.00<br />
13.00<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
Feedback (Volts)<br />
PICCV-25-018-PT Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Charts for PICCVs with MFT Actuator<br />
PICCV-25-016 (-PT) to PICCV-25-018 (-PT) (16 to 18 GPM)<br />
PICCV-25-016 (-PT) Normally Open<br />
16.00<br />
15.00<br />
14.00<br />
13.00<br />
12.00<br />
11.00<br />
10.00<br />
9.00<br />
8.00<br />
7.00<br />
6.00<br />
5.00<br />
4.00<br />
3.00<br />
2.00<br />
1.00<br />
0.00<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
Feedback (Volts)<br />
PICCV-25-018-PT Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
41
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-32-018-PT to PICCV-32-022-PT (18 to 22 GPM)<br />
42<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
PICCV-32-018-PT Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
Feedback (Volts)<br />
PICCV-32-020-PT Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-32-022-PT Normally Closed<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
PICCV-32-018-PT Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
Feedback (Volts)<br />
PICCV-32-020-PT Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-32-022-PT Normally Open<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® Feedback<br />
PICCV-32-024-PT Normally Closed<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-32-026-PT Normally Closed<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Charts for PICCVs with MFT Actuator<br />
PICCV-32-024-PT to PICCV-32-026-PT (24 to 26 GPM)<br />
PICCV-32-024-PT Normally Open<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-32-026-PT Normally Open<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
43
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-40-026-PT to PICCV-40-028-PT (26 to 28 GPM)<br />
44<br />
PICCV-40-026-PT Normally Closed<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-40-028-PT Normally Closed<br />
28.00<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-40-026-PT Normally Open<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
PICCV-40-028-PT Normally Open<br />
28.00<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
PICCV-40-030-PT Normally Closed<br />
30.00<br />
28.00<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-40-033-PT Normally Closed<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-40-030-PT to PICCV-40-033-PT (30 to 33 GPM)<br />
PICCV-40-030-PT Normally Open<br />
30.00<br />
28.00<br />
26.00<br />
24.00<br />
22.00<br />
20.00<br />
18.00<br />
16.00<br />
14.00<br />
12.00<br />
10.00<br />
8.00<br />
6.00<br />
4.00<br />
2.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
PICCV-40-033-PT Normally Open<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
45
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-50-033-PT to PICCV-50-040-PT (33 to 40 GPM)<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
46<br />
PICCV-50-033-PT Normally Closed<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-036-PT Normally Closed<br />
36.00<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
40.00<br />
36.00<br />
32.00<br />
28.00<br />
24.00<br />
20.00<br />
16.00<br />
12.00<br />
8.00<br />
4.00<br />
Feedback (Volts)<br />
PICCV-50-040-PT Normally Closed<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-033-PT Normally Open<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-036-PT Normally Open<br />
36.00<br />
33.00<br />
30.00<br />
27.00<br />
24.00<br />
21.00<br />
18.00<br />
15.00<br />
12.00<br />
9.00<br />
6.00<br />
3.00<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
40.00<br />
36.00<br />
32.00<br />
28.00<br />
24.00<br />
20.00<br />
16.00<br />
12.00<br />
8.00<br />
4.00<br />
Feedback (Volts)<br />
PICCV-50-040-PT Normally Open<br />
0.00<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
®<br />
Feedback<br />
PICCV-50-044-PT Normally Closed<br />
0.0<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-048-PT Normally Closed<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-052-PT Normally Closed<br />
52.0<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
Charts for PICCVs with MFT Actuator<br />
PICCV-50-044-PT to PICCV-50-052-PT (44 to 52 GPM)<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
PICCV-50-044-PT Normally Open<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-048-PT Normally Open<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-052-PT Normally Open<br />
52.0<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
47
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-50-056-PT to PICCV-50-065-PT (56 to 65 GPM)<br />
48<br />
PICCV-50-056-PT Normally Closed<br />
56.0<br />
52.0<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-060-PT Normally Closed<br />
60.0<br />
55.0<br />
50.0<br />
45.0<br />
40.0<br />
35.0<br />
30.0<br />
25.0<br />
20.0<br />
15.0<br />
10.0<br />
5.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-065-PT Normally Closed<br />
65.0<br />
60.0<br />
55.0<br />
50.0<br />
45.0<br />
40.0<br />
35.0<br />
30.0<br />
25.0<br />
20.0<br />
15.0<br />
10.0<br />
5.0<br />
0.0<br />
2 3 4 5 6 7 8 9 10<br />
Feedback (Volts)<br />
PICCV-50-056-PT Normally Open<br />
56.0<br />
52.0<br />
48.0<br />
44.0<br />
40.0<br />
36.0<br />
32.0<br />
28.0<br />
24.0<br />
20.0<br />
16.0<br />
12.0<br />
8.0<br />
4.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-060-PT Normally Open<br />
60.0<br />
55.0<br />
50.0<br />
45.0<br />
40.0<br />
35.0<br />
30.0<br />
25.0<br />
20.0<br />
15.0<br />
10.0<br />
5.0<br />
0.0<br />
2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
Feedback (Volts)<br />
PICCV-50-065-PT Normally Open<br />
65.0<br />
60.0<br />
55.0<br />
50.0<br />
45.0<br />
40.0<br />
35.0<br />
30.0<br />
25.0<br />
20.0<br />
15.0<br />
10.0<br />
5.0<br />
0.0<br />
2 3 4 5 6 7 8 9 10<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
Feedback (Volts)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-50-070-PT to PICCV-50-080-PT (70 to 80 GPM)<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
49
Feedback Charts for PICCVs with MFT Actuator<br />
PICCV-50-090-PT to PICCV-50-100-PT (90 to 100 GPM)<br />
Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />
Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />
50<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Field Adjustable Flow Ranges<br />
with the LRB24-3 and FlowSetR<br />
Default<br />
Model # Flow Rate Field Adjustable<br />
Valve (GPM)* Design Flow (GPM)**<br />
PICCV-15-0.50 (-PT) 0.5<br />
PICCV-15-001 (-PT) 1<br />
PICCV-15-1.50 (-PT) 1.5<br />
PICCV-15-002 (-PT) 2<br />
0.5 to 1.3<br />
PICCV-15-003 (-PT) 3 0.5 to 5.5<br />
PICCV-15-004 (-PT) 4<br />
PICCV-15-005 (-PT) 5<br />
PICCV-20-006 (-PT) 6<br />
PICCV-20-007 (-PT) 7<br />
PICCV-20-008 (-PT) 8 2 to 10<br />
PICCV-20-009 (-PT) 9<br />
PICCV-20-010 (-PT) 10<br />
PICCV-25-012 (-PT) 12<br />
PICCV-25-014 (-PT) 14 2 to 16<br />
PICCV-25-016 (-PT) 16<br />
Procedure:<br />
(1) Adjust valve to its full<br />
rated GPM opening.<br />
(2) Measure pressure<br />
across P/T ports.<br />
(3) For default flow rate,<br />
compare DeltaP to<br />
chart value.<br />
P/T ports to<br />
verify flow<br />
PICCV-25-018 (-PT) 18 6 to 19<br />
*The indicated default flows are maximum flow values at 100%<br />
actuator travel. However, the PICCV maintains a steady flow<br />
at any degree of ball opening and balances the system<br />
dynamically from 0 to 100% of the heating or cooling load.<br />
**Specified accuracy not guaranteed.<br />
Field Adjustable Flow Ranges and<br />
P/T Port <strong>Pressure</strong> Flow Data<br />
P/T Port <strong>Pressure</strong> Flow Data<br />
Model # Flow Rate DeltaP across<br />
Valve (GPM) P/T Ports<br />
PICCV-15-0.50 (-PT) 0.5 3.0 - 3.9<br />
PICCV-15-001 (-PT) 1 2.95 - 3.4<br />
PICCV-15-0.50 (-PT) 0.5 3.3 - 4.7 NEW ♦<br />
PICCV-15-001 (-PT) 1 3.0 - 4.4 NEW ♦<br />
PICCV-15-1.50 (-PT) 1.5 2.5 - 5.5<br />
PICCV-15-002 (-PT) 2 2.5 - 5.5<br />
PICCV-15-003 (-PT) 3 2.0 - 3.2<br />
PICCV-15-004 (-PT) 4 1.9 - 2.7<br />
PICCV-15-005 (-PT) 5 1.5 - 2.4<br />
PICCV-20-006 (-PT) 6 2.5 - 3.0<br />
PICCV-20-007 (-PT) 7 2.5 - 2.8<br />
PICCV-20-008 (-PT) 8 2.2 - 2.6<br />
PICCV-20-009 (-PT) 9 1.6 - 2.4<br />
PICCV-20-010 (-PT) 10 0.0 - 2.3<br />
PICCV-25-012 (-PT) 12 2.75 - 3.2<br />
PICCV-25-014 (-PT) 14 2.4 - 2.8<br />
PICCV-25-016 (-PT) 16 1.45 - 1.75<br />
PICCV-25-018 (-PT) 18 1.20 - 1.70<br />
PICCV-32-018-PT 18 3.35 - 3.65<br />
PICCV-32-020-PT 20 3.0 - 3.5<br />
PICCV-32-022-PT 22 2.85 - 3.5<br />
PICCV-32-024-PT 24 2.85 - 3.65<br />
PICCV-32-026-PT 26 3.0 - 3.85<br />
PICCV-40-026-PT 26 3.1 - 3.9<br />
PICCV-40-028-PT 28 3.1 - 3.8<br />
PICCV-40-030-PT 30 3.0 - 3.4<br />
PICCV-40-033-PT 33 2.9 - 3.7<br />
PICCV-50-033-PT 33 2.1 - 2.95<br />
PICCV-50-036-PT 36 2.0 - 2.9<br />
PICCV-50-040-PT 40 2.0 - 2.85<br />
PICCV-50-044-PT 44 3.5 - 4.0<br />
PICCV-50-048-PT 48 2.0 - 4.0<br />
PICCV-50-052-PT 52 2.2 - 3.2<br />
PICCV-50-056-PT 56 1.2 - 3.0<br />
PICCV-50-060-PT 60 1.2 - 2.5<br />
PICCV-50-065-PT 65 1.0 - 3.0<br />
PICCV-50-070-PT 70 1.0 - 2.9<br />
PICCV-50-075-PT 75 1.0 - 2.5<br />
PICCV-50-080-PT 80 1.3 - 3.0<br />
PICCV-50-090-PT 90 2.6 - 3.8<br />
PICCV-50-100-PT 100 2.0 - 3.4<br />
♦ Please use “NEW” readings if order was placed after<br />
July 24, 2007.<br />
51
Field Adjustable Flow Ranges and<br />
P/T Port <strong>Pressure</strong> Flow Data for Customized Flows<br />
Field Adjustable Flow Ranges<br />
with the LRB24-3 and FlowSetR<br />
Default<br />
Model # Flow Rate Field Adjustable<br />
Valve (GPM)* Design Flow (GPM)**<br />
PICCV-15-2.50 (-PT) 2.5<br />
PICCV-15-3.50 (-PT)<br />
PICCV-15-4.50 (-PT)<br />
3.5<br />
4.5<br />
0.5 to 5.5<br />
PICCV-15-5.50 (-PT) 5.5<br />
PICCV-20-6.50 (-PT) 6.5<br />
PICCV-20-7.50 (-PT) 7.5<br />
PICCV-20-8.50 (-PT) 8.5<br />
PICCV-20-9.50 (-PT) 9.5<br />
52<br />
Procedure:<br />
(1) Adjust valve to its full<br />
rated GPM opening.<br />
(2) Measure pressure<br />
across P/T ports.<br />
(3) For default flow rate,<br />
compare DeltaP to<br />
chart value.<br />
P/T ports to<br />
verify flow<br />
2 to 10<br />
PICCV-25-011 (-PT) 11<br />
PICCV-25-013 (-PT) 13 2 to 16<br />
PICCV-25-015 (-PT) 15<br />
PICCV-25-017 (-PT) 17<br />
6 to 19<br />
PICCV-25-019 (-PT) 19<br />
*The indicated default flows are maximum flow values at 100%<br />
actuator travel. However, the PICCV maintains a steady flow<br />
at any degree of ball opening and balances the system<br />
dynamically from 0 to 100% of the heating or cooling load.<br />
**Specified accuracy not guaranteed.<br />
P/T Port <strong>Pressure</strong> Flow Data<br />
Model # Flow Rate DeltaP across<br />
Valve (GPM) P/T Ports<br />
PICCV-15-2.50 (-PT) 2.5 2.0 - 3.2<br />
PICCV-15-3.50 (-PT) 3.5 1.9 - 2.7<br />
PICCV-15-4.50 (-PT) 4.5 1.5 - 2.4<br />
PICCV-15-5.50 (-PT) 5.5 1.5 - 2.4<br />
PICCV-20-6.50 (-PT) 6.5 2.5 - 2.8<br />
PICCV-20-7.50 (-PT) 7.5 2.2 - 2.6<br />
PICCV-20-8.50 (-PT) 8.5 1.6 - 2.4<br />
PICCV-20-9.50 (-PT) 9.5 0.0 - 2.3<br />
PICCV-25-011 (-PT) 11 2.75 - 3.2<br />
PICCV-25-013 (-PT) 13 2.4 - 2.8<br />
PICCV-25-015 (-PT) 15 1.45 - 1.75<br />
PICCV-25-017 (-PT) 17 1.20 - 1.70<br />
PICCV-25-019 (-PT) 19 1.20 - 1.70<br />
PICCV-32-019-PT 19 3.0 - 3.5<br />
PICCV-32-021-PT 21 2.85 - 3.5<br />
PICCV-32-023-PT 23 2.85 - 3.65<br />
PICCV-32-025-PT 25 3.0 - 3.85<br />
PICCV-40-027-PT 27 3.1 - 3.8<br />
PICCV-40-029-PT 29 3.0 - 3.4<br />
PICCV-40-031-PT 31 2.9 - 3.7<br />
PICCV-40-032-PT 32 2.9 - 3.7<br />
PICCV-50-034-PT 34 2.0 - 2.9<br />
PICCV-50-035-PT 35 2.0 - 2.9<br />
PICCV-50-037-PT 37 2.0 - 2.9<br />
PICCV-50-038-PT 38 2.0 - 2.9<br />
PICCV-50-039-PT 39 2.0 - 2.9<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Customized Flows*<br />
® Available<br />
PICCV’s are available in a wide variety of the standard maximum<br />
flow rates as listed. This allows you to match the design<br />
flow rate much more accurately then it was possible with the<br />
selection of Cv-value of a conventional valve. If you want to<br />
customize the maximum flow rate of a PICCV you can do so,<br />
as noted in the increments in the table below. In an additional<br />
process we will set the PICCV to a specific flow rate to match<br />
your design flow, as noted in the table below. The smallest<br />
available increment is 0.50 GPM and the smallest flow is<br />
0.50 GPM.<br />
Customized Flows and<br />
Certified Factory Calibrated Flows<br />
Certified Factory Calibrated Flows† (ZP-PICCV-CAL)<br />
Valve Size GPM Custom Flow Rates Actuator selections<br />
1/2” 2.5, 3.5, 4.5, 5.5<br />
LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />
TF24-MFT US, LF24-MFT US, AF24-MFT US<br />
3/4” 6.5, 7.5, 8.5, 9.5<br />
LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />
LF24-MFT US, AF24-MFT US<br />
1” 11, 13, 15, 17, 19<br />
LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />
LF24-MFT US, AF24-MFT US<br />
1-1/4” 19, 21, 23, 25 ARX24-MFT, AF24-MFT US<br />
1-1/2” 27, 29, 31, 32 ARX24-MFT, AF24-MFT US<br />
2” 34, 35, 37, 38, 39 ARX24-MFT, AF24-MFT US<br />
ORDERING EXAMPLE<br />
1<br />
2<br />
Available Customized Flows*<br />
Choose the desired valve/actuator combination<br />
based on valve ratings and actuator control<br />
parameters.<br />
PICCV-15-3.50-PT + LRX24-MFT<br />
Specify Configuration (important)<br />
• Multi-Function Technology: P-10019 (2-10 VDC input / 2-10 VDC feedback)<br />
• Set-up: NC (Normally Closed)<br />
• Tagging: AHU<br />
• Calibration Charge: ZP-PICCV-CAL<br />
Factory calibrated PICCV’s will be programmed to a customized<br />
flow setting as mentioned in the opposite paragraph.<br />
Additionally, each single valve will be installed in a calibration<br />
rig to verify the flow rate with a high quality flow measurement<br />
device, calibrated to the requirements of ANSI/ISA -75.02-<br />
1996, with traceability to NIST standards. For each PICCV<br />
calibrated you will receive a test certificate. Using this procedure<br />
allows for the highest flow accuracy in the field.<br />
†Operating pressure ranges are 5-10 psi,10-30 psi, 30-50 psi.<br />
Default pressure range is 5-30 psi.<br />
Expected flow accuracy ±5% (related to nominal valve flow).<br />
This service is available for the 1/2” to 1-1/4” PICCV15-0.50 (-PT)<br />
to PICCV-32-026-PT.<br />
*Part numbers for the<br />
valve body custom flows<br />
are noted in the charts<br />
on page 52. Actuator<br />
selections are the same<br />
as the standard offerings.<br />
PICCV-15-3.50+LRX24-MFT+P-10019+NC+AHU+ZP-PICCV-CAL<br />
53
PICCV Running Times<br />
All MFT actuators have constant running time of 100 seconds. Whether they are set for on/off, floating<br />
or proportional control, the running time remains constant.<br />
Note for Floating Point Control with LRB24-3: These actuators have a constant running time. The running<br />
time is dependent on the model number or FlowSetR position as indicated in the table below.<br />
Some DDC controllers need an adjustment of the running time, otherwise they lose the position information.<br />
In any case, we recommend a position reset once a day.<br />
Running Time (sec.) Running Time (sec.)<br />
Model # Flow Rate LRX24-MFT, ARX24-MFT<br />
Valve (GPM) LRB24-3 TF24-MFT US, LF24-MFT US, AF24-MFT US<br />
PICCV-15-0.50 (-PT) 0.5 36 100<br />
PICCV-15-001 (-PT) 1 60 100<br />
PICCV-15-1.50 (-PT) 1.5 45 100<br />
PICCV-15-002 (-PT) 2 51 100<br />
PICCV-15-003 (-PT) 3 56 100<br />
PICCV-15-004 (-PT) 4 63 100<br />
PICCV-15-005 (-PT) 5 68 100<br />
PICCV-20-006 (-PT) 6 61 100<br />
PICCV-20-007 (-PT) 7 64 100<br />
PICCV-20-008 (-PT) 8 67 100<br />
PICCV-20-009 (-PT) 9 69 100<br />
PICCV-20-010 (-PT) 10 76 100<br />
PICCV-25-012 (-PT) 12 62 100<br />
PICCV-25-014 (-PT) 14 67 100<br />
PICCV-25-016 (-PT) 16 86 100<br />
PICCV-25-018 (-PT) 18 67 100<br />
PICCV-32-018-PT 18 na 100<br />
PICCV-32-020-PT 20 na 100<br />
PICCV-32-022-PT 22 na 100<br />
PICCV-32-024-PT 24 na 100<br />
PICCV-32-026-PT 26 na 100<br />
PICCV-40-026-PT 26 na 100<br />
PICCV-40-028-PT 28 na 100<br />
PICCV-40-030-PT 30 na 100<br />
PICCV-40-033-PT 33 na 100<br />
PICCV-50-033-PT 33 na 100<br />
PICCV-50-036-PT 36 na 100<br />
PICCV-50-040-PT 40 na 100<br />
PICCV-50-044-PT 44 na 100<br />
PICCV-50-048-PT 48 na 100<br />
PICCV-50-052-PT 52 na 100<br />
PICCV-50-056-PT 56 na 100<br />
PICCV-50-060-PT 60 na 100<br />
PICCV-50-065-PT 65 na 100<br />
PICCV-50-070-PT 70 na 100<br />
PICCV-50-075-PT 75 na 100<br />
PICCV-50-080-PT 80 na 100<br />
PICCV-50-090-PT 90 na 100<br />
PICCV-50-100-PT 100 na 100<br />
54<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® PICCV<br />
Customized Flow Rate Running Times<br />
Running Time (sec.) Running Time (sec.)<br />
Model # Flow Rate LRX24-MFT, ARX24-MFT<br />
Valve (GPM) LRB24-3 TF24-MFT US, LF24-MFT US, AF24-MFT US<br />
PICCV-15-2.50 (-PT) 2.5 53 100<br />
PICCV-15-3.50 (-PT) 3.5 58 100<br />
PICCV-15-4.50 (-PT) 4.5 66 100<br />
PICCV-15-5.50 (-PT) 5.5 73 100<br />
PICCV-20-6.50 (-PT) 6.5 62 100<br />
PICCV-20-7.50 (-PT) 7.5 66 100<br />
PICCV-20-8.50 (-PT) 8.5 68 100<br />
PICCV-20-9.50 (-PT) 9.5 71 100<br />
PICCV-25-011 (-PT) 11 60 100<br />
PICCV-25-013 (-PT) 13 64 100<br />
PICCV-25-015 (-PT) 15 69 100<br />
PICCV-25-017 (-PT) 17 65 100<br />
PICCV-25-019 (-PT) 19 78 100<br />
PICCV-32-019-PT 19 na 100<br />
PICCV-32-021-PT 21 na 100<br />
PICCV-32-023-PT 23 na 100<br />
PICCV-32-025-PT 25 na 100<br />
PICCV-40-027-PT 27 na 100<br />
PICCV-40-029-PT 29 na 100<br />
PICCV-40-031-PT 31 na 100<br />
PICCV-40-032-PT 32 na 100<br />
PICCV-50-034-PT 34 na 100<br />
PICCV-50-035-PT 35 na 100<br />
PICCV-50-037-PT 37 na 100<br />
PICCV-50-038-PT 38 na 100<br />
PICCV-50-039-PT 39 na 100<br />
55
Instructions for Field Adjustment of Flow and<br />
Valve Sizing and Selection<br />
Instructions for Non-Spring Actuator Utilizing the FlowSetR<br />
Non-Spring Return Actuator: LRB24-3<br />
Default set-up:<br />
FlowSetR<br />
The factory setting corresponds to the ordered flow rate<br />
(selected from Belimo’s standard product range).<br />
The valves factory setting is in open position (valve always<br />
closes in CW direction).<br />
To set or adjust desired maximum flow (actuator,<br />
FlowSetR and valve are connected):<br />
1. Fully close the valve via actuator control signal or via manual<br />
override (press button and turn handle in clockwise direction).<br />
Note: The FlowSetR fixed clockwise end stop purposely<br />
prevents the actuator from returning to its full zero-degree<br />
position, eliminating excess rotation.<br />
2. Use the integrated hex tool in the actuator lever to turn adjustment<br />
screw in plus (+) or minus (-) direction in order to move<br />
scale indicator to desired flow rate. A standard hex tool (i.e.<br />
Allen wrench) size 5/32” or 4mm can also be used to turn<br />
adjustment screw.<br />
Sizing and Selection of PICCVs<br />
To select the proper flow rate and actuation for<br />
your application:<br />
Sizing of the <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control<br />
Valves is based on GPM, and there is no need to calculate Cv<br />
rating. <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves are<br />
2-way valves that operate between a 5-50 PSI operating range.<br />
For example: If an application requires 4 GPM:<br />
Select the valve rated for 4 GPM. In the catalog, this part<br />
number is the PICCV-15-004.<br />
For example: If you wish to narrow the flow to 3.5 GPM:<br />
Narrowing the flow to 3.5 GPM can be achieved with the use<br />
of the FlowSetR if you have the LRB24-3 actuator. With the<br />
use of a 5/32" or 4 mm hex tool, the flow can be adjusted in<br />
the field. For all other MFT actuators, you may reprogram to<br />
3.5 GPM using the PC software and following the MFT guidelines.<br />
Note: Please note that PICCV bodies have a range of flow.<br />
Consult page 51 and 52 for details.<br />
56<br />
PICCV flow can be field adjusted by using a hex tool.<br />
Therefore, the maximum flow can be increased or<br />
decreased within the valves adjustable flow range.<br />
Integrated<br />
Hex Tool<br />
FlowSetR<br />
Adjustable<br />
with hex tool<br />
size 5/32” [4mm]<br />
Avoid disconnecting FlowSetR from actuator or valve! If necessary, refer to instruction sheet<br />
on how to install FlowSetR to valve, and actuator to FlowSetR.<br />
GPM<br />
For example, the valve body PICCV-15-001 can maintain flows<br />
from 0.50 GPM to 1.0 GPM, and the PICCV-15-005 can maintain<br />
flows between 1.5 GPM to 5.5 GPM.<br />
There will be two <strong>Pressure</strong>/Temperature ports as a standard<br />
offering for the 1-1/4" valves and larger, and available as an<br />
option for the 1" valves and smaller. The <strong>Pressure</strong>/Temperature<br />
ports will be reflected in the part number as "PT".<br />
i.e PICCV-15-004-PT + LF24-MFT US.<br />
The remaining step is to select the type of actuation, based on<br />
your requirements.<br />
Prior to ordering, please provide whether you wish to have the<br />
valve normally open or normally closed, and if spring return<br />
actuation is required, please note whether the valve is to<br />
spring open or spring closed upon power loss.<br />
For example: If your application for the above valve requires<br />
spring return, 2-10 VDC input signal, 100 sec run time and 2-10<br />
VDC feedback signal, select LF24-MFT US and MFT programming<br />
code P-10019.<br />
0.5<br />
Sample scale<br />
PICCV-15-001<br />
On Floating Point actuators, the running time is constant but<br />
dependent on the overall angle of rotation.<br />
1<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
1. Verify that the system is purged and filled to the<br />
proper pressure.<br />
2. Verify pump rotation.<br />
® PICCV<br />
PICCV Test and Balance Procedure<br />
3. Open all valves through the building management<br />
system if the total connected load➀ matches the pump<br />
GPM. Systems with diversity must have a percent of<br />
the valves closed to match the pump GPM.<br />
4. Test total flow by accurate method.*<br />
5. Decrease the pump speed until a flow decrease occurs.<br />
6. Increase the pump speed until the original flow is<br />
reestablished.<br />
PICCV Troubleshooting<br />
1. Is the pump on and rotating properly?<br />
2. Is the pressure differential adequate to produce<br />
design GPM?<br />
3. Is the water temperature at the required level?<br />
4. Is the PICCV installed in the right direction?<br />
5. Is there too much diversity in the system?<br />
6. Does the valve tag GPM match the listed design GPM?<br />
7. Does the ATC signal stroke the valve in the<br />
right direction?<br />
8. Are strainers plugged?<br />
9. Is the coil installed counterflow?<br />
10. Discharge temperature not to required rating:<br />
A. Is reset temperature high enough?<br />
B. Is air by-passing the coil?<br />
C. Are all coil areas heating/cooling uniformly?<br />
11. Room cold complaints:<br />
A. Is there enough throw➁ to penetrate air to the<br />
occupancy level?<br />
➁Throw is the distance discharge air is propelled<br />
in order to reach the occupant level.<br />
B. Test discharge air temperature and stratification.<br />
C. Is the building under a negative pressure?<br />
D. Is the hot water temperature at design?<br />
Resets may not be effective for reheat coils.<br />
Test and Balance Procedure,<br />
Troubleshooting<br />
7. Record system ΔP and provide this value to the<br />
ATC contractor.<br />
8. Perform a “Practical Test” to verify that the designer’s<br />
intent has been met. Taking a leaving air temperature<br />
can quickly verify the operation.<br />
*Accurate Methods<br />
Calibrated circuit setters on main lines<br />
Orifice<br />
Venturi<br />
Equipment pressure drops if the components are clean<br />
Ultrasonic Flowmeter<br />
Pump curves and triple duty valves have less<br />
accuracy than the above listed items<br />
GOOD IDEAS:<br />
Install taps on at least one valve with the largest<br />
DP requirement, or near the end run or near<br />
the DP transmitter.<br />
➀Total connected load is the summation of all<br />
terminal GPM.<br />
Often, engineers will design a pumping system for the<br />
total GPM as listed for all of the coils.<br />
Some engineers will take advantage of diversity and<br />
realize that no more than ± 80% of the valves will be<br />
calling at any one time during normal operation.<br />
For instance, if you have 100 GPM of total<br />
connected load, a pump sized for 80 GPM could<br />
be installed. In this case, if all valves open after<br />
a weekend of being closed, none of the valves will<br />
handle the design flow rate. A requirement of 20%<br />
of the valves would have to be closed to match the<br />
pump to the total connected load.<br />
57
Parallel Piping the PICCV<br />
to Achieve an Increase in Flow Rate<br />
Typical Parallel Piping in Relation<br />
to The Input and Output (Scale: None)<br />
58<br />
H/C–COIL<br />
H/C–COIL<br />
AIR VENT<br />
FLOW<br />
FLOW<br />
DRAIN<br />
Typical Piping in Relation<br />
to The Input and Output (Scale: None)<br />
AIR VENT<br />
DRAIN<br />
P/T PORT<br />
P/T PORT<br />
FLOW<br />
P/T PORT<br />
BELIMO PICCV (TYP.)<br />
FLOW<br />
FLOW<br />
BELIMO PICCV (TYP.)<br />
UNION CONNECTION (TYP.)<br />
P/T PORT<br />
P/T PORT<br />
FLOW<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves can<br />
be be piped in a parallel orientation to achieve increased flow<br />
rates.<br />
Our PICCV valves are available in flows to 100 GPM. To<br />
achieve flows larger than this, it is recommended to connect<br />
two of these valves in parallel leading to a common manifold.<br />
To correctly operate these valves, the Belimo Multi Function<br />
Technology (MFT) will be employed to utilize one common<br />
control signal.<br />
For example, the first valve will be outfitted with an MFT actuator<br />
that will correspond to a 2-5 or 2.6 VDC signal. The second<br />
valve would be outfitted with an MFT actuator that would correspond<br />
to a 6-10 VDC signal. Therefore, through a single 2-10<br />
VDC output, the full flow range will be achieved. The actuators<br />
will be wired in a parallel arrangement. The established configured<br />
P Codes are P-10137 for 2-5 VDC, P-10118 for 2-6 VDC,<br />
and P-10119 for 6-10 VDC.<br />
This recommended application provides the control of flows up<br />
to 200 GPM by using two valves. The top diagram details<br />
valves piped in a parallel arrangement. The bottom diagram<br />
features a typical single piping arrangement.<br />
PARALLEL PIPING ARRANGEMENT<br />
FOR PICCV VALVES<br />
P/T PORT<br />
P/T PORT<br />
STRAINER<br />
P/T PORT P/T PORT<br />
FLOW<br />
FLOW<br />
FLOW FLOW<br />
STRAINER<br />
UNION CONNECTION (TYP.)<br />
FLOW<br />
FLOW<br />
TYPICAL PARALLEL PIPING IN RELATION<br />
TO THE INPUT AND OUTPUT<br />
SHUT–OFF<br />
VALVE<br />
SHUT–OFF<br />
VALVE<br />
TEE (TYP.)<br />
SHUT–OFF<br />
VALVE<br />
SHUT–OFF<br />
VALVE<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Dimension with LRB24-3, LRX24-3<br />
2.6"<br />
[66]<br />
E F<br />
3.22"<br />
[82]<br />
Dimensions with LRB24-3, LRX24-3 with P/T Ports<br />
Dimensions with ARX24-MFT with P/T ports<br />
D<br />
1.69"<br />
[42]<br />
Dimensions–<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with Non-Spring Return Actuator<br />
6.5" [165]<br />
B<br />
A<br />
0.78" [20]<br />
C<br />
2.34"<br />
[59.4]<br />
FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
3/4" NPT 5.25 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />
1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />
2.6"<br />
[66]<br />
E F<br />
3.22"<br />
[82]<br />
D<br />
1.69"<br />
[42]<br />
6.5" [165]<br />
B<br />
A<br />
C<br />
2.34"<br />
[59.4]<br />
0.78" [20] FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />
3.46"<br />
[88]<br />
2.5"<br />
[64]<br />
E F<br />
3.3"<br />
[84]<br />
D<br />
1.35"<br />
[35]<br />
8.0" [203]<br />
B<br />
A<br />
C<br />
2.49"<br />
[63.4]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1-1/4" NPT 8.75 [222] 8.75 [222] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />
1-1/2" NPT 8.00 [203] 8.00 [203] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />
2" NPT* 8.5 [216] 8.5 [216] 6.62 [168] 4.4 [112] 1.77 [45] 3.03 [77]<br />
*Flows to 40 GPM.<br />
D146<br />
D147<br />
D158<br />
Dimensions with LRX24-MFT<br />
2.6"<br />
[66] 7.5" [191]<br />
D127<br />
E F<br />
Dimensions with LRX24-MFT with P/T Ports<br />
2.6"<br />
[66] 7.5" [191]<br />
D129<br />
E F<br />
3.22"<br />
[82]<br />
3.22"<br />
[82]<br />
D<br />
1.69"<br />
[42]<br />
D<br />
1.69"<br />
[42]<br />
B<br />
A<br />
C<br />
2.34"<br />
[59.4]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />
B<br />
A<br />
C<br />
2.34"<br />
[59.4]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
3/4" NPT 5.25 [133] 5.03 [128] 4.22 [107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />
1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />
Dimensions with ARX24-MFT with P/T ports<br />
3.46"<br />
[88]<br />
2.5"<br />
[64]<br />
E F<br />
2.49"<br />
[63.4]<br />
C<br />
D<br />
8.0" [203]<br />
H<br />
3.3"<br />
1.35"<br />
[84]<br />
[35]<br />
BELIMO<br />
DN 50<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve* A B C D E F G H<br />
2" NPT 16.39 [416.2] 15.6 [396.2] 9.38 [238.3] 6.31 [160.3] 2.65 [67.3] 3.05 [77.5] 13.27 [337.1] 20.6 [523.24]<br />
B<br />
A<br />
2<br />
G<br />
D159<br />
2" NPT with larger flows from 44 GPM to 100 GPM<br />
59
Dimensions–<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with Spring Return Actuator<br />
TF24-MFT US<br />
LF24-MFT US<br />
60<br />
3.0"<br />
[76.2]<br />
E F<br />
3.78"<br />
[96]<br />
E F<br />
4.49"<br />
[114]<br />
D<br />
B<br />
A<br />
7.64"<br />
[194]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
3/4" NPT 5.25 [133] 5.03 [128] 4.22 [107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />
1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />
C<br />
2.28"<br />
[58]<br />
D128<br />
AF24-MFT US with P/T ports<br />
E F<br />
LF24-MFT US with P/T ports AF24-MFT US with P/T ports<br />
3.78"<br />
[96]<br />
E F<br />
2.93"<br />
[74.5]<br />
D<br />
4.49"<br />
[114]<br />
D<br />
B<br />
A<br />
6.28"<br />
[159.55]<br />
B<br />
A<br />
7.64"<br />
[194]<br />
C<br />
2.40"<br />
[61]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />
C<br />
2.28"<br />
[58]<br />
D189<br />
D130<br />
TF24-MFT US with P/T ports<br />
3.0"<br />
[76.2]<br />
E F<br />
3.86"<br />
[98]<br />
3.86"<br />
[98] 2.24"<br />
[57]<br />
E F<br />
2.93"<br />
[74.5]<br />
C<br />
D<br />
3.66"<br />
[93]<br />
D<br />
D<br />
10.47"<br />
[266]<br />
6.28"<br />
[159.55]<br />
B<br />
A<br />
H<br />
3.66"<br />
[93]<br />
10.47"<br />
[266]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1-1/4" NPT 8.75 [222] 8.75 [222] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />
1-1/2" NPT 8.0 [203] 8.0 [203] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />
2" NPT 8.5 [216] 8.5 [216] 6.62 [168] 4.4 [112] 1.77 [45] 3.03 [77]<br />
*Flows to 40 GPM.<br />
BELIMO<br />
DN 50<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve* A B C D E F G H<br />
2" NPT 16.39 [416.2] 15.6 [396.2] 9.38 [238.3] 6.31 [160.3] 2.65 [67.3] 3.05 [77.5] 12.92 [328.2] 21.9 [556.3]<br />
2<br />
B<br />
A<br />
C<br />
2.40"<br />
[61]<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
B<br />
A<br />
C<br />
2.24"<br />
[57]<br />
G<br />
D190<br />
D132<br />
D125<br />
2" NPT with larger flows from 44 GPM to 100 GPM<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
W431<br />
On/Off<br />
1<br />
Line<br />
Volts<br />
1<br />
2<br />
®<br />
24 VAC Transformer<br />
a open<br />
a closed<br />
The indication of direction<br />
is valid for switch position 1.<br />
Notes:<br />
a<br />
2 3 4 5<br />
Blk (1) Common<br />
Red (2) +<br />
Wht (3) +<br />
1 0<br />
Provide overload protection and disconnect as required.<br />
3 Actuators may also be powered by 24 VDC.<br />
LRB24-3…<br />
Actuators may be connected in parallel. Power<br />
consumption and input impedance must be observed.<br />
Wiring Diagrams for LRB24-3 Actuator<br />
Floating Point<br />
5<br />
1<br />
Line<br />
Volts<br />
24 VAC Transformer<br />
The indication of direction<br />
is valid for switch position 1.<br />
2 3 4 5<br />
Blk (1) Common<br />
Red (2) +<br />
Wht (3) +<br />
1 0<br />
LRB_24-3…<br />
4 Meets cULus or UL and CSA requirements without<br />
the need of an electrical ground connection.<br />
Actuators with plenum rated cable do not have<br />
numbers on wires; use color codes instead.<br />
Actuators with appliance cables are numbered.<br />
61
Wiring Diagrams for LRX24-MFT and ARX24-MFT Actuators<br />
VDC/4-20 mA<br />
Floating Point<br />
PWM<br />
62<br />
Actuators: LMX, LRX, NMX, AMX, ARX, GMX24-MFT<br />
Hazard Identification<br />
Warnings and Cautions appear at appropriate sections throughout<br />
INSTALLATION NOTES<br />
this manual. Read these carefully.<br />
3 Actuators may also be powered by 24 VDC.<br />
CAUTION<br />
Indicates a potentially hazardous situation which, if not avoided,<br />
may result in minor or moderate injury. It may also be used to<br />
5<br />
alert against unsafe practices.<br />
8<br />
2<br />
Equipment damage!<br />
Actuators may be connected in parallel if not mechanically<br />
mounted to the same shaft. Power consumption and input<br />
impedance must be observed.<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing,<br />
servicing and troubleshooting<br />
of this product, it maybe<br />
necessary to work with live<br />
electrical components. Have a<br />
qualified licensed electrician or<br />
other individual who has been<br />
Line<br />
Volts<br />
Control Signal<br />
4 to 20 mA<br />
or<br />
2 to 10 VDC<br />
Line<br />
Volts<br />
24 VAC Transformer<br />
(–)<br />
(+)<br />
24 VAC Transformer (AC only)<br />
Position (–)<br />
Feedback VDC (+)<br />
Ω 500Ω<br />
1/4 watt<br />
properly trained in handling live electrical components perform these tasks.<br />
Failure to follow all electrical safety precautions when exposed<br />
to live electrical components could result in death or serious injury.<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing,<br />
servicing and troubleshooting<br />
of this product, it maybe<br />
necessary to work with live<br />
electrical components. Have a<br />
qualified licensed electrician or<br />
other individual who has been<br />
properly trained in handling live<br />
electrical components perform these<br />
tasks. Failure to follow all electrical safety<br />
precautions when exposed to live electrical<br />
components could result in death or serious injury.<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing,<br />
servicing and troubleshooting<br />
of this product, it maybe<br />
necessary to work with live<br />
electrical components. Have a<br />
qualified licensed electrician or<br />
other individual who has been<br />
Line<br />
Volts<br />
7<br />
24 VAC Transformer<br />
properly trained in handling live electrical components perform these tasks.<br />
Failure to follow all electrical safety precautions when exposed to live electrical<br />
components could result in death or serious injury.<br />
8<br />
2 to 10 VDC<br />
Feedback Signal<br />
A<br />
B<br />
9<br />
11<br />
Direction of rotation switch<br />
CCW<br />
CCW<br />
CW<br />
CW<br />
A B 5<br />
8<br />
A B 5<br />
2<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y1 Input, 2 to 10V<br />
Grn (5) U Output, 2 to 10V<br />
CCW CW<br />
2<br />
2<br />
3 5<br />
3<br />
Blk (1) Common –<br />
Red (2) Hot + 10<br />
Wht (3) Y1 Input<br />
Pnk (4) Y2 Input<br />
Org (5) U Output 2 to 10V<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y Input<br />
Org (5) U Output<br />
7<br />
9<br />
11<br />
10<br />
Two Position<br />
Actuators with plenum rated cable do not have numbers on<br />
wires; use color codes instead. Actuators with appliance<br />
cables are numbered.<br />
Control signal may be pulsed from either the Hot (Source)<br />
or Common (Sink) 24 VAC line.<br />
For triac sink the Common connection from the actuator<br />
must be connected to the Hot connection of the controller.<br />
APPLICATION NOTES<br />
Meets cULus or UL and CSA requirements without<br />
the need of an electrical ground connection.<br />
A 500Ω resistor converts the 4 to 20 mA control signal<br />
to 2 to 10 VDC.<br />
Contact closures A & B also can be triacs. A & B should<br />
both be closed for triac source and open for triac sink.<br />
Position feedback cannot be used with a Triac sink controller.<br />
The actuator internal common reference is not compatible.<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing,<br />
24 VAC/DC Transformer<br />
servicing and troubleshooting Line<br />
of this product, it maybe necessary<br />
to work with live electrical<br />
Volts<br />
components. Have a qualified<br />
licensed electrician or other<br />
Position (–)<br />
a<br />
individual who has been properly<br />
trained in handling live electrical<br />
Feedback VDC (+)<br />
components perform these tasks. Failure to<br />
follow all electrical safety precautions when<br />
exposed to live electrical components could<br />
result in death or serious injury.<br />
Override control to min, mid, max, positions<br />
WARNING<br />
24 VAC Transformer<br />
Live Electrical Components!<br />
During installation, testing,<br />
servicing and trouble<br />
Line<br />
Volts<br />
shooting of this product,<br />
it maybe necessary to<br />
Ω<br />
work with live electrical Control Signal (–)<br />
components. Have a<br />
qualified licensed electrician<br />
or other individual who has<br />
been properly trained in<br />
2-10 VDC or (+)<br />
4 to 20 mA 500Ω<br />
1/4 watt<br />
7<br />
handling live electrical<br />
Min*<br />
components perform these tasks.<br />
Mid*<br />
Failure to follow all electrical safety<br />
Max*<br />
precautions when exposed to live<br />
electrical components could result in<br />
death or serious injury.<br />
Normal**<br />
A<br />
B<br />
C<br />
Functions<br />
0%<br />
50%<br />
100%<br />
Control mode acc. to Y<br />
Blk (1) Common<br />
Red (2) Hot<br />
Wht (3) Y Input<br />
Org (5) U Output<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y 1 Input, 2 to 10V<br />
a b c<br />
* Default selectable 0-100%. See Configuration Data Sheet.<br />
** Customizable. See Configuration Data Sheet.<br />
3<br />
2 3<br />
®<br />
W400<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® Wiring<br />
Wiring Diagrams<br />
Standard Wiring<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
3<br />
Red (2) + Hot 3<br />
Control Signal (–) 2<br />
2 to 10 VDC (+)<br />
Wht (3) Y1 Input, 2 to 10V<br />
2 to 10 VDC Feedback Signal<br />
24 VAC Transformer<br />
1<br />
Line<br />
Volts<br />
3<br />
Control Signal (–) A 2<br />
2 to 10 VDC (+)<br />
A Open = 0 V Position<br />
A Closed = Normal Operation<br />
Override to zero position<br />
Ω<br />
Grn (5) U Output, 2 to 10V<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y 1 Input, 2 to 10V<br />
Override to 10 V position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal (–) B 2<br />
2 to 10 VDC<br />
(+)<br />
C<br />
Wht (3) Y1 Input, 2 to 10V<br />
B Closed = 10 V Position<br />
C Closed = Normal Operation<br />
1<br />
Line<br />
Volts<br />
3<br />
Override control to min, mid, max, positions<br />
24 VAC Transformer<br />
Control Signal (–)<br />
2-10 VDC or (+)<br />
4 to 20 mA 500Ω<br />
1/4 watt<br />
4<br />
A<br />
B<br />
C<br />
CCW(L) CW(R)<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y 1 Input, 2 to 10V<br />
Functions a b c<br />
Min* 0%<br />
Mid* 50%<br />
Max* 100%<br />
Normal** Control mode acc. to Y<br />
* Default selectable 0-100%. See Configuration Data Sheet.<br />
** Customizable. See Configuration Data Sheet.<br />
2 to 10 VDC Control Signal<br />
W024<br />
Diagrams for TF24-MFT US Actuators<br />
24 VAC Transformer<br />
1<br />
Line<br />
Volts<br />
3<br />
Ω 500Ω<br />
1/4 watt<br />
Control Signal<br />
4 to 20 mA<br />
(–)<br />
(+)<br />
4<br />
Standard Wiring<br />
2<br />
Blk (1) Common<br />
Red (2) + Hot<br />
3<br />
Wht (3) Y 1 Input, 2 to 10V<br />
Grn (5) U Output, 2 to 10V<br />
Override to zero position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal (–)<br />
Ω 2<br />
4 to 20 mA (+)<br />
4<br />
A<br />
Wht (3) Y1 Input, 2 to 10V<br />
A Open = 4 mA Position<br />
A Closed = Normal Operation<br />
500Ω<br />
1/4 watt<br />
Override to 20 mA position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal<br />
(–)<br />
4 to 20 mA<br />
(+)<br />
4<br />
Ω<br />
500Ω<br />
1/4 watt<br />
B<br />
C<br />
2<br />
Wht (3) Y1 Input, 2 to 10V<br />
B Closed = 20 mA Position<br />
C Closed = Normal Operation<br />
4 to 20 mA Control Signal<br />
Notes<br />
1<br />
2<br />
3<br />
4<br />
CCW(L) CW(R)<br />
With a 4-20 mA Input, up to 4 actuators may<br />
be wired in parallel. A 2% shift in the signal<br />
is seen when using a 500Ω resistor. Power<br />
consumption must be observed.<br />
Provide overload protection and disconnect as required.<br />
Actuators may be connected in parallel if not mechanically mounted<br />
to the same shaft. Power consumption and input impedance must<br />
be observed.<br />
Actuator may also be powered by 24 VDC.<br />
ZG-R01 may be used.<br />
W025<br />
63
Wiring Diagrams for LF24-MFT US<br />
and AF24-MFT US Actuators<br />
64<br />
Standard Wiring<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
3<br />
Red (2) + Hot 3<br />
Control Signal (–) 2<br />
2 to 10 VDC (+)<br />
Wht (3) Y1 Input, 2 to 10V<br />
2 to 10 VDC Feedback Signal<br />
24 VAC Transformer<br />
1<br />
Line<br />
Volts<br />
3<br />
Control Signal (–) A 2<br />
2 to 10 VDC (+)<br />
A Open = 0 V Position<br />
A Closed = Normal Operation<br />
Override to zero position<br />
Ω<br />
Wht (5) U Output, 2 to 10V<br />
CCW(L) CW(R)<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y 1 Input, 2 to 10V<br />
Override to 10 V position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal (–) B 2<br />
2 to 10 VDC<br />
(+)<br />
C<br />
Wht (3) Y1 Input, 2 to 10V<br />
B Closed = 10 V Position<br />
C Closed = Normal Operation<br />
1<br />
Line<br />
Volts<br />
3<br />
Override control to min, mid, max, positions<br />
24 VAC Transformer<br />
Control Signal (–)<br />
2-10 VDC or<br />
4 to 20 mA<br />
(+)<br />
500Ω<br />
4<br />
1/4 watt<br />
Min*<br />
Mid*<br />
Functions<br />
0%<br />
50%<br />
A<br />
B<br />
C<br />
Blk (1) Common<br />
Red (2) + Hot<br />
Wht (3) Y 1 Input, 2 to 10V<br />
a b c<br />
Max* 100%<br />
Normal** Control mode acc. to Y<br />
* Default selectable 0-100%. See Configuration Data Sheet.<br />
** Customizable. See Configuration Data Sheet.<br />
2 to 10 VDC Control Signal<br />
W012<br />
24 VAC Transformer<br />
1<br />
Line<br />
Volts<br />
3<br />
Ω 500Ω<br />
1/4 watt<br />
Control Signal<br />
4 to 20 mA<br />
(–)<br />
(+)<br />
4<br />
Standard Wiring<br />
2<br />
Blk (1) Common<br />
Red (2) + Hot<br />
3<br />
Wht (3) Y 1 Input, 2 to 10V<br />
Wht (5) U Output, 2 to 10V<br />
Override to zero position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal (–)<br />
Ω 2<br />
4 to 20 mA (+)<br />
4<br />
A<br />
Wht (3) Y1 Input, 2 to 10V<br />
A Open = 4 mA Position<br />
A Closed = Normal Operation<br />
500Ω<br />
1/4 watt<br />
Override to 20 mA position<br />
24 VAC Transformer<br />
1<br />
Line<br />
Blk (1) Common<br />
Volts<br />
Red (2) + Hot<br />
3<br />
Control Signal<br />
(–)<br />
4 to 20 mA<br />
(+)<br />
4<br />
Ω<br />
500Ω<br />
1/4 watt<br />
B<br />
C<br />
2<br />
Wht (3) Y1 Input, 2 to 10V<br />
B Closed = 20 mA Position<br />
C Closed = Normal Operation<br />
4 to 20 mA Control Signal<br />
CCW(L) CW(R)<br />
With a 4-20 mA Input, up to 4 actuators may<br />
be wired in parallel. A 2% shift in the signal<br />
is seen when using a 500Ω resistor. Power<br />
consumption must be observed.<br />
Notes<br />
Provide overload protection and disconnect as required.<br />
1<br />
Actuators may be connected in parallel if not mechanically mounted<br />
2 to the same shaft. Power consumption and input impedance must<br />
be observed.<br />
3<br />
5<br />
6<br />
S1<br />
S2<br />
S3<br />
S4<br />
S5<br />
S6<br />
NC<br />
NO<br />
NC<br />
NO<br />
5°<br />
5<br />
6<br />
25° to 85°<br />
Auxiliary Switch AF24-MFT-S US<br />
4<br />
Actuator may also be powered by 24 VDC.<br />
ZG-R01 may be used.<br />
W014<br />
S1<br />
NC<br />
S2<br />
S3<br />
NO<br />
For end position indication, interlock control, fan startup, etc.,<br />
AF24-MFT-S US incorporates two built-in auxiliary switches:<br />
2 x SPDT, 7A (2.5A) @250 VAC, UL listed, one switch is fixed at +5°,<br />
one is adjustable 25° to 85°.<br />
LF24-MFT-S US incorporates one built-in auxiliary switch:<br />
1 x SPDT, 6A (1.5A) @250 VAC, UL listed, adjustable 0° to 95°.<br />
Meets UL and CSA requirements without the need of an electrical<br />
ground connection.<br />
5<br />
0° to 95°<br />
Auxiliary Switch LF24-MFT-S US<br />
6<br />
®<br />
W013<br />
W026<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® <strong>Pressure</strong><br />
Optimize<br />
Your Heat<br />
Pump<br />
Application<br />
by Using a <strong>Pressure</strong><br />
<strong>Independent</strong><br />
<strong>Characterized</strong><br />
Control Valve<br />
What are the benefits?<br />
A balanced system is achieved<br />
without the need for a balancer to<br />
manually balance each circuit.<br />
Because the system is dynamic<br />
and the PICCV performs dynamic<br />
balancing, Differential <strong>Pressure</strong>s<br />
are no longer an issue to be<br />
concerned with. The PICCV will<br />
maintain a constant flow at part<br />
load and during morning warm-up<br />
when all loops become critical.<br />
With the PICCV, each terminal<br />
gets the required flow, no over-flow<br />
or under-flow at this critical time.<br />
The PICCV allows a mechanic<br />
to easily commission additional<br />
circuits after the initial system is<br />
up and running, again thanks to<br />
dynamic balancing capability. The<br />
PICCV is available in flow rates<br />
from .5 GPM to 19 GPM. Choosing<br />
the right PICCV is as easy as<br />
determining the appropriate flow<br />
for your heat pump and then<br />
choosing the valve that satisfies<br />
the flow requirement.<br />
<strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />
How does it work?<br />
Heat Pump Applications<br />
Keep with the same idea of a conventional heat pump system,<br />
then add the Belimo PICCV (2-way <strong>Pressure</strong> <strong>Independent</strong><br />
<strong>Characterized</strong> Control Valve). Think savings, and not necessarily first<br />
cost of equipment. Add a VFD (with its known and accepted benefits)<br />
and a Belimo PICCV as your flow control valve, and you have now<br />
optimized your system flow for very little additional cost.<br />
expansion<br />
device<br />
expansion<br />
device<br />
refrigerant-to-air<br />
heat exchanger<br />
refrigerant-to-air<br />
heat exchanger<br />
Heat Pump in Heating Mode<br />
refrigerant-to-water<br />
heat exchanger<br />
pump<br />
Heat Pump in Cooling Mode<br />
refrigerant-to-water<br />
heat exchanger<br />
compressor<br />
reversing<br />
valve<br />
pump<br />
compressor<br />
reversing<br />
valve<br />
water<br />
loop<br />
water<br />
loop<br />
65
P2 Series PICCV for Water Source Heat Pumps for Fast Running Time<br />
with Switch Options and On/Off, Non-Spring Return Actuator<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range:<br />
Differential <strong>Pressure</strong><br />
-22°F to 122°F [-30°C to 50°C]<br />
Across Valve Range (ΔP): 5 to 50 psid<br />
Actuator:<br />
Running Time: 40 sec<br />
Power Supply 24 VAC/VDC<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />
Valve Non-Spring Return Actuator<br />
66<br />
Model Valve On/Off<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off<br />
Valve GPM sec Inches mm psi LRCB24-3<br />
PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 66<br />
PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 66<br />
PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 66**<br />
PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 66<br />
PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 66<br />
PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 66<br />
Electrical 3 ft cable<br />
Connection 1/2” conduit fitting<br />
LRCB24-3<br />
LRCB…<br />
Note: Other actuator options including switch options are available. Please contact your Belimo Account Manager or call 877-833-1609 for assistance.<br />
Options (add to list price) LRCB24-3-S<br />
Built-in aux. switch (-S) ❑ Pg 68<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (12 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
P2 Series PICCV for Water Source Heat Pumps for Fast Running Time<br />
with Switch Option and On/Off, Non-Spring Return Actuator<br />
Service: chilled or hot water, 60% glycol<br />
Flow Characteristic: equal percentage<br />
Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />
Ambient Temp Range:<br />
Differential <strong>Pressure</strong><br />
-22°F to 122°F [-30°C to 50°C]<br />
Across Valve Range (ΔP): 5 to 50 psid<br />
Actuator:<br />
Running Time: 40 sec<br />
Power Supply 24 VAC/VDC<br />
Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T Ports, NPT Female Ends<br />
P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T Ports<br />
Valve Non-Spring Return Actuator<br />
Model Valve On/Off<br />
# Flow Rate Nominal Size Close-<br />
PICCV Liter/ DN Off<br />
Valve GPM sec Inches mm psi LRCB24-3<br />
PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 66<br />
PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 66<br />
PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 66<br />
PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 66<br />
PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 66<br />
PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 66<br />
PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 66<br />
PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 66<br />
Electrical 3 ft cable<br />
Connection 1/2” conduit fitting<br />
Options (add to list price) LRCB24-3-S<br />
Built-in aux. switch (-S) ❑ Pg 68<br />
*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />
**1” body has two different disc sizes (12 GPM to 16 GPM) (17 GPM to 19 GPM)<br />
LRCB24-3<br />
LRCB…<br />
67
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with On/Off, Non-Spring Return Actuator, P/T Ports (Optional)<br />
Valve Specifications<br />
Service chilled or hot water, 60% glycol<br />
Flow characteristic equal percentage<br />
Size 1/2”, 3/4”, 1”<br />
Type of end fitting<br />
Materials:<br />
female, NPT<br />
Body forged brass, nickel plated<br />
Ball chrome plated brass<br />
Stem chrome plated brass<br />
Seat O-rings Viton<br />
Seat fiberglass reinforced teflon® PTFE<br />
Characterizing disc TEFZEL®<br />
Packing 2 EPDM O-rings, lubricated<br />
Diaphragm polyester reinforced silicone<br />
Regulator components stainless steel/brass/Delrin 500 AF<br />
Spring stainless Steel<br />
Pete’s Plug* (Qty 2) 1/4” brass/Nortel (Optional P/T)<br />
Body pressure rating 600 PSI<br />
Media temp. range 0°F to 212°F [-18°C to 100°C]<br />
Close off pressure 200 PSI<br />
Leakage ANSI Class IV (0.01% of rated valve<br />
capacity at 50 psi differential)<br />
Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />
1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />
3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />
5 GPM [.32 l/s]<br />
Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />
8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />
10 GPM [0.63 l/s]<br />
Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />
16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />
Rangeability 100 : 1<br />
Differential pressure<br />
operating range<br />
5 to 50 PSI<br />
Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />
Variation due to<br />
manufacturing tolerances<br />
≤ ± 5% (5 to 50 PSI)<br />
Hysteresis (absolute) ≤ 1%<br />
Weight of valve body 1/2” = 2.52 lbs, 3/4” = 3.05 lbs<br />
1” = 4.98 lbs<br />
Tefzel® and Teflon® are registered trademarks of Dupont<br />
*Pete’s Plugs offered as an option on 1/2”, 3/4” and 1” valves.<br />
68<br />
Application:<br />
The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve along with<br />
the LRCB24-3 is paired together specifically for use in Heat<br />
Pump applications to precisely control the flow of condenser<br />
water. This assembly is suitable for use in a hydronic system<br />
with constant or variable flow.<br />
Actuator Specifications<br />
❏ LRCB24-3… On/Off<br />
Power Supply 24 VAC ± 20% 50/60 Hz<br />
24 VDC ± 10%<br />
Power Consumption 1.5 W (0.2 W)<br />
Transformer Sizing 3 VA (Class 2 power source)<br />
Electrical Connection 18 GA plenum rated cable<br />
1/2” conduit connector<br />
❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />
Overload Protection electronic throughout 0 to 95° rotation<br />
Control On/Off<br />
Input Impedance 600Ω<br />
Angle of Rotation 95°<br />
Direction of Rotation reversible with protected switch<br />
Position Indication handle<br />
Manual Override external push button and handle<br />
Running Time 40 second constant independent of load<br />
Humidity 5 to 95% RH non condensing<br />
(EN 60730-1)<br />
Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />
Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />
Housing NEMA 2/IP54<br />
Housing Material UL94-5VA<br />
Agency Listings cULus acc. to UL60730-1A/-2-14,<br />
CAN/CSA E60730-1, CSA C22.2<br />
No. 24-93, CE acc. to 89/336/EEC and<br />
(-S Models) 2006/95/EC†<br />
Noise Level
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
Dimensions<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />
with On/Off, Non-Spring Return Actuator<br />
LRCB24-3 LRCB24-3 with P/T Ports<br />
Line<br />
Volts<br />
WARNING<br />
Live Electrical Components!<br />
During installation, testing, servicing and troubleshooting of this product, it maybe<br />
necessary to work with live electrical components. Have a qualified licensed electrician<br />
or other individual who has been properly trained in handling live electrical components<br />
perform these tasks. Failure to follow all electrical safety precautions when exposed<br />
to live electrical components could result in death or serious injury.<br />
1<br />
2.6"<br />
[66]<br />
E F<br />
Wiring Diagram<br />
24 VAC Transformer<br />
a open<br />
a closed<br />
3.22"<br />
[82]<br />
The indication of direction<br />
is valid for switch position 1.<br />
D<br />
1.69"<br />
[42]<br />
a<br />
6.5" [165]<br />
B<br />
A<br />
3<br />
0.78" [20]<br />
Blk (1) Common –<br />
Red (2) +<br />
Wht (3) +<br />
1 0<br />
C<br />
2.34"<br />
[59.4]<br />
FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />
3/4" NPT 5.25 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />
1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />
3<br />
®<br />
LRCX24-3<br />
Notes:<br />
1 Provide overload protection and disconnect as required.<br />
Actuators may also be powered by 24 VDC.<br />
Meets cULus requirements without the<br />
need of an electrical ground connection.<br />
LRCB24-3 On/Off<br />
D146<br />
W569<br />
2.6"<br />
[66]<br />
E F<br />
3.22"<br />
[82]<br />
D<br />
1.69"<br />
[42]<br />
6.5" [165]<br />
B<br />
A<br />
C<br />
2.34"<br />
[59.4]<br />
0.78" [20] FlowSetR Dimensions<br />
Dimensions (All ratings in brackets are in millimeters.)<br />
Valve A B C D E F<br />
1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />
1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />
D147<br />
69
ZS-CCV… New Control Valve Weather Shield<br />
Installation Instructions<br />
Weather shield for PICCV/CCV to provide protection for<br />
actuators in outdoor applications.<br />
Specifications<br />
Cover PETG with UV resistant smoke tint<br />
Perimeter Gasket Silicon Rubber<br />
Rubber Gasket Silicon Rubber<br />
Spring Clips Stainless Steel<br />
Temperature limitations: -22˚F to 122˚F (-30˚C to 50˚C)<br />
Plate (ZS-CCV-100) Aluminum<br />
Plate Galvaneal w/black powder coat<br />
WEATHER SHIELDS*<br />
ZS-CCV-60<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />
70<br />
ZS-CCV-90<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />
ZS-CCV-100<br />
<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />
*Designed for NEMA 4 specifications<br />
PARTS LIST<br />
Cover including Rubber Perimeter Gasket, Rubber Gasket<br />
Back Plate<br />
Anti-Rotation Post with screw and lock washer<br />
Valve Gasket<br />
APPLICATION<br />
The ZS-CCV… weather shield provides moderate protection<br />
for valves which are mounted outdoors. This product is<br />
designed as a water tight enclosure. The housing allows<br />
easy mounting over the actuator, while allowing easy viewing<br />
of the actuator in operation.<br />
Part Number L W H<br />
ZS - CCV - 60 10” [254] 7.75” [197] 4”[100]<br />
ZS - CCV - 90 16.25” [413] 8.75” [222] 4.5” [114]<br />
ZS - CCV-100 15.67” [398] 7.61” [193] 4.0” [102]<br />
LR (B) (X) (CX) AR (X) (CX) LF AF List Price<br />
●<br />
●<br />
with CCV EXT-KIT<br />
● ●<br />
Assorted Cap plugs for unused holes<br />
Screws: LF - 2 screws provided<br />
AF - 2 bolts with nylon insert locking nuts<br />
LR(B)(X)(CX), AR(X)(CX) - 1 screw, 1 washer<br />
● ●<br />
●<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Flexible Products – Introduction<br />
Table of Contents<br />
Flexible Section<br />
Introduction ............................................73<br />
Ordering..................................................74<br />
Non-Spring Return<br />
“At A Glance”..........................................75<br />
MFT Programming Codes ......................76<br />
Non-Spring Return<br />
Base Actuator Table................................76<br />
Multi-Functional Technology<br />
Belimo damper actuators and control valves with Multi-Function Technology ® (MFT) include standard 2<br />
to 10 VDC proportional control functions, plus they can be re-programmed. Parameters can be<br />
changed on-site to optimize/enable application. Parameters can be set for voltage control (VDC), time<br />
proportional control (PWM), floating point, on-off or feedback signal. You can also set, modify or read<br />
position, running time, mechanical working range, address, status, and diagnostics. MFT allows you to<br />
adapt the actuator to your system for service replacement and to improve system functionality.<br />
71
Flexible Products – Ordering<br />
72<br />
Ordering example – Non-Spring Return<br />
The ordering process for the new Flexible non-spring return actuators is very simple. First select<br />
a base actuator that meets the needs of the application and then simply add the desired options.<br />
1. Valve Assembly PICCV-50-040-PT+ARX24-MFT (AR100) OC1 A19 ●<br />
Flexible list add<br />
Select a valve assembly<br />
●<br />
• Torque or linear force, control input, position feedback, power supply…<br />
2. Clamp option Default valve linkage (O) ●<br />
3. Electrical Connection option 16 ft. [5m] 18 GA, plenum rated cable (C5) ●<br />
• Default connection is a 3 ft. [1m] long cable. 10 ft [3m] or 16ft [5m] cables are also available.<br />
4. Programming P-10019 (A19) ●<br />
• For –MFT type actuators refer to page 79 for available configurations.<br />
5. Total PICCV-50-040-PT+ARX24-MFT (AR100 OC5 A19) ●<br />
Ordering example – Spring Return<br />
1. Valve Assembly PICCV-50-040-PT+AF24-MFT-S US ●<br />
Select a base actuator<br />
2. Programming P-10019 (A19) ●<br />
2 – 10 VDC input / 2 – 10 VDC feedback<br />
Select pre-set programming code<br />
● P-100xx (Axx) Control voltage applications<br />
● P-200xx (Wxx) Pulse width modulation applications<br />
● P-300xx (Fxx) Floating point applications<br />
● Or create custom MFT configuration codes, see page 82<br />
● Or create custom MFT configurations in the field with MFT-Actuate PC software.<br />
3. Total PICCV-50-040-PT+AF24-MFT-S US+P10019 (A19) ●<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
®<br />
Base product nomenclature<br />
Actuator Torque<br />
LR… 45 in-lb<br />
AR… 180 in-lb<br />
Flexible Valve/Actuator Selection At A Glance<br />
PICCV + Non-Spring Return MFT, Multi-Functional Technology<br />
Model Description Reorder for actuator<br />
PICCV-50-040-PT ARX 24 –MFT AR 100 O C1 A19<br />
VALVE SIZES<br />
Valve Designation Sizes<br />
PICCV Valve 15 – 50 = 1/2”– 2”<br />
TYPE OF VALVE<br />
PRESSURE INDEPENDENT<br />
CHARACTERIZED<br />
CONTROL VALVE (CCV)<br />
P2… 2-way Stainless<br />
Steel Ball & Stem<br />
Actuator family and<br />
torque/force output<br />
Electrical Connection<br />
blank 3 ft cable<br />
Reorder number break-down<br />
Base Actuator Linkage Electrical connector options Programming codes<br />
AR 100 O C1 A19<br />
See Base Actuators<br />
Page 74<br />
Power Supply<br />
24 24 VAC/DC<br />
Electrical connector options<br />
Code Description*<br />
C1 Default, 3 ft [1m] cable<br />
C3 10 ft [3m] cable<br />
C5 16 ft [5m] cable<br />
*24V actuators supplied with 18GA plenum<br />
rated cable.<br />
Control Type<br />
–MFT Multi-Function technology<br />
–3 On/Off-Floating Point<br />
The reorder#<br />
is a complete<br />
description of the<br />
flexible actuator,<br />
including all<br />
custom options.<br />
Options<br />
Codes Description (MFT Only)<br />
A19 P-10019*<br />
A28 P-10028<br />
AAJ P-10118<br />
AAK P-10119<br />
AD5 P-10137<br />
W31 P-20031<br />
W32 P-20032<br />
W34 P-20034<br />
F03 P-30003<br />
*For On/Off control input, please order<br />
P-10019 and wire as on/off.<br />
73
Flexible Products – MFT Programming Codes<br />
PRODUCTS<br />
Base Actuator Running Angle of Power VA Weight Built-in<br />
Model Codes Control Input Feedback Time Rotation/Stroke Supply Rating (lb) Aux. Switch<br />
180 in-lb [20 Nm]<br />
LRX24-3 LR000 Floating Point 2-10 VDC 90 (Default) 95 deg 24 VAC/DC 3 1.10<br />
LRX24-3-S LR020 Floating Point 2-10 VDC 90 (Default) 95 deg 24 VAC/DC 3 1.10 Yes<br />
LRX120-3 LR060 Floating Point 2-10 VDC 95 (Default) 95 deg 120 VAC 4 1.10<br />
LRX24-MFT LR100 2-10 VDC (Default) 2-10 VDC 100 (Default) 95 deg 24 VAC/DC 3.5 1.10<br />
LRCB24-3 LR000 on/off 2-10 VDC 40 95 deg 24 VAC/DC 3 1.08<br />
LRCB24-3-S LR020 on/off 2-10 VDC 40 95 deg 24 VAC/DC 3 1.08 Yes<br />
ARX24-MFT AR100 2-10 VDC (Default) 2-10 VDC 100 (Default) 95 deg 24 VAC/DC 6 2.02<br />
† For correct code please call Belimo Customer Service 800-543-9038<br />
Multi-Function Technology<br />
74<br />
Description Code Control Input Built-in Feedback Running Time<br />
DC Voltage<br />
P-10019* A19 2-10 VDC 2-10 VDC 100<br />
P-10028 A28 0-10 VDC 0-10 VDC 100<br />
P-10118 AAJ 2-6 VDC 2-10 VDC 100<br />
P-10119 AAK 6-10 VDC 2-10 VDC 100<br />
P-10137 AD5 2-5 VDC 2-10 VDC 100<br />
Pulse Width Modulation<br />
P-20031 W31 0.02-5.00 sec. PWM 2-10 VDC 100<br />
P-20032 W32 0.10-25.5 sec. PWM 2-10 VDC 100<br />
P-20034 W34 0.59-2.93 sec. PWM 2-10 VDC 100<br />
Floating Point<br />
On/Off<br />
P-30003 F03 Floating Point 2-10 VDC 100<br />
P-10019* J13 On/Off 2-10 VDC 100<br />
**Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
2.16 CONTROL VALVES<br />
®<br />
A. Control Valves: Factory fabricated of type, body<br />
material, and pressure class based on maximum<br />
pressure and temperature rating of the piping<br />
system, unless otherwise indicated.<br />
B. <strong>Pressure</strong> <strong>Independent</strong> Control Valves<br />
a. Manufacturers:<br />
i. BELIMO AIRCONTROLS (USA), INC.<br />
b. The modulating control valves shall be<br />
pressure independent.<br />
c. The control valves shall accurately control the flow<br />
from 0 to 100% full rated flow with an equal<br />
percentage flow characteristic. The flow shall not<br />
vary more than +/- 5% due to system pressure<br />
fluctuations across the valve with a minimum of<br />
5 PSID across the valve.<br />
d. Forged brass body rated at no less than 400 PSI,<br />
chrome plated brass ball and stem, female NPT<br />
union ends, dual EPDM lubricated O-rings and<br />
TEFZEL characterizing disc.<br />
e. Combination of actuator and valve shall provide a<br />
minimum close-off pressure rating of 200 PSID.<br />
f. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
g. All actuators shall be electronically programmed<br />
by use of a handheld programming device or<br />
external computer software. Programming using<br />
actuator mounted switches or multi-turn actuators<br />
are NOT acceptable. [Actuators for 3-wire<br />
floating (tri-state) on 1/2” – 1” pressure<br />
independent control valves shall fail in place<br />
and have a mechanical device inserted<br />
between the valve and the actuator for the<br />
adjustment of flow.] [Actuators for two-position<br />
1/2” – 1” pressure independent control<br />
valves shall fail in place and have a mechanical<br />
device inserted between the valve and the<br />
actuator for the adjustment of flow.] [Actuators<br />
shall be provided with an auxiliary switch to<br />
prove valve position.]<br />
h. The actuator shall be of the same manufacturer<br />
as the valve, integrally mounted to the valve at the<br />
factory via a single screw on a four-way DIN<br />
mounting-base.<br />
i. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
j. The manufacturer shall warrant all components<br />
for a period 5 years from the date of production,<br />
with the first two years unconditional.<br />
k. The use of pressure independent valves piped in<br />
parallel to achieve the rated coil flow shall be<br />
permitted. Actuators shall be electronically<br />
programmed to permit sequencing the flow with a<br />
single control output point. The use of external<br />
devices to permit sequencing is NOT acceptable.<br />
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong><br />
Control Valves (1/2” – 2”)<br />
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves Master Format<br />
To be inserted into Section 15900 – HVAC Instrumentation and Controls<br />
To be inserted into Section 15181 – HYDRONIC PIPING<br />
2.6 CONTROL VALVES<br />
K. Calibrated Balancing Valves and Automatic<br />
Flow-Control Valves shall not be required on devices<br />
where pressure independent control valves are<br />
installed.<br />
NOTE TO BE ADDED TO THE PIPING DETAIL:<br />
Strainers shall not be required in front of each pressure<br />
independent control valve. A Type 20 strainer (or<br />
equivalent) should be installed in the system, in<br />
additional to other system strainers.<br />
To be inserted into Section 15950 – TESTING,<br />
ADJUSTING, AND BALANCING<br />
3.11 PROCEDURE FOR HYDRONIC SYSTEMS<br />
[CHOOSE ONE OF THE FOLLOWING TWO PARAGRAPHS]<br />
H. Systems installed with pressure independent control<br />
valves shall not require hydronic system balancing.<br />
H. Systems installed with pressure independent valves<br />
shall require verification of flow for [10%] [20%]<br />
[25%] of the total<br />
installed product. Exact locations of tested product<br />
to be coordinated with the design engineer.<br />
75
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong><br />
Control Valves (1/2” – 2”)<br />
Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves - Master Format<br />
To be inserted into Section 230900 – INSTRUMENTATION AND CONTROL FOR HVAC<br />
2.16 CONTROL VALVES<br />
76<br />
A. Control Valves: Factory fabricated of type, body<br />
material, and pressure class based on maximum<br />
pressure and temperature rating of the piping<br />
system, unless otherwise indicated.<br />
B. <strong>Pressure</strong> <strong>Independent</strong> Control Valves<br />
a. Manufacturers:<br />
i. BELIMO AIRCONTROLS (USA), INC.<br />
b. The modulating control valves shall be pressure<br />
independent.<br />
c. The control valves shall accurately control the flow<br />
from 0 to 100% full rated flow with an equal<br />
percentage flow characteristic. The flow shall not<br />
vary more than +/- 5% due to system pressure<br />
fluctuations across the valve with a minimum of<br />
5 PSID across the valve.<br />
d. Forged brass body rated at no less than 400 PSI,<br />
chrome plated brass ball and stem, female NPT<br />
union ends, dual EPDM lubricated O-rings and<br />
TEFZEL characterizing disc.<br />
e. Combination of actuator and valve shall provide a<br />
minimum close-off pressure rating of 200 PSID.<br />
f. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
g. All actuators shall be electronically programmed<br />
by use of a handheld programming device or<br />
external computer software. Programming using<br />
actuator mounted switches or multi-turn actuators<br />
is NOT acceptable. [Actuators for 3-wire floating<br />
(tri-state) on 1/2” – 1” pressure independent<br />
control valves shall fail in place and have a<br />
mechanical device inserted between the valve<br />
and the actuator for the adjustment of flow.]<br />
[Actuators for two-position 1/2” – 1” pressure<br />
independent control valves shall fail in place<br />
and have a mechanical device inserted<br />
between the valve and the actuator for the<br />
adjustment of flow.] [Actuators shall be provided<br />
with an auxiliary switch to prove valve<br />
position.]<br />
h. The actuator shall be of the same manufacturer<br />
as the valve, integrally mounted to the valve at the<br />
factory via a single screw on a four-way DIN<br />
mounting-base.<br />
i. The control valve shall require no maintenance<br />
and shall not include replaceable cartridges.<br />
j. The manufacturer shall warrant all components for<br />
a period of 5 years from the date of production,<br />
with the first two years unconditional.<br />
k. The use of pressure independent valves piped in<br />
parallel to achieve the rated coil flow shall be<br />
permitted. Actuators shall be electronically<br />
programmed to permit sequencing the flow with<br />
a single control output point. The use of external<br />
devices to permit sequencing is NOT acceptable.<br />
To be inserted into Section 232113 – HYDRONIC PIPING<br />
2.6 CONTROL VALVES<br />
K. Calibrated Balancing Valves and Automatic<br />
Flow-Control Valves shall not be required on<br />
devices where pressure independent control<br />
valves are installed.<br />
NOTE TO BE ADDED TO THE PIPING DETAIL:<br />
Strainers shall not be required in front of each pressure<br />
independent control valve. A Type 20 strainer (or<br />
equivalent) should be installed in the system, in<br />
additional to other system strainers.<br />
To be inserted into Section 230593 – TESTING,<br />
ADJUSTING, AND BALANCING FOR HVAC<br />
3.11 PROCEDURE FOR HYDRONIC SYSTEMS<br />
[CHOOSE ONE OF THE FOLLOWING TWO PARAGRAPHS]<br />
H. Systems installed with pressure independent control<br />
valves shall not require hydronic system balancing.<br />
H. Systems installed with pressure independent valves<br />
shall require verification of flow for [10%] [20%]<br />
[25%] of the total<br />
installed product. Exact locations of tested product<br />
to be coordinated with the design engineer.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® ®<br />
I. GENERAL<br />
A. Warranty all actuators for a period of two or five years from the production<br />
date as stated in the Terms and Conditions of Sale and Warranty.<br />
B. Electronic valve and damper actuators shall be as manufactured, brand<br />
labeled, or distributed by Belimo.<br />
C. Electronic control valves, as specified, shall be Belimo or other brands<br />
manufactured, brand labeled or distributed by Belimo.<br />
D. Other manufacturers must be approved, in writing, 10 days prior to the<br />
bid date.<br />
II. PRODUCTS<br />
A. Electronic Damper Actuators<br />
1. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO<br />
9001 quality certification and be cULus listed under standard 60730-1 or<br />
UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.<br />
2. Electronic actuators used on dampers shall be designed to directly couple<br />
and mount to a stem, shaft or ISO style-mounting pad. Actuator<br />
mounting clamps shall be a V-bolt with a toothed V-clamp creating a cold<br />
weld, positive grip effect. Single point, bolt, or single screw actuator type<br />
fastening techniques or direct-coupled actuators requiring field assembly<br />
of the universal clamp is not acceptable.<br />
3. Actuators shall be fully modulating/proportional, pulse width,floating/tristate,<br />
or two position as required and be factory or field selectable.<br />
Actuators shall have visual position indicators and shall operate in<br />
sequence with other devices if required.<br />
4. Optional auxiliary switches shall be available.<br />
5. Actuators shall have an operating range of –22° to 122°F.<br />
6. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal and<br />
provide a 2-10 VDC or 4-20 mA (with a 500 W load resistor) operating range.<br />
7. Actuators shall be capable of operating on 24, 120 or 230VAC, or 24VDC<br />
and Class 2 wiring as dictated by the application. Power consumption<br />
shall not exceed 10 VA for AC, including 120VAC actuators, and 8 watts<br />
per actuator for DC applications.<br />
8. NEMA 2 rated actuators shall be provided with a three foot (minimum),<br />
pre-wired, electrical cable. Actuators requiring removal of the actuator<br />
cover for access to wiring terminals, exposing electronic, printed circuit<br />
boards to damage, are unacceptable.<br />
9. Actuators shall have electronic overload protection or digital rotation<br />
sensing circuitry to prevent actuator damage throughout the entire rotation.<br />
End switches to deactivate the actuator at the end rotation or magnetic<br />
clutches are not acceptable.<br />
10. For power-failure/safety applications, an internal mechanical spring return<br />
mechanism shall be built into the actuator housing. Spring return actuators<br />
shall be capable of CW or CCW mounting orientation. Spring return<br />
models > 60 in-lbs. and non-spring return models > 90 in-lbs. will be<br />
capable of mounting on shafts up to 1.05"in diameter. Spring return actuators<br />
with more than 60 in-lb. of torque shall have a metal, manual override<br />
crank.<br />
11. Actuators using "on-board" chemical storage systems, capacitors, or other<br />
"on-board" non-mechanical forms of fail-safe operation are unacceptable.<br />
12. Upon loss of control signal, a proportional actuator shall fail open or<br />
closed based on the minimum control signal. Upon loss of power, a nonspring<br />
return actuator shall maintain the last position.<br />
13. Actuators shall be capable of being mechanically and electrically paralleled<br />
to increase torque if required. Valves and dampers requiring greater torque<br />
or higher close off may be assembled with multiple low torque actuators.<br />
14. Dual mounted actuators using additional anti-rotation strap mechanical<br />
linkages, or special factory wiring to function are not acceptable.<br />
Actuators in a tandem pair must be "off the shelf," standard actuators<br />
ready for field wiring.<br />
15. Damper and valve actuators will not produce more than 62 dB (A) when<br />
furnished with a mechanical fail-safe spring. Non-spring return actuators<br />
shall conform to a maximum noise rating of 45 dB(A) with power on or in<br />
the running or driving mode.<br />
16. Proportional actuators shall be fully programmable. Control input, position<br />
feedback and running time shall be factory or field programmable.<br />
Diagnostic feedback shall provide indications of hunting or oscillation,<br />
mechanical overload, mechanical travel and mechanical load limit. The<br />
actuators shall also provide actuator service data, at minimum, number of<br />
hours powered and number of hours in motion.<br />
17. Proportional actuators shall be capable of digital communication, as built.<br />
Actuator/Valve Specification<br />
Download specifications at www.belimo.com<br />
B. Smoke and Combination Fire and Smoke Actuators<br />
In Section 15820 or equivalent<br />
1. All smoke and combination fire and smoke dampers shall be<br />
provided with Belimo Aircontrols FSLF (30 in-#), FSNF (70 in-#),<br />
or FSAF (133 in-#) actuators.<br />
2. Equals shall be approved 10 days prior to submission of bid.<br />
3. Actuator shall carry a manufacturer’s 5-year warranty and be manufactured<br />
under ISO 9001 quality control.<br />
4. Actuator shall have microprocessor or electronic based motor controller<br />
providing:<br />
a. Electronic cut off at full open so that no noise can be generated while<br />
holding open. Holding noise level shall be inaudible.<br />
b. Protection so that actuator shall be incapable of burning out if stalled<br />
before full rotation is reached.<br />
5. Housing shall be steel and gears shall be permanently lubricated.<br />
6. The actuators shall be direct coupled and employ a steel toothed coldweld<br />
clamp for connecting to damper or jack shafts. Aluminum clamps or<br />
set-screw attachment are not acceptable.<br />
7. Actuator shall have UL555S Listing by the damper manufacturer for 250°F.<br />
8. FSLF shall be applied on dampers up to 6 sq. ft. Current draw shall be<br />
no more than .15A at 120V running, or .06A holding at 120V (5 VA and<br />
3.5 VA respectively for 24V power).FSNF shall be applied on dampers up<br />
to 16 sq.ft. Current draw shall be no more than .23A at 120V running, or<br />
.1A holding at 120V (27 VA and 10 VA respectively for 24V power).<br />
9. FSAF shall be applied on dampers up to 20 sq.ft. Current draw shall be<br />
no more than .1A at 120V running, or .05A holding at 120V (10 VA and<br />
3 VA respectively for 24V power).<br />
10. Dampers shall be installed straight and true, level in all planes, and<br />
square in all dimensions. Dampers shall move freely without undue<br />
stress due to twisting, racking, bowing, or other installation error.<br />
11. Do not install in area where moisture can penetrate damper or actuator<br />
nor where actuator temperature exceeds 120°F.<br />
Note: FSLF and FSNF are 350°F actuators, 15 seconds open and<br />
close. UBC and UL555S<br />
FSAF is a 250F actuator, 75 seconds open, 20 seconds close.<br />
UL555S.<br />
C. Electronic Valve Actuators<br />
1. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO<br />
9001 quality certification and be cULus listed under standard 60730-1 or<br />
UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.<br />
2. Electronic actuators used on valves shall be designed to directly couple<br />
and mount to a stem, shaft or ISO style-mounting pad.<br />
3. Actuators shall be fully modulating/proportional, floating/tri-state, or two<br />
position as required and be factory or field selectable.<br />
4. Optional auxiliary switches shall be available.<br />
5. Actuators shall have an operating range of –22° to 122°F.<br />
6. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal<br />
and provide a 2-10 VDC or 4-20 mA (with a load resistor) operating range.<br />
7. Actuators shall be capable of operating on 24VAC, 120VAC or 230VAC,<br />
or 24VDC and Class 2 wiring as dictated by the application. Power consumption<br />
shall not exceed 10 VA for AC, including 120VAC actuators, and<br />
8 watts per actuator for DC applications.<br />
8. NEMA 2 rated actuators shall be provided with either a covered terminal<br />
strip, or a three, six, or ten foot pre-wired, electrical cable.<br />
9. For power-failure/safety applications, an internal mechanical spring return<br />
mechanism shall be built into the actuator housing. Spring return actuators<br />
shall be capable of CW or CCW mounting orientation. Spring return<br />
actuators with more than 60 in-lb. of torque shall have a metal, manual<br />
override crank.<br />
10. Actuators using "on-board" chemical storage systems, capacitors, or other<br />
"on-board" non-mechanical forms of fail-safe operation are unacceptable.<br />
11. Upon loss of control signal, a proportional actuator shall fail open or<br />
closed based on the minimum control signal. Upon loss of power, a nonspring<br />
return actuator shall maintain the last position.<br />
12. Actuators utilizing brushless DC technology shall be capable of being<br />
mechanically and electrically paralleled to increase torque if required.<br />
Valves requiring greater torque or higher close off may be assembled<br />
with two low torque actuators.<br />
77
Actuator/Valve Specification<br />
78<br />
13. Dual mounted actuators using additional anti-rotation strap mechanical<br />
linkages, or special factory wiring to function are not acceptable.<br />
Actuators in a tandem pair must be "off the shelf," standard actuators<br />
ready for field wiring.<br />
14. Valve actuators will not produce more than 62 dB (A) when furnished<br />
with a mechanical fail-safe spring. Non-spring return actuators shall conform<br />
to a maximum noise rating of 45 dB(A) with power on or in the running<br />
or driving mode.<br />
15. Proportional actuators shall be fully programmable. Control input, position<br />
feedback and running time shall be factory or field programmable.<br />
Diagnostic feedback shall provide indications of hunting or oscillation,<br />
mechanical overload, mechanical travel and mechanical load limit. The<br />
actuators shall also provide actuator service data, at minimum, number of<br />
hours powered and number of hours in motion.<br />
16. Proportional actuators shall be capable of digital communication, as built.<br />
D. Industrial Actuators<br />
1. Belimo SY Series Industrial Electric Actuators<br />
a. The valve actuator shall consist of a thermally protected capacitor-type<br />
reversible electric motor, a patented planetary worm combination drive,<br />
heater, limit switches and wiring termination blocks, all contained in a die<br />
cast aluminum enclosure. The drive system will provide continuous,<br />
smooth torque transmission throughout a 90 degree travel. Adjustable<br />
stops provide mechanical adjustment of end-of-travel. The transmission<br />
shall allow continuous duty operation of a manual override handwheel<br />
without the need to remove power, or de-clutch the manual system.<br />
b. Enclosure shall be designed to meet NEMA 4, 4X (weatherproof) requirements,<br />
or CSA approved for non-hazardous locations.<br />
c. The actuator shall employ ISO5211 mounting standards to provide for a<br />
wide range of international applications.<br />
d. The enclosure will have an industrial quality coating.<br />
e. Actuator shall have a motor rated for a minimum of 25% duty cycle in<br />
modulating applications.<br />
f. Actuator shall be suitable for operation in ambient temperature ranging<br />
from -4°F to +150°F [-20°C to +65°C].<br />
g. The motor shall be fractional horsepower; permanent split capacitor type<br />
designed to operate on 24 VAC, 110 VAC or 220 VAC, 1 pH, 50/60 Hz<br />
supply. A self resetting thermal switch shall be imbedded in the motor for<br />
overload protection.<br />
h. Internal terminal blocks shall be clearly marked for field wiring. A wiring<br />
diagram shall be permanently attached to the OUTSIDE of the actuator<br />
housing.<br />
i. Actuator will have a suitable sized NPT entry for external connections.<br />
j. Gears shall be hardened alloy steel, permanently lubricated. The worm<br />
drive system negates the need for a brake.<br />
k. Two adjustable cam actuated end travel limit switches shall be provided<br />
to control electrical movement of the actuator.<br />
l. 2 SPDT auxiliary switches, rated 10A at 250 VAC shall be included. The<br />
switches are factory pre-set at 3 degrees and 87 degrees rotation, and<br />
may be field adjusted.<br />
m. Actuator shall be equipped with a hand wheel or shaft for manual override<br />
to permit operation of the actuator in the event of electrical power failure<br />
or system malfunction. Hand wheel, where applicable, must be permanently<br />
attached to the actuator. (SY2 and larger)<br />
n. The handwheel override shall be continuously operational regardless of<br />
the powered state of the actuator, without the need to remove electrical<br />
power if present during the override phase. (SY2 and larger)<br />
o. The hand wheel will not rotate while the actuator is electrically driven.<br />
p. The actuator shall provide a visual indicator beacon on the top of the<br />
housing for position status of the actuator and attached devices.<br />
q. Actuator shall have an internal heater and thermostat to minimize the<br />
build-up of moisture inside the sealed enclosure.<br />
r. Modulating units shall operate under 2-10 VDC, 4-20mA, and 1-5 VDC<br />
control modes. The default shall be 2-10 VDC control.<br />
E. Electronic Control Valves<br />
1. General<br />
a. The manufacturer shall be capable of providing individual valve identification<br />
tagging on each printed valve label. Valve tag identification shall be<br />
documented on the approved, submitted valve schedule.<br />
b. Valves shall be designed and provided with the proper actuators to provide<br />
the rated valve close-off.<br />
2. <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves<br />
a. Control valves shall be pressure independent. Balancing valves and<br />
associated balancing shall not be required on devices where pressure<br />
independent control valves are installed. Balancing valves and balancing<br />
are required if self-contained pressure independent control valves are not<br />
installed.<br />
b. The absolute flow accuracy through the valve shall be +/- 5 % due to system<br />
pressure fluctuations across the valve in the selected operating<br />
range, and +/- 5% variation due to manufacturing tolerances.<br />
c. The control valves shall be available with floating or proportional actuators.<br />
The actuator shall be directly coupled to the valve at the factory.<br />
Proportional actuators shall be Multi Function Technology as manufactured<br />
by Belimo. Multi-turn actuators are not acceptable.<br />
d. The valve shall have an equal percentage characteristic and shall accurately<br />
control the flow from 0 to 100% full rated flow.<br />
e. A minimum of 5 PSI shall be required to operate the valve pressure independently.<br />
f. Valves shall require no maintenance and shall not include replaceable<br />
cartridges.<br />
g. Valves shall be available with optional pressure/temperature ports to<br />
allow flow verification.<br />
h. Control valves shall be by Belimo.<br />
3. <strong>Characterized</strong> Control Valves<br />
a. Control valves shall be of the <strong>Characterized</strong> Control Valve type provided<br />
by Belimo.<br />
b. <strong>Characterized</strong> Control Valves shall be used for all water applications<br />
requiring equal percentage characteristics.<br />
c. A TEFZEL‚ flow-characterizing disc shall be installed in the inlet of Twoway<br />
characterized control valves and in the control port of Three-way<br />
valves. The valve trim shall utilize a stainless steel ball and stem for all<br />
water or glycol solutions up to 60%. For water applications, an optional<br />
chrome plated brass ball and brass stem may be used for sizes 3/4’’ and<br />
smaller.<br />
d. Valve bodies shall be nickel-plated, forged brass with female NPT<br />
threads. Bodies to 1-1/4" shall be rated at 600 psi and sizes 1-1/2" to 3"<br />
at 400 psi.<br />
e. <strong>Characterized</strong> Control Valves shall have a self-aligning, blowout proof,<br />
brass stem with a dual EPDM O-ring packing design. Fiberglass reinforced<br />
Teflon seats shall be used.<br />
f. The valves shall have a four bolt mounting flange to provide a 4 position,<br />
field changeable, electronic actuator mounting arrangement.<br />
g. A non-metallic coupling, constructed of high temperature, continual use<br />
material shall provide a direct, mechanical connection between the valve<br />
body and actuator. The coupling shall be designed to provide thermal<br />
isolation and eliminate lateral and rotational stem forces. Vent hole shall<br />
be provided to reduce condensation build-up.<br />
4. Globe Valves<br />
a. Globe valves, as specified, shall be by Belimo.<br />
b. Two-way and Three-way globe valves may be used only if characterized<br />
control valves do not fit the sizing criteria or application.<br />
c. Globe valves may be used for chilled or hot water, steam, or glycol solutions<br />
to 60%. Screwed and flanged water valves shall have equal percentage<br />
or linear flow characteristics for Two-way or Three-way valves,<br />
respectively. All stems shall be stainless steel.<br />
d. Screwed globe valves 1/2" through 2" shall have bronze bodies rated at<br />
ANSI Class 250. For water up to 35 psi or steam up to 15 psi, trim shall<br />
include a brass plug, a spring-loaded TFE packing, and a bronze seat.<br />
The maximum differential shall be 35 psi for water and 15 psi for steam.<br />
e. Two-way and Three-way flanged globe valves 2-1/2" to 6" shall have cast<br />
iron bodies rated for ANSI Class 125 or ANSI 250. The maximum differential<br />
shall be 25 psi for water and 10 psi for steam. Trim shall include stainless<br />
steel stems, bronze plugs, bronze seats, and a NLP packaging or a<br />
complete stainless steel trim and a TFE V-ring packaging.<br />
f. For steam inlet pressures higher than those stated above, furnish globe<br />
valves with stainless steel trim specifically rated for the application.<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® ®<br />
5. Direct Coupled Globe Valve Actuator and Adaptor Bracket<br />
a. Actuator shall be designed with an integrated adaptor bracket that will<br />
direct mount to the valve.<br />
b. Actuator shall provide a linear force capable of fulfilling the required<br />
close-off of the valve.<br />
c. Actuator shall include an automatic valve coupling device that shall lock<br />
securely to the valve stem.<br />
d. Proportional and spring return actuators shall adapt upon powering the<br />
actuator. This adaptation will determine stroke length and enable the<br />
actuator to set the minimum and maximum limits of the supplied control<br />
signal, thereby utilizing the entire control signal range. Feedback, running<br />
time and other parameters are automatically adjusted to the effective<br />
stroke.<br />
e. Actuator shall have a manual override equipped with an interlocking<br />
device to protect the actuator from over-torque of the manual override.<br />
6. Butterfly Valves – Resilient Seat<br />
a. Butterfly valves, as specified, shall be by Belimo.<br />
b. Butterfly valves 2" to 12" shall have a fully lugged, drilled and tapped,<br />
cast iron body, rated to 200 psi body pressure, with 14" and larger valves<br />
having a body pressure rating of 150 psi. Flanges shall meet ANSI<br />
125/150 standards. The one-piece body shall feature an extended neck<br />
allowing sufficient clearance for flanges and 2" of piping insulation. The<br />
disc shall be 304 stainless steel and provide bi-directional bubble-tight<br />
close off in either direction for chilled or hot water or 50% glycol applications.<br />
The disc shall be polished and contoured to minimize torque and<br />
wear. Shaft shall be mechanically retained in valve body using split-thrust<br />
washer and internal retaining-ring design for ease of service. The valve<br />
body shall employ ISO5211 actuator mounting and shaft connection<br />
standards.<br />
c. The disc shall have full 360-degree concentric seating. Valves up through<br />
12" shall utilize an internal spline for the disc-to-stem connection. External<br />
mechanical methods to achieve this mechanical connection, such as pins<br />
or screws, shall not be employed. Valves 14" and larger will utilize a dualpin<br />
method to prevent the heavy disc from settling onto the liner, causing<br />
distortion. A phenolic backed, non-collapsing, EPDM seat shall be field<br />
replaceable and shall create a positive seal between flange face and<br />
valve body. No gaskets shall be required between the valve and flange<br />
faces. The shaft shall be supported at four locations by RPTFE bushings.<br />
d. The flow characteristic shall be modified equal percentage for Two-way<br />
valves and linear for Three-way valves. Valves 2" through 12" shall be<br />
rated for standard HVAC service of up to 50 psi close-off, or for heavy<br />
commercial service of up to 200 psi close-off. Valves 14" and larger shall<br />
be rated for up to 150 psi close-off.<br />
e. A permanent metal tag shall designate manufacturer, series number and<br />
materials of construction.<br />
f. Butterfly valves may be used in all two-position applications and modulating<br />
applications larger than 2", or where the close off rating of other valve<br />
styles does not meet the design requirements.<br />
g. Butterfly valves shall be sized primarily by using velocity calculations to<br />
prevent fluid velocities from exceeding 12 feet per second. For modulating<br />
applications, CV factors at sixty (60) degrees shall be used for determining<br />
delta P once size has been determined by the velocity calculations.<br />
h. High torque industrial valve actuators, >300 in-lb. of rated torque, may be<br />
used where low torque actuators are not suitable. High torque actuators<br />
shall be as manufactured or provided by Belimo.<br />
Actuator/Valve Specification<br />
7. Butterfly Valves – High Performance<br />
a. Butterfly valves, as specified, shall be by Belimo.<br />
b. Butterfly valves 2" to 30" shall have a fully lugged, drilled and tapped,<br />
carbon steel body conforming to ANSI class 150 or class 300 standards.<br />
Flanges shall meet ANSI 150 or ANSI 300 standards. The one-piece<br />
body shall feature an extended neck allowing sufficient clearance for<br />
flanges and 2" of piping insulation.<br />
c. The disc shall be 316 stainless steel and provide bi-directional bubbletight<br />
close off in either direction for chilled or hot water, 50% glycol applications<br />
or steam applications up to the ANSI class limits. The disc shall<br />
employ a 360 degree uninterrupted spherical edge for sealing. The disc<br />
profile shall be designed for maximum flow and equal percentage control.<br />
d. Shaft shall be mechanically retained in the valve body using an<br />
adjustable gland flange. This flange also serves to prevent leakage out<br />
the valve neck by applying a load against TFE Chevron design washers.<br />
These washers provide full ANSI hydrostatic seal to 150% of CWP rating.<br />
e. The RTFE bi-directional seat shall employ an encapsulated elastomeric<br />
o-ring core for resiliency. The seat is retained in the valve body by use of<br />
a retaining ring. The outside diameter of the retaining ring is recessed<br />
within the gasket sealing surface to prevent external leakage. The retaining<br />
ring is held in place by means of a stainless wedge ring.<br />
f. A permanent metal tag shall designate manufacturer, recommended flow<br />
direction, series number and materials of construction.<br />
g. Butterfly valves may be used in all two-position applications and modulating<br />
applications larger than 2", or where the close off rating of other valve<br />
styles does not meet the design requirements.<br />
h. Butterfly valves shall be sized primarily by using velocity calculations to<br />
prevent fluid velocities from exceeding 32 feet per second. For modulating<br />
applications, CV factors at sixty (60) degrees shall be used for determining<br />
delta P once size has been determined by the velocity calculations.<br />
i. High torque industrial valve actuators, >300 in-lb. of rated torque, may be<br />
used where low torque actuators are not suitable. High torque actuators<br />
shall be as manufactured or provided by Belimo.<br />
8. Zone Valves<br />
a. Zone valves, as specified, shall be by Belimo.<br />
b. Zone valves shall be used in terminal unit water applications requiring a<br />
Two-way or Three-way diverting valve in sizes 1’’ and smaller.<br />
c. Zone valves shall have brass bodies with female NPT or sweat ends and<br />
a stainless steel stem.<br />
d. Zone valve actuators shall on/off and shall be available in 24VAC or<br />
120VAC.<br />
e. Zone valve actuators shall have a minimum of 20 psi close-off rating.<br />
f. Zone valves shall have push button for quick removal of actuator.<br />
g. Zone valves shall have a leakage rate of 0.1% or lower<br />
9. Industrial Ball Valves<br />
a. Ball valves, as specified, shall be by Belimo.<br />
b. Two-way and three-way ball valves may be used only if characterized<br />
control valves do not fit the sizing criteria or application.<br />
c. Ball valves may be used for chilled or hot water, steam, or glycol solutions<br />
to 50%. Screwed or flanged water valves shall have modified equal<br />
percentage or modified linear flow characteristics for two-way and threeway<br />
valves, respectively. The ball and stem shall be stainless steel, and<br />
seats will be RPTFE.<br />
d. VS Series screwed ball valves 1/2" through 3" shall have bronze bodies<br />
rated to at least 400 WOG. Flanged ball valves 2" through 10" shall have<br />
cast iron bodies rated to at least 200 WOG. The maximum differential rating<br />
will match the respective valve close-off rating.<br />
e. VSS Series screwed ball valves 1/2" through 3" shall have stainless steel<br />
bodies rated to at least 600 WOG. The maximum differential rating will<br />
match the respective valve close-off rating.<br />
f. VS and VSS series ball valves shall provide bubble-tight close-off capabilities<br />
on all ports up to the specified close-off rating.<br />
79
Terms and Conditions of Sale and Warranty<br />
I. General<br />
1.1. The following Terms and Conditions of Sale (“Terms”) apply<br />
to the sale of products described in this Product Guide<br />
(“Products”). As used herein, “Seller” or “Belimo” refers to<br />
Belimo Aircontrols (USA) Inc. or Belimo Aircontrols (CAN) Inc., as<br />
applicable, and “Client” refers to the individual or business entity<br />
that purchases the Products from Seller. These Terms shall apply<br />
unless the parties mutually agree to different terms and memorialize<br />
such agreement in a writing signed by both Client and Seller.<br />
II. Price<br />
2.1. The Seller’s price for Products (the “Price”) is net, F.O.B.<br />
Point of Origin, and is calculated in US currency for sales made<br />
by Belimo Aircontrols (USA), Inc. and calculated in Canadian<br />
currency for sales made by Belimo Aircontrols (CAN) Inc.<br />
2.1.The Price, unless otherwise agreed upon, does not include<br />
freight and packaging (wooden crates, pallets, etc), the costs<br />
of which will be charged to Client at cost for each shipment and<br />
shall be payable with payment of the Price.<br />
2.3. Orders for Products with a net value of less than US$300<br />
(CAN$450) will be subject to a US$20 (CAN$35) handling fee<br />
(the “Handling Fee”). The Handling Fee will not be charged for<br />
orders of Products with a net value equal to or greater than<br />
US$300 (CAN$450) or for Products ordered through Seller’s<br />
internet ordering system at: www.belimo.com.<br />
2.4. Seller reserves the right to make partial deliveries of orders<br />
of Products, each of which deliveries may be invoiced separately<br />
by Seller.<br />
2.5.The Price does include charges for wiring diagrams, installation,<br />
and commissioning, which will be charged to Client separately<br />
and will be payable on demand.<br />
III. Payment<br />
3.1. Invoices are payable in US currency for sales made by<br />
Belimo Aircontrols (USA), Inc. and in Canadian currency<br />
for sales made by Belimo Aircontrols (CAN) Inc. and are due<br />
no later than 30 days from the date of invoice, without any<br />
deductions.<br />
3.2. If Client fails to pay the entire invoice balance within 60<br />
days from the date of the invoice, Client will be subject to an<br />
interest charge of 2% per month (or the maximum rate permitted<br />
by law, whichever is less) on the outstanding unpaid balance<br />
due to Seller.<br />
3.3. Clients who maintain outstanding balances for 45 days or<br />
more after the date of invoice may be subject to restricted shipments<br />
of Products or may be required to pay for all future deliveries<br />
of Products on a cash-on-delivery basis.<br />
IV. Title and Risk<br />
4.1. Title to all Products shall remain with Seller and shall not<br />
pass to Client until Seller has received full payment for the<br />
Products.<br />
V. Damage or Loss in Transit<br />
5.1. Seller assumes no liability for damage or loss of shipment<br />
of Products, which risk shall at all times remain with the carrier.<br />
All shipments must be unpacked and examined by Client immediately<br />
upon receipt. Any external evidence of loss or damage<br />
must be noted on the freight bill accompanying the shipment of<br />
Products or carrier’s receipt and signed by the carrier’s agent at<br />
the time of delivery. Failure to do so will result in the carrier’s<br />
refusal to honor any claim relating to damage of Products.<br />
Client must also notify Seller of such damage by providing<br />
Seller with a copy of the freight bill or damage report so that<br />
80<br />
Seller can file a claim for loss or damage in transit with the carrier.<br />
If the damage does not become apparent until the shipment<br />
is unpacked, customer must make a request for inspection<br />
by the carrier’s agent and file with the carrier within 15 days<br />
after receipt of product and notify Seller of the same. Seller is<br />
not liable for consequential damage to Client’s property or a<br />
third-party’s property resulting from the installation of damaged<br />
Products.<br />
VI. Delivery<br />
6.1. Seller undertakes to make every attempt to adhere to its<br />
stated delivery parameters and to make a timely delivery of the<br />
Products but does not guarantee any delivery specifications.<br />
Each contract entered into for the purchase of Products is not<br />
cancelable nor is Seller liable for any direct or indirect losses<br />
that may arise, for any reason whatsoever, due to Seller’s failure<br />
to meet any stated or assumed delivery schedules.<br />
VII. Return of Goods<br />
7.1. Products received by Client cannot be returned unless: (i)<br />
Client alerts Seller that it intends to return such Products, (ii)<br />
Seller agrees to accept the return of such Products, (iii) Client<br />
obtains a Return Material Authorization (“RMA”) number from<br />
Seller for the return of such Products, and (iv) Client follows all<br />
return instructions provided by the Seller. The RMA number<br />
must be clearly written on the outside of all packaging for any<br />
returned Products. Only Products returned to proper the location<br />
as instructed by Seller and identified with an RMA number<br />
will be considered for credit.<br />
7.2. Only Products that are returned in original packaging may<br />
be accepted for return. Such returned Products must be<br />
received in good condition, adequate for resale as new<br />
Products to qualify for credit. Client will be responsible for payment<br />
of a restocking charge for all returned Products in an<br />
amount no less than 20% of the invoice value of the Products<br />
(“Restocking Charges”). All return Products must be shipped<br />
to Seller at Client’s cost.<br />
7.3. Returns that result from Seller errors will be credited in full<br />
and will not be subject to Restocking Charges.<br />
VIII. Warranty<br />
VIII.A 5-year Warranty<br />
8.1. Products that are listed in this Product Guide as carrying a<br />
5-year warranty and shipped after May 1, 2000 to a location in<br />
the United States or Canada shall carry a 5-year warranty. The<br />
5-year warranty is unconditional for the first two years from the<br />
date of production of the Products. After the first two years<br />
from the date of Production, the warranty shall be conditional<br />
and the warranty coverage shall not apply to damage to<br />
Products caused by ordinary wear and tear, negligence or<br />
improper use by Client, or other causes beyond the control of<br />
the Seller. Product -specific terms of warranty with regard to<br />
warranty period or conditions of warranty may apply to certain<br />
specified Products as stated in the documentation for those<br />
Products.<br />
VIII.B 2-year Conditional Warranty<br />
8.2. Products that are listed in this Product Guide as carrying a<br />
2-year warranty and shipped after May 1, 2005 to a location in<br />
the United States or Canada shall carry a 2-year warranty. The<br />
2-year warranty is conditional and the warranty coverage shall<br />
not apply to damage to Products caused by ordinary wear and<br />
tear, negligence or improper use by Client, or other causes<br />
beyond the control of the Seller. Product -specific terms of warranty<br />
with regard to warranty period or conditions of warranty<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
® ®<br />
may apply to certain specified Products as stated in the documentation<br />
for those Products.<br />
VIII.C General Warranty Terms<br />
8.3. Seller’s warranty may be null and void in the event of any:<br />
(a) modification or unauthorized repairs of Products by Client,<br />
(b) unauthorized incorporation or integration of Products into<br />
or with Client’s equipment, (c) use of Products in an unauthorized<br />
manner, or (d) damage to Products not caused by Seller.<br />
8.4. Client must promptly notify Seller of Products’ alleged<br />
defect and provide Seller with other evidence and documentation<br />
reasonably requested by Seller. Before removing<br />
Products from service, Client should contact a Seller-authorized<br />
support technician by calling Belimo customer service.<br />
The contact information for Belimo customer service is listed<br />
on the back page of Belimo’s Product Guide and Price List<br />
(“PGPL”) or may be found at www.belimo.com. Belimo customer<br />
service will work with field technicians to troubleshoot<br />
problems. Many problems can be resolved over the phone.<br />
8.5. If a problem cannot be resolved over the phone, an RMA<br />
number will be issued by Seller for return of the Products. Prior<br />
to returning any Products under a warranty, Client must obtain<br />
an RMA number from Seller, along with shipping instructions for<br />
the return. The RMA number must be clearly written on the outside<br />
of the box containing the returned Products. Only Products<br />
returned to the proper location and identified with an RMA number<br />
will be accepted by the Seller.<br />
8.6. All returned Products should be packaged appropriately to<br />
prevent further damage. Seller reserves the right to refuse any<br />
returned material if improperly packaged or labeled (without<br />
an RMA number). Products returned without proper RMA<br />
documentation will void Seller’s warranty.<br />
8.7. Products found to be defective for which a warranty is<br />
applicable will either be replaced or repaired at the Seller’s discretion.<br />
Seller is not responsible for charges that Client may<br />
incur as a result of the removal or replacement of Products.<br />
8.8. Repaired or replacement Products are shipped from<br />
Seller via ground shipment. Other shipping methods are available<br />
at the sole expense of the Client.<br />
8.9. Repaired, replaced or exchanged Products will carry a<br />
warranty for a period of time equal to the greater of: (i) the<br />
remainder of the original 5-year warranty or 2-year warranty<br />
that was applicable to the repaired, replaced or exchanged<br />
Products, or (ii) six months, effective from the date the<br />
repaired, exchanged or replaced Products are shipped by<br />
Seller (the “Replacement Warranty Period”).<br />
8.10. Advanced replacement Products for Products covered<br />
under warranty may be obtained from Seller after the Belimo<br />
customer service troubleshooting process has been completed.<br />
For industrial products (such as butterfly valves), a purchase<br />
order is required. The purchase order will be credited<br />
upon the receipt and verification by Seller of the returned<br />
defective Products. For non-industrial products, an invoice will<br />
be issued and shall be due and payable is the returned<br />
Products are not received by Seller within 60 days from the<br />
date of that the replacement Products are shipped. Additional<br />
charges may apply if the nature of the problem has been misrepresented<br />
by Client.<br />
8.11. Both the conditional and unconditional warranties cover<br />
the Products only, and do NOT cover labor associated with the<br />
troubleshooting, removal or replacement of such Products.<br />
8.12. New Products ordered in an attempt to circumvent the<br />
warranty process may NOT be reimbursed if, upon receipt of<br />
returned Products, it is determined that the defect in the<br />
returned Products is actually field related, or the Products<br />
Terms and Conditions of Sale and Warranty<br />
have been returned for cosmetic reasons only.<br />
8.13. Advanced replacement Products for butterfly valve actuators<br />
may not be new, but have been verified by the Seller for<br />
electrical and mechanical operation. Such Products carry the<br />
full warranty for the entire Replacement Warranty Period.<br />
IX. No Warranty for Non-HVAC Application<br />
9.1. All Seller warranties shall extend only to HVAC use of the<br />
Products. If Products are used in non-HVAC application (e.g.,<br />
aircraft, industrial processes, etc.), Seller’s warranties shall not<br />
cover such Products. Client will be solely responsible for any<br />
damage to or malfunction of Products or for any damage<br />
resulting from such use of Products.<br />
X. Liability Disclaimer<br />
10.1. These Terms constitute the entire understanding and<br />
agreement between Seller and Client regarding the warranties<br />
that cover Products and supersedes all previous understandings,<br />
agreements, communications and representations.<br />
Seller shall not be responsible for and Client does not have<br />
any right to make any claim for, damage that occurs to any<br />
property other than Products. Seller shall in no way be<br />
responsible for any costs incurred by Client in the determination<br />
of the causes of damage to any of Client’s property, for<br />
expert opinions, or for any punitive or special, incidental or<br />
consequential damages of any kind whatsoever.<br />
10.2. Seller shall not be liable for any damage resulting from or<br />
contributed by Client or third parties acting within the scope of<br />
responsibility of Client or such third party when:<br />
1. Products are used for non-HVAC applications, such as in<br />
aircrafts, industrial processes, etc.;<br />
2. Client uses the Products without complying with applicable<br />
law or institutional regulations or Belimo data and installation<br />
sheets or Client uses the Products without following<br />
good industry practice;<br />
3. Products are used by personnel who have not received<br />
suitable instruction; or<br />
4. Products are modified or repaired without the written<br />
approval of Seller.<br />
When requested to do so, Client shall immediately release<br />
Seller in full from any possible third party claims resulting in<br />
connection with the circumstances listed above. This also<br />
applies to claims in connection with product liability.<br />
10.3. If Client becomes aware that any third party has made or<br />
appears likely to make any claim regarding Products (including,<br />
without limitation, regarding Product defects or rights infringed<br />
by Products), then Client shall immediately inform Seller and<br />
afford to Seller all assistance that Seller may require to enforce<br />
its rights and defend such claim.<br />
XI. Proper Law and Jurisdiction<br />
11.1. All sales of Products under these Terms and the warranties<br />
described herein shall be governed by the laws of the<br />
State of Connecticut, and the parties agree to submit to the<br />
exclusive jurisdiction of the Federal and state courts located in<br />
the State of Connecticut with respect to any dispute arising<br />
from the subject matter hereof. The parties hereby waive all<br />
rights to a jury trial in connection with any claims relating to the<br />
subject matter hereof.<br />
81
®<br />
Custom MFT Configuration Order Form<br />
FAX: USA Toll Free 1-800-228-8283<br />
#1 Select an Actuator<br />
(use one sheet for each unique actuator/configuration)<br />
❑ AF24-MFT US<br />
❑ AF24-MFT-S US<br />
❑ NF24-MFT US<br />
❑ LF24-MFT US<br />
❑ LF24-MFT-S US<br />
❑ AF24-MFT95 US<br />
❑ NV24-MFT US<br />
❑ NVF24-MFT US<br />
❑ NVF24-MFT-E US<br />
❑ NVFD24-MFT US<br />
❑ NVFD24-MFT-E US<br />
Control Types<br />
➁<br />
Feedback signals U 5<br />
➂<br />
Running time<br />
➃<br />
82<br />
Quantity<br />
Override control and<br />
electronic angle of rotation<br />
limiting<br />
➄<br />
❑ GMX24-MFT<br />
❑ AMX24-MFT<br />
❑ NMX24-MFT<br />
❑ LMX24-MFT<br />
❑ LRX24-MFT<br />
❑ GMX24-MFT95<br />
❑ AMX24-MFT95<br />
❑ NMX24-MFT95<br />
❑ LMX24-MFT95<br />
(-S=Auxiliary Switch)<br />
#2 Create a Custom Configuration<br />
Quantity<br />
Angle of rotation setting<br />
Deactivated (Default)<br />
➀ Activated<br />
VDC PWM Floating On/Off<br />
2 – 10 0.2 to 5.0 sec.<br />
0 – 10 0.1 to 25.5 sec.<br />
Variable 0.59 to 2.93 sec.<br />
Start .<br />
Manual triggering by pressing the pushbutton twice<br />
Automatic triggering each time the unit is powered up<br />
or by pressing the pushbutton twice.<br />
Variable<br />
Stop . Start .<br />
Stop .<br />
Position Feedback U DC 2...10 V (Default)<br />
Position Feedback U DC 0...10 V<br />
Position Feedback U<br />
150 s (Default)<br />
Name ____________________________________________________________________________________<br />
Company__________________________________________________________________________________<br />
Address __________________________________________________________________________________<br />
City ________________________________________________________ State ____ Zip________________<br />
Phone ____________________________________ Fax __________________________________________<br />
Email ____________________________________<br />
Field Labeling: LBL-MFT<br />
❑ Custom configuration labels required<br />
1-3/8” X 1-1/4” orange labels preprinted to your specifications<br />
12 label sets per sheet. Includes configuration code and wiring labels.<br />
Start DC . V (0...8 V)<br />
Finish DC . V (2...10 V)<br />
Running time s (75...300 s) (in 5 sec. increments)<br />
Note: The sound power level [dB(A)] increases<br />
when the running time is below 150 s.<br />
➁ ➄<br />
The following settings - refer to the full angle of<br />
rotation of 95º.<br />
The following settings ➁ - ➄ are automatically adapted<br />
to the effective mechanical angle of rotation.<br />
LM 35…150 s<br />
NM 45…170 s<br />
AM 90…300 s<br />
GM 90…300 s<br />
Others 75…300 s<br />
The finish must<br />
be at least 2 V<br />
above the start!<br />
Min. (min. position) = % (0...100%) (beginning of working range) default 0<br />
ZS (intermediate position) = % (0...100%) (0% = Min.; 100% = Max.) default 50<br />
Max.(max. position) = % (0...100%) (end of working range) default 100<br />
®<br />
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.
J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />
USA<br />
ACR Supply Company Inc.<br />
2719 Hillsborough Road<br />
Durham, NC 27705<br />
Phone: 919-286-2228<br />
With branches in NC<br />
Aireco Supply<br />
9120 Washington Boulevard<br />
Savage, MD 20763-0414<br />
Phone: 301-953-8800<br />
With branches in MD, VA<br />
Amcon Controls, Inc.<br />
11906 Warfield Street<br />
San Antonio,TX 78216<br />
Phone: 210-349-6161<br />
With branch in Houston, TX<br />
Applied Automation<br />
A Wilson Mohr Company<br />
3186 South Washington Street, #230<br />
Salt Lake City, UT 84115<br />
Phone: 801-486-6454<br />
Boston Aircontrols, Inc.<br />
8 Blanchard Road<br />
Burlington, MA 01803<br />
Phone: 781-272-5800<br />
Charles D. Jones Co.<br />
445 Bryant Street, Unit #1<br />
Denver, CO. 80204-4800<br />
Phone: 800-777-0910<br />
With branches in CO, MO, KS<br />
Climatic Control Co., Inc.<br />
5061 W. State Street<br />
Milwaukee, WI 53208<br />
Phone: 800-242-1656<br />
With branches in WI, IL<br />
Cochrane Supply and Engineering, Inc.<br />
30303 Stephenson Highway<br />
Madison Heights, MI 48071-1633<br />
Phone: 800-482-4894<br />
With branches in MI<br />
Columbus Temperature Control<br />
1053 E. 5th Avenue<br />
Columbus, OH 43201<br />
Phone: 800-837-1837<br />
Controlco<br />
5600 Imhoff Drive, Suite G<br />
Concord, CA 94520<br />
Phone: 925-602-7728<br />
With branches in CA<br />
Edward C. Smyers & Co.<br />
223 Fort Pitt Boulevard<br />
Pittsburgh, PA 15222-1505<br />
Phone: 412-471-3222<br />
First Source Distributors, LLC<br />
710 Peninsula Lane, Suite E<br />
Charlotte, NC 28273<br />
Phone: 800-670-5977<br />
G & O Thermal Supply<br />
5435 N. Northwest Highway<br />
Chicago, IL 60630<br />
Phone: 773-763-1300<br />
With branches in IL<br />
Industrial Controls Distributors LLC<br />
1776 Bloomsbury Avenue<br />
Wanamassa, NJ 07712<br />
Phone: 800-631-2112<br />
With branches in<br />
KY, ME, NC, NY, OH, PA, TN, MA, GA, WI, IL<br />
Interstate HVAC Controls<br />
30 Vineland Street<br />
Brighton, MA 02135<br />
Phone: 617-782-9000<br />
Jackson Controls<br />
1708 E. 10th Street<br />
Indianapolis, IN 46201<br />
Phone: 317-231-2200<br />
M & M Controls<br />
9E West Aylesbury Road<br />
Timonium, MD 21093<br />
Phone: 410-252-1221<br />
Meier Supply<br />
123 Brown Street<br />
Johnson City, NY 13790<br />
Phone: 607-797-7700<br />
With branches in NY, PA<br />
MICONTROLS, Inc.<br />
6516 5th Place South<br />
Seattle, WA 98124<br />
Phone: 800-877-8026<br />
With branches in WA, OR<br />
Minvalco, Inc.<br />
3340 Gorham Avenue<br />
Minneapolis, MN 55426-4267<br />
Phone: 952-920-0131<br />
With branches in MN<br />
RSD/Total Control<br />
26021 Atlantic Ocean Drive<br />
Lake Forest, CA 92630<br />
Phone: 949-380-7878<br />
With branches in<br />
CA, NV, OR, AK, AZ, ID, UT, WA<br />
Saint Louis Boiler Supply, Co.<br />
617 Hanley Industrial Court<br />
St. Louis, MO 63144<br />
Phone: 314-962-9242<br />
South Side Control Supply, Co.<br />
488 N. Milwaukee Avenue<br />
Chicago, IL 60610-3923<br />
Phone: 312-226-4900<br />
With branches in IL, IN<br />
Stromquist and Company<br />
4620 Atlanta Road<br />
Smyrna, GA 30080<br />
Phone: 404-794-3440<br />
With branch in FL<br />
Temperature Control Systems<br />
10315 Brockwood Road<br />
Dallas, TX 75238<br />
Phone: 214-343-1444<br />
With branches in OK, TX<br />
Tower Equipment Co., Inc.<br />
1320 West Broad Street<br />
Stratford, CT 06615<br />
Phone: 800-346-4647<br />
Twinco Supply Corporation<br />
55 Craven Street<br />
Huntington Station, NY 11746-2143<br />
Phone: 800-794-3188<br />
With branches in NY<br />
Belimo Platinum Distributors<br />
Airex<br />
C - 5 Sandhill Court<br />
Brampton, ON, L6T 5J5<br />
Phone: 905-790-8667<br />
Baymar Supply Co.<br />
3200 Jefferson Boulevard<br />
Windsor, ON, N8T 2W8<br />
Phone: 519-974-5800<br />
With branch in London, ON<br />
Le Groupe Master<br />
1675 de Montarville<br />
Boucherville, QC, J4B 7W4<br />
Phone: 514-527-2301<br />
With branches across Eastern Canada<br />
O’Dell Associates Inc.<br />
#3 - 1038 Cooke Boulevard<br />
Burlington, ON, L7T 4A8<br />
Phone: 905-681-3901<br />
Prokontrol<br />
1989 Michelin<br />
Laval, QC, H7L 5B7<br />
Phone: 450-973-7765<br />
With branches in Ville Vanier and Ontario<br />
Refrigerative Supply<br />
3958 Myrtle Street, Burnaby, BC, V5C 4G2<br />
Phone: 604-435-7151<br />
With branches in British Columbia,<br />
Alberta, Saskatchewan,Manitoba<br />
Regal Controls<br />
1156 Kingsway<br />
Vancouver, BC V5V 3C8<br />
Phone: 604-879-6357<br />
With branch in Langley<br />
Regulvar Laval<br />
1985 Boul Industriel Laval, QC, H7S-1P6<br />
Phone: 450-629-0435<br />
With branches in Sherbrooke,<br />
St. Hubert, Lachine, Quebec City<br />
Regulvar Ottawa Inc.<br />
170 Laurier Ax West Suite 714<br />
Ottawa, Ontario, K1P-5V6<br />
Phone: 613-565-2129<br />
With branch in Gatineau<br />
Sinclair Supply<br />
10914 - 120 Street<br />
Edmonton, AB, T5H 3P7<br />
Phone: 780-452-3110<br />
With branches in British Columbia,<br />
Alberta, Saskatchewan<br />
SCI<br />
3311 Boul Industriel<br />
Laval, QC, H7L 4S3<br />
Phone: 450-668-8866<br />
Wiles & Legault<br />
#5 - 505 Industriel Avenue<br />
Ottawa, ON, K1G 0Z1<br />
Phone: 613-747-1867<br />
Yorkland Controls<br />
2689 Steeles Avenue, W.<br />
Downsview, ON, M3J 2Z8<br />
Phone: 416-661-3306<br />
With branch in Mississauga<br />
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA<br />
CANADA
HVAC Division<br />
t. (81) 8333-7738 · (81) 8333-7717<br />
e. info@duralitte.com.mx<br />
www.duralitte.com.mx
Belimo worldwide: www.belimo.com<br />
BELIMO Americas<br />
USA Locations, 43 Old Ridgebury Road, Danbury, CT 06810<br />
Tel. 800-543-9038, Fax 800-228-8283, marketing@us.belimo.com<br />
1675 East Prater Way, Suite 101, Sparks, NV 89434<br />
Tel. 800 987-9042, Fax 800-987-8875, marketing@us.belimo.com<br />
Canada Locations, 14/16 – 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8<br />
Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com<br />
Latin America Customer Service, Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com