■ Technical specifications<br />
Definitions<br />
Process A process object (PO) is a synonym for an operable<br />
object (PO) and observable block with approx. 30 to 50 individual<br />
OS variables (parameters). Thus the quantity framework<br />
data of the engineering system can be compared<br />
with those of the operating system.<br />
OS variable An OS variable or parameter is a defined memory location<br />
required for operating and monitoring with the<br />
operator system; values can be written into it and read<br />
from it (e.g. setpoint, actual value etc.). A PO usually<br />
has several OS variables (which can be operated and<br />
monitored).<br />
Licensing As of SIMATIC <strong>PCS</strong> 7 V7.0, the OS software will only be<br />
licensed on the basis of POs. This significantly simplifies<br />
calculation of the required license. An average of<br />
50 OS variables will be calculated for a PO, where<br />
motors, valves etc. require fewer variables, and controls,<br />
dosing functions etc. require more variables.<br />
Checking of the license will also be carried out using<br />
the POs, and additionally includes checking of the total<br />
number of OS variables used.<br />
Process<br />
objects<br />
OS variables (approx.)<br />
250 12500<br />
1000 50000<br />
2000 100000<br />
3000 150000<br />
5000 250000<br />
8500 425000<br />
© Siemens AG <strong>2007</strong><br />
Operator system<br />
1) If every OS client has access to all OS servers/pairs of servers<br />
Siemens <strong>ST</strong> <strong>PCS</strong> 7 · <strong>March</strong> <strong>2007</strong><br />
Introduction<br />
OS quantity framework<br />
Max. number of OS servers / pairs 12<br />
of servers<br />
Max. number of automation systems 64<br />
per OS server / pair of servers<br />
Max. number of OS clients in multiclient<br />
mode 1) 32<br />
(per multi-user<br />
system)<br />
Max. number of monitors per 4<br />
operator station with multi-channel<br />
operation<br />
Max. number of OS areas 64<br />
Max. number of windows per 1 to 16 (adjustable)<br />
monitor<br />
Number of trends per trend window 10<br />
Selection time for OS area display < 2 s<br />
(100 process symbols)<br />
Max. number of process objects:<br />
• Per OS single station 5000 PO<br />
• Per OS server 8500 PO<br />
Max. number of configurable 50000<br />
messages per server<br />
Number of process tags<br />
• Per OS single station Approx. 3000<br />
• Per OS server Approx. 5000<br />
• Per multi-user system Approx. 60000<br />
Integral high-performance<br />
archive system<br />
(cyclic buffer), based on Microsoft<br />
SQL server, for:<br />
• Process value archiving (per Approx.1000/s<br />
OS server / single station)<br />
• Message archiving (per<br />
Steady-state load approx. 10/s<br />
OS server / single station) Message peak approx. 3000 / 4 s<br />
Long-term archiving<br />
• Process value archiving with Process values from up to<br />
StoragePlus<br />
4 single stations, servers or pairs<br />
of servers<br />
- Process values of one server Approx. 1000/s<br />
- Process values of all servers Approx. 1600/s<br />
• Process value archiving with Process values from up to<br />
central archive server (CAS) 11 servers or pairs of servers<br />
- Process values of one server Approx. 1000/s<br />
- Process values of all servers Approx. 10000/s<br />
5/3<br />
5