IPVB Power Venter<br />

EXSTREAM<br />

P E R F O R M A N C E<br />

D EVELOPED AND MANUFACTURED BY EXHAUSTO<br />

IPVB-ECO Power Venter with Economizer<br />

EXSTREAM<br />

P E R F O R M A N C E<br />

D EVELOPED AND MANUFACTURED BY EXHAUSTO<br />

• True inline exhaust fan in compact design<br />

• High-efficiency aluminum centrifugal impeller (stainless steel in 620-models)<br />

• Made in 316SS <strong>for</strong> indoor <strong>and</strong> outdoor installation<br />

• Variable speed, direct drive, TEFC motor<br />

• 7 sizes available, ETL <strong>and</strong> ETLc listed to UL378<br />

• True inline exhaust fan in compact design<br />

• High efficiency cast alu impeller (stainless steel in 620-models)<br />

• Made in 316SS<br />

• Variable speed, direct drive, TEFC motor<br />

• Economizer coil in copper or stainless steel<br />

• 7 sizes available, ETL <strong>and</strong> ETLc listed to UL378<br />

IPVB 620­5ECO IPVB 620­7ECO IPVB 620­10ECO<br />

Power Supply VAC 3 x 400­480<br />

Amperage Amp 7.5 11.3 15.0<br />

Motor Output HP (kW) 5.0 (3.7) 7.5 (5.6) 10.0 (7.4)<br />

RPM 1,350 (45) 1,500 (51) 1,740 (60)<br />

Weight Lbs (kg)<br />

IPVB 300 IPVB 300 IPVB 350 IPVB 400 IPVB 500<br />

Power Supply VAC 1x120 1x220­240 3x200­240 / 3x400­480<br />

Amperage Amp 5.8 2.9 3.1 / 1.7 6.5 / 2.9 9.0 / 4.0<br />

Motor Output HP (kW) 0.5 (0.35) 0.5 (0.35) 1.0 (0.75) 2.0 (1.5) 3.0 (2.25)<br />

RPM 1600 1400 1720 1720 1720<br />

Weight Lbs (kg) 34 (75) 34 (75) 43 (94) 58 (128) 83 (183)<br />

Duct Connections Inch (mm) 12 (300) 12 (300) 14 (350) 16 (400) 20 (500)<br />

Max Capacity CFM (m 3 /h) 1,350 (2,300) 1,200 (2,000) 1,200 (2,000) 3,600 (6,100) 5,400 (8,700)<br />

IPVB 300 IPVB 300 IPVB 350 IPVB 400 IPVB 500<br />

Power Supply VAC 1x120 1x220­240 3x200­240 / 3x400­480<br />

Amperage Amp 5.8 2.9 3.1 / 1.7 6.5 / 2.9 9.0 / 4.0<br />

Motor Output HP (kW) 0.5 (0.35) 0.5 (0.35) 1.0 (0.75) 2.0 (1.5) 3.0 (2.25)<br />

RPM 1600 1400 1720 1720 1720<br />

Weight Lbs (kg) 34 (75) 34 (75) 43 (94) 58 (128) 83 (183<br />

Duct Connections Inch (mm) 12 (300) 12 (300) 14 (350) 16 (400) 20 (500)<br />

Max Capacity CFM (m 3 /h) 1,000 (1,700) 890 (1,510) 1,750 (2,975) 3,000 (5,100) 4,750 (8,000)<br />

Max MBH * (kW) 2,000 (580) 1,800 (530) 3,500 (1,000) 6,000 (1,750) 9,000 (2,600)<br />

Duct Connections Inch (mm) 24 (610)<br />

IPVB 620­5 IPVB 620­7 IPVB 620­10<br />

Power Supply VAC 3x400­480<br />

Amperage Amp 7.5 11.3 15.0<br />

Motor Output HP (kW) 5.0 (3.7) 7.5 (5.6) 10.0 (7.4)<br />

Max RPM (Hz) 1,350 (45) 1,500 (51) 1,740 (60)<br />

Weight Lbs (kg) 434 (240) 434 (240) 444 (202)<br />

Duct Connections Inch (mm) 24 (610)<br />

Max Capacity CFM (m 3 /h) 10,000 (17,000) 11,500 (19,500) 13,500 (22,900)<br />

Max Capacity CFM (m 3 /h) 9,000 (15,000) 10,000 (17,000) 12,000 (20,500)<br />

Max MBH * (kW) 18,000 (5,275) 20,000 (5,860) 24,000 (7,000)<br />

* Depending on boiler type<br />