SOLENOID/PILOT – ELECTRICAL OPERATOR SPECIFICATIONS<br />
Solenoid/Pilot actuated Series V & T valves are available with a variety of different solenoids for both nonhazardous and hazardous<br />
locations. Basic details of actuators are listed below. For additional data consult factory.<br />
NONHAZARDOUS LOCATION SOLENOIDS (Inline or upright style)<br />
Suffix Protection Area Classification Certification Ingress<br />
Identification Classification and (Gas Grouping) (Conformance) Protection<br />
HAZARDOUS LOCATION SOLENOIDS (upright style only)<br />
Suffix Protection Area Classification Certification Ingress<br />
Identification Classification and (Gas Grouping) (Conformance) Protection<br />
V-3.7<br />
None General Purpose Indoor & Outdoor CSA NEMA 1,2,3<br />
or<br />
-U<br />
-HC General Purpose Indoor & Outdoor CSA NEMA 4;<br />
-HCC IP65<br />
-XX Hazardous Locations Class I, Division 2 (A & B) UL NEMA 7 & 9<br />
Class I, Division 1 (C & D) CSA<br />
Class II, Division 1 (E,F,G)<br />
-3567 Hazardous Locations Class I, Division 2 (A & B) UL NEMA 7 & 9<br />
Class I, Division 1 (C & D) CSA<br />
Class II, Division 1 (E,F,G)<br />
-XN (d) Flameproof Zones 1 & 2 ATEX IP66<br />
(IIB+H 2 ) Category 2G<br />
T4<br />
-LB-XN (d) Flameproof Zones 1 & 2 ATEX IP66<br />
(IIB+H 2 ) Category 2G<br />
T6<br />
-XDAS (d) Flameproof Zones 1 & 2 ATEX IP66 & IP67<br />
or (IIC) Category 2G<br />
-XDAT<br />
-XMAA (m) Encapsulation Zones 1 & 2 ATEX IP66 & IP67<br />
or (e) Increased Safety (II) Category 2G<br />
-XMAE<br />
or<br />
-XMAF<br />
or<br />
-XMAG<br />
XMFA (m) Encapsulation Zones 1 & 2 ATEX IP66 & IP67<br />
or (e) Increased Safety (II) Category 2G<br />
-XMFE<br />
or<br />
-XMFF<br />
or<br />
-XMFG<br />
-HC-XISC Hazardous Locations Class I, Groups (A,B,C,D) Factory Mutual NEMA 4<br />
-HCC-XISC Class II, Groups (E,F,G) CSA<br />
Class III, Division 1<br />
-HC-XISX6 (ia) Intrinsic Safe Zones 0, 1 and 2, ATEX IP65<br />
-HCC-XISX6 (IIC) Category 1G<br />
T6<br />
-XIFA (ib) Intrinsic Safe Zones 1 & 2 ATEX IP66 & IP67<br />
or (IIB) Category 1G<br />
-XIFE<br />
or<br />
-XIFF<br />
* See page V-3.5 for more detailed voltage/coil data.<br />