7<br />
Dilatation belts MIRELON<br />
After the floor has been laid, the dilatation issue must also be handled as regards<br />
the connection of the tiling with the lining or baseboard. Special dilatation<br />
profiles designed for this purpose can be used here; silicon putty is also an option.<br />
(profiles Schluter are being distributed e.g. firm OSTAV s.r.o., Cihelní 99, Ostrava,<br />
tel. 069/661 90 93).<br />
Dilatation joint must be performed for larger surfaces as well. Maximum area of the<br />
dilatation unit is 25 m2. Length of the dilatation unit should not exceed 8 m and the<br />
mutual ratio of sides 1:2. Choice of dilatation joints is in accordance with the<br />
ground plan of the room. Ground plans in shape of L, Z or T divides on rectangular or<br />
square fields.<br />
Dilatation joint is being made into spreading concrete layer even in the tiles<br />
itself. In tiles this can be done with elastic silicone or special dilatation<br />
profiles ( e.g. Schluter DILEX-BWB – distributes OSTAV s.r.o, Ostrava ). In narrow,<br />
long rooms ( e.g. corridors ) we recommend max. length of diagonal for one dilatation<br />
area 7m.<br />
Profile Schluter – DILEX – MP+MPV profile Schluter – DILEX – EP+BWB<br />
Dilatation joint must be done in the whole layer of spreading concrete (as in picture<br />
above ) i.e. even under dilatation profile which is installed in the tiles. Suitable<br />
material is e.g. mirelon belts thick 2 x 8 mm. Dilatation joint must be done through<br />
all the width of the room, i.e. it without interrupting connected on the perimeter<br />
dilatation.<br />
Heating cables and mats ECOFLOOR must not lead across dilatation joints. If the cold<br />
connections lead across the dilatation joints, these must be put freely in the<br />
protection tube.