16 PT/03/BD1076/R Revision 2<br />

FIGURE 8.1 OPERATOR SCREEN FOR ISBS SYSTEM AS<br />

INSTALLED AT PLANT HAMMOND<br />

9 UNIT OPTIMISER<br />

The unit optimiser is the new software that was developed within the project to resolve<br />

potentially conflicting advice from different individual optimisers. The unit optimisation<br />

process was developed by E.ON UK’s Dr I Mayes.<br />

If several local optimisers give conflicting control settings for the unit then the total unit<br />

costs need to be considered to optimally resolve the situation. Whereas each local<br />

optimiser has it’s own cost function to minimise and only has knowledge of it’s own local<br />

restricted environment, the unit optimiser has to integrate the advice from all the local<br />

optimisers to produce an overall control strategy. In order to do this some means of<br />

compromising individual advice must be found. Since the objective functions for the local<br />

optimisers involve different high-level plant variables a common factor needs to be found<br />

to enable appropriate recommendations to be made. This factor must be the total unit costs<br />

and a unit cost function has to be defined in terms of high level plant variables such as<br />

NOx, carbon in ash, boiler efficiency, etc. It is important that costs can be associated with<br />

the high-level plant variables otherwise it is not possible to fully define a unit cost<br />

function.