System design<br />
6. Check ampere capacity of each string of inverter, select size<br />
of blocking diode to be 30 % larger than string short circuit<br />
current with diode max voltage more than 2 times of max<br />
system voltage.<br />
8. Select proper wire size so voltage drop for DC side is less<br />
than 3%<br />
8.1 Select wire size between each string to the combiner box<br />
to enable less than 1% voltage drop<br />
8.2 Select wire size between the combiner box to control<br />
box / inverter to enable less than 2% voltage drop<br />
9. Select proper wire size so voltage drop for AC side is less<br />
than 3%<br />
10. Select size of disconnect switch both DC and AC side to<br />
proper rating