Mounting and operating instructions <strong>AMTRON</strong> R○ X-<strong>50</strong><br />
M-Bus loop<br />
The following variables are shown or set in the M-Bus loop:<br />
M-bUS<br />
Nr 1, 2 bAud 2400<br />
Adr 0 ... 2<strong>50</strong><br />
Nr 1 bAud 2400<br />
Nr 2 bAud 2400<br />
Ac1 0...255<br />
Ac2 0...255<br />
bAud 300<br />
bAud 2400<br />
CONFIG loop (Configuration)<br />
S-Edit<br />
S-Edit<br />
S-Edit<br />
The following variables are shown or set in the configuration loop:<br />
CONFIG<br />
SMU 1.55 K/°R<br />
Rem 60 s<br />
Ftr 1<br />
Loc USEr<br />
S-Edit<br />
S-Edit<br />
S-Edit<br />
S-Edit<br />
RES CANCEL S-Edit<br />
SMU 1.55 K 0 ... 2.99 K/°R S-Edit<br />
Primary M-Bus address<br />
Baud rate for M-Bus (function, when card is present)<br />
Baud rate for M-Bus (Opto & M-Bus #2 card)<br />
Number of accesses over M-Bus 1<br />
Number of accesses over M-Bus 2<br />
Possible baud rates<br />
∆T, low flow cut off<br />
Rem = time of display of instantaneous values<br />
Filter-number (0 … 20)<br />
Activated operating mode (lock level)<br />
Reset of alarms and counters<br />
Temperature difference below which no further energy is<br />
counted.<br />
The unit for ºC is K and for ºF it is ºR<br />
VD 3-248 e 03.2006 18 Aquametro AG