Mounting and operating instructions <strong>AMTRON</strong> R○ X-<strong>50</strong><br />

Error messages, alarms<br />

In case of failure the message “alarm” is displayed overlaying the numbers in the display. The cause for the error can<br />

be found in the Information loop based on a short message.<br />

Message Error / Alarm Possible cause Action<br />

th-ERROR Error temperature<br />

warm side, no<br />

measurement is<br />

possible<br />

tc-ERROR Error temperature cold<br />

side, no measurement<br />

is possible<br />

SYSt-Error Memory problem<br />

EEPROM<br />

th-ALArM Temperature warm<br />

side outside the<br />

permissible measuring<br />

range<br />

tc-ALArM Temperature cold side<br />

outside the permissible<br />

measuring range<br />

dt-ALArM Temperature<br />

difference outside the<br />

permissible measuring<br />

range<br />

Data back-up<br />

The device data is saved in the EEPROM as follows:<br />

• Wrong installation of the<br />

sensor<br />

• Disconnection/ short<br />

circuit of the sensor<br />

cables<br />

See above See above<br />

• Control the wiring<br />

• Control the disconnected<br />

sensor cables with an<br />

Ohmmeter<br />

• If OK control the input<br />

with a resistor:<br />

Pt 100 100 - 1<strong>50</strong>Ω<br />

Pt <strong>50</strong>0: <strong>50</strong>0 - 620Ω<br />

Component-/ device problem Send back device for an<br />

inspection<br />

Temperature of the heating Check the actual<br />

circuit is to high or to low temperature in the menu<br />

InStAnt with the temperature<br />

in the menu InPutS<br />

See above See above<br />

• Temperature difference of<br />

the heating circuit is to<br />

high or negative<br />

• Problem of the sensor<br />

• Battery unit: once a day (23.59)<br />

• Mains unit: All data remains on power failure when the internal battery is present.<br />

• Mains unit: If the internal battery is missing: every complete hour.<br />

Recalibration/auditing<br />

Check the actual<br />

temperature difference in the<br />

menu InStAnt with the<br />

temperature in the menu<br />

InPutS<br />

A data logger (EEPROM), in which important settings are stored, is located on the terminal module of the totaliser. This<br />

configuration memory simplifies recalibration and auditing of the unit.<br />

A replacement unit with the correct calibration (verification) parameters (pulse value, mounting side, etc.) has just to be<br />

plugged in. Other parameters do not have to be re-entered. The field wiring remains connected.<br />

Procedure<br />

Calibrated instruments are to be returned to the factory for recalibration once the expiry date has passed.<br />

The device has the advantage that only the totaliser module has to be returned. The field wiring can remain connected.<br />

Due to the integrated configuration memory in the connecting board, the measuring point data remain (this does not<br />

apply to calibration data) .<br />

VD 3-248 e 03.2006 22 Aquametro AG